Product Manual

27
3 SYSTEM CONFIGURATION
3.4 Confi gure Distribution Box - Load Disconnect Settings
The Confi gure TVMS Disconnect page allows you to set the Disconnect Trigger for the
RedVision system.
First the trigger type must be chosen from the drop down ‘Disconnect When’ menu, the
default Trigger Type is ‘Never’.
• Always - Always Disconnected
• Voltage - Triggers based on the voltage at the Batt + terminal on the Distribution Box
• BMS Voltage - Triggers on voltage of the Auxiliary Battery as measured by the Manager
• BMS SoC - Triggers on SoC of the Auxiliary Battery as measured by the Manager
• Never - Always Connected
Next the Disconnect and Reconnect levels must be set, based on the method selected.
The App will ensure that Disconnect is always set 5% or 0.5V lower than Reconnect,
depending on the trigger type chosen.
Tap SAVE to confi rm settings.
1
2
From the Main Menu:
1. Tap the Distribution
Box Button, then
2. Tap the Load
Disconnect Settings
Button