2 INSTALLATION GUIDE
2.6 Battery & Charger Connection
2.6.1 Battery Connection
Wire the Auxiliary Battery Positive (+) to the Distribution Box through the supplied
80A MIDI fuse - this fuse should be mounted as close as practical the battery.
Refer to Section 2.3 for cable sizing.
Wire the distribution box Battery Ground (-) to either a suitable grounding point
(i.e. chassis or earth stud) or connect directly to the GND (
) terminal of the
Manager’s battery sensor.
2.6.2 Charger Connection (Manager 15 or 30)
The Manager should be mounted as close as possible to the Distribution Box.
Connect the Battery Management System’s battery output positive (+) and
Ground (
) to the Distribution Box Charger (+) and Ground (-) connections.
Refer to Section 2.3 for cable sizing.
The Distribution Box includes a 50A MIDI fuse to protect the charging circuit (the
maximum charging current is 40A). Refer to Section 2.5 for details.
Auxiliary Battery
Supplied
Fuse
BMS
Battery Sensor