2.2.3 Chassis Ground
Always connect chassis ground to battery negative. Use 1.5mm² or more.
RISK OF ELECTRICAL SHOCK. OPERATION OF THE INVERTER WITHOUT A PROPER GROUND
CONNECTION MAY RESULT IN AN ELECTRICAL SAFETY HAZARD. ENSURE PROPER GROUND
CONNECTION IS MADE DURING INSTALLATION. FOR FIXED AND/OR TRANSPORTABLE
(VEHICLE) INSTALLATIONS, INSTALL ACCORDING TO APPROPRIATE AS/NZS STANDARD.
2.2.4 DC Input Connection
Prior to installation:
DC Supply cables should be as short as possible (no longer than the values shown in table
2.2.4.1 & 2.2.4.2)
The size of the cable should be thick enough to maintain a voltage drop of less than 2%
when carrying the maximum input current. This will help prevent frequent low-input voltage
warnings and shutdown.
The following sizes of cables and fuses are recommended for connection of the supply
batteries to inverter, see table 2.2.4.1 & 2.2.4.2 over the page for suitable cable sizing for
your installation.
Ensure lugs suitable to the selected cable size and to the inverter terminals are used, refer
to table 2.2.4.3 over the page for suitable lug size with reference to your chosen cable size.