Regency Horizon™ HZ42E Gas Fireplace Owners & Installation Manual MODELS: HZ42E-NG Natural Gas HZ42E-LP Propane www.regency-fire.com WARNING: FOR YOUR SAFETY If the information in these instructions are not followed exactly, What to do if you smell gas: a fire or explosion may result causing property damage, Do not try to light any appliance Do not touch any electrical switch: personal injury or loss of life. do not use any phone in your FOR YOUR SAFETY building.
To the New Owner: Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The HZ42E has been designed to provide you with all the warmth and charm of a fireplace at the flick of a switch. The model HZ42E has been approved by Warnock Hersey/Intertek for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow.
MANUFACTURED MOBILE HOME REQUIREMENTS INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE This Regency® product has been tested and listed by Warnock Hersey/Intertek as a Direct Vent Wall Furnace to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88a-2007 / CSA 2.33a-2007 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN / CGA 2.17-M91.
TABLE OF CONTENTS SAFETY LABEL Copy of Safety Decal .....................................................5 REQUIREMENTS MA Code - CO Detector.................................................6 DIMENSIONS Unit Dimensions ............................................................7 Pilot Adjustment ...........................................................34 Gas Pipe Pressure Testing ..........................................34 886 S.I.T. Valve Description.........................................
SAFETY LABEL This is a copy of the label that accompanies each HZ42E-NG and HZ42E-LP Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. NOTE: Regency® units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
REQUIREMENTS MA Code - CO Detector (for the State of Massachusetts only) 5.08: Modifications to NFPA-54, Chapter 10 (2) Revise 10.8.
DIMENSIONS UNIT DIMENSIONS 47” (1194mm) 18-5/8” (473mm) 15-5/8” (397mm) ½” (13mm) 1-½” (38mm) 41-3/16”” (1046mm) 1-½” (38mm) 28-7/8” (733mm) 21-3/16” (538mm) ½” (13mm) 23-5/8” (600mm) 12-7/8” (327mm) 36” (914mm) 36-7/8” (937mm) 30” (762mm) 38”” (965mm) 14-5/32” (360mm) 48-3/4” (1238mm) HZ42E Regency Horizon™ Gas Fireplace 7
INSTALLATION IMPORTANT MESSAGE SAVE THESE INSTRUCTIONS The HZ42E Direct Vent Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fireplace is installed in compliance with manufacturers instructions and all applicable codes.
INSTALLATION INSTALLATION CHECKLIST 1) Locate appliance a) Room location (Refer to "Locating Your Gas fireplace" section) b) Clearances to Combustibles (Refer to "Clearances" section) c) Mantle Clearances (Refer to "Mantel Clearances" section) d) Framing & Finishing Requirements (Refer to "Framing & Finishing" section) e) Venting Requirements (Refer to "Venting" section) This includes: 1) Clocking the appliance to ensure the correct firing rate (rate noted on label 26,000 Btu/h (NG), 24,500 Btu/h (LP) afte
INSTALLATION CLEARANCES The clearances listed below are Minimum distances unless otherwise stated: A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions. Caution Requirements The top, back and sides of the fireplace are defined by standoffs.
INSTALLATION MANTEL CLEARANCES 14 12 10 8 6 4 2 0 Due to the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in the diagram on the right. 26 12" (305mm) Note: Ensure the paint that is used on the mantel and the facing is "High Quality" or the paint may discolour.
INSTALLATION UNIT ASSEMBLY PRIOR TO INSTALLATION The Nailing Strips and the 2 Standoffs must be correctly positioned and attached before unit is slid into position. NAILING STRIPS The nailing strips come attached to the unit. There is 1 plate on each side, 1 on the top, and one on the bottom that can be folded out as required. The top and side nailing strips are secured to the framing. The bottom nailing strip is secured to the unfinished floor - if installing the unit directly on the floor.
INSTALLATION FRAMING DIMENSIONS Framing Dimensions Description A B Framing Height Framing Width C* Framing Depth* D E F G H I J K Minimum Height to Combustibles Corner Wall Depth Corner Facing Wall Width Vent Centerline Height Non-combustible facing height Gas Connection Opening Height Gas Connection Height Gas Connection Inset L Gas Connection Opening Width HZ42E 37-1/4” (946mm) 47 - 1/2" (1207mm) C1 Horizontal Vent 18 - 3/4" (476mm) C2 Vertical Vent 22" (559mm) Vertical rise -terminating horizon
INSTALLATION NON-COMBUSTIBLE REQUIREMENTS All four pieces (top, 2 sides, bottom) are now supplied to meet the non combustible requirements. Previously only the top was supplied Metal Stud Metal Stud 16" (406mm) 4-3/8" (111mm) 34 -1/4" (870mm) Non-combustible Note: Calcium Silicate is 1/2' thick 41-3/8” 21-1/2” 18-3/4” (467mm) If finishing the wall above the unit with materials such as tile, brick, marble, etc. non-combustible board available from the building supply store can be used.
INSTALLATION FRAMING & FINISHING 1) Frame in the enclosure for the unit with framing material. IMPORTANT: The framed opening must be of non-combustible material. Note: When constructing the framed opening, please ensure there is access to install the gas lines when the unit is installed.
INSTALLATION Note: Depending on the material used for finishing, the nailing strips must be set accordingly so that the finished material is always at the 1-1/2" edge of the flange.
INSTALLATION VENT RESTRICTOR POSITION Vent restriction is required for certain venting installations, see the diagrams in the "Venting Arrangements" section to determine if they are required for your installation. The Vent Restrictor plate is located on the inside top of the firebox. To set the vent restriction as indicated in the venting arrangements diagrams, refer to the following instructions; 1) Remove the glass door - see instructions in this manual.
INSTALLATION EXTERIOR VENT TERMINATION REQUIREMENTS Minimum Clearance Requirements Canada1 USA2 A Clearance above grade, veranda, porch, deck, or balcony 12"(30cm) 12"(30cm) B Clearance to window or door that may be opened 12"(30cm) 9" (23cm) C Clearance to permanently closed window * * D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61cm) from the center line of the terminal (check with the local code) 19"(48cm) 19"(48cm) E C
INSTALLATION 4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART ONLY Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
INSTALLATION Description Simpson Selkirk Direct Vent Pro® Direct Temp™ American Metal Products® Metal-Fab™ Security ICC Excel Sure Seal Secure- Vent® Direct Amerivent Direct Attic Insulation Shield 12” 46DVA-IS N/A@ FPI N/A 4DAIS12 N/A SV4RSA N/A Attic Insulation Shield - Cold Climates 36” N/A N/A 4DAIS12 N/A N/A TM-4AS Basic Horizontal Termination Kit (A) Disc.
INSTALLATION VENTING INTRODUCTION The HZ42E uses the "balanced flue" technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney. Note: These flue pipes must not be connected to any other appliance.
INSTALLATION HORIZONTAL TERMINATIONS FLEX VENT 4" X 6-5/8" These venting systems, in combination with the HZ42E Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Warnock Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination Locations" section. Regency® Direct Vent (Flex) System Termination Kits includes all the parts needed to install the HZ42E using a flexible vent.
INSTALLATION HORIZONTAL TERMINATIONS RIGID PIPE 4" X 6-5/8" The minimum components required for a basic horizontal termination are: 1 1 1 1 1 Horizontal Termination Cap 45o Elbow Rigid Pipe Adaptor (510-994) Wall Thimble Length of pipe to suit wall thickness (see chart) Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap.
INSTALLATION HORIZONTAL TERMINATIONS RIGID PIPE 4" X 6-5/8" The diagrams below shows examples of horizontal termination arrangements using one, two, or three 90o elbows (two 45o elbows equal one 90o elbow) 1) A maximum of three 90o elbows are permitted (not including the starting 45o elbow at the flue collar when using rigid venting). 2) Minimum distance between elbows is 1 ft. (305mm). • • • • • • Maintain clearances to combustibles as listed in the "Clearances" section.
INSTALLATION Horizontal Venting with Two (2) 90o Elbows Horizontal Venting with Three (3) 90o Elbows One 90o elbow = Two 45o elbows. One 90o elbow = Two 45o elbows. Option V H + H1 A) 1' Min. 3' Max. B) 2' Min. 4' Max. C) 3' Min. 5' Max. D) 4' Min. 6' Max. E) 5' Min. 7' Max. F) 6' Min. 8' Max. With these options, maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal. Option H V H+H1+H2 A) 1' Max. 1' Min. 3' Max.
INSTALLATION Horizontal Venting with Three (3) 90o Elbows One 90o elbow = Two 45o elbows. Option V H V+V1 H+H1 A) 2' Min. 1' Max. 3' Min. 4' Max. B) 3' Min. 2' Max. 4' Min. 5' Max. C) 4' Min. 3' Max. 6' Min. 6' Max. D) 5' Min. 4' Max. 8' Min. 7' Max. E) 6' Min. 5' Max. 10' Min. 8' Max. F) 7' Min. 6' Max. 12' Min. 9' Max. With these options, maximum total pipe length is 30 feet with minimum of 12 feet total vertical and maximum 9 feet total horizontal.
INSTALLATION VENTING ARRANGEMENT FOR VERTICAL TERMINATIONS Horizontal (Feet) 0 The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90o elbows, with Rigid Pipe Venting Systems. 2 4 6 8 10 12 14 18 16 40 Two 45o elbows equal to one 90o elbow. Maximum of four 45o elbows allowed, not including the starting 45o elbow at the flue collar. • Vent must be supported at offsets. • Minimum distance between elbows is 1 ft.
INSTALLATION VERTICAL TERMINATIONS RIGID PIPE 4" X 6-5/8" The minimum components required for a basic vertical termination are: 1 1 1 1 1 1 1 Vertical Termination Cap 45o Elbow Rigid Pipe Adaptor (510-994) Ceiling Firestop Flashing Storm Collar Length of pipe to suit wall thickness (see chart) Vertical Terminal Storm Collar Flashing Galvanized pipe is desirable above the roofline due to its higher corrosion resistance.
INSTALLATION VERTICAL TERMINATIONS RIGID PIPE 4" X 6-5/8" • • • • • • • Two 45o elbows equal to one 90o elbow. Maximum of four 45o elbows allowed, not including the starting 45o elbow at the flue collar. Vent must be supported at offsets. Minimum distance between elbows is 1 ft. (305mm). Maintain clearances to combustibles as listed in the "Clearances" section. Horizontal vent must be supported every 3 feet. Firestops are required at each floor level and whenever passing through a wall.
INSTALLATION Vertical Venting with Three (3) 90o Elbows One 90o elbow = Two 45o elbows. Option A) B) C) D) E) H 1' Max. 2' Max. 3' Max. 4' Max. 5' Max. V 1' Min. 2' Min. 3' Min.' 4' Min. 5' Min. H + H1 3' Max. 4' Max. 5' Max. 6' Max. 7' Max. V + V1 3' Min. 5' Min. 7' Min. 9' Min. 11' Min. With these options, max. total pipe length is 30 feet with min. of 11 feet total vertical and max. 7 feet total horizontal. Please note min. 1 foot between 90 o elbows is required.
INSTALLATION UNIT INSTALLATION WITH HORIZONTAL TERMINATION 5) Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection. 4" X 6-5/8" VENTING (Rigid Vent Systems) Note: For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty.
INSTALLATION 4" X 6-5/8" VENTING (Flex Vent Systems) Minimum Vent Clearances to Combustibles * Clearances noted below must be maintained; except when passing through a wall, ceiling or at the termination where the use of a firestop or wall thimble reduces clearance to 1-1/2" (38mm).
INSTALLATION UNIT INSTALLATION WITH VERTICAL TERMINATION 4) Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed. 4" X 6-5/8" VENTING (Rigid Vent Systems) Diagram 4 1) Maintain the 1-1/2" clearances (air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfaces. Do not pack air spaces with insulation.
INSTALLATION HZ42E-NG SYSTEM DATA Min. Supply Pressure 5" WC (1.25 kpa) Low Setting Man. Pressure 1.6" WC (0.40kpa) Max. Manifold Pressure 3.5" WC (0.87 kpa) Orifice Size #40 DMS Minimum Input 17,500 Btu/h (5.13 kW) Maximum Input 26,000 Btu/h (7.62 kW) PILOT ADJUSTMENT Burner Flame Sensor HZ42E-LP SYSTEM DATA Min. Supply Pressure 12" WC (2.98 kpa) Low Setting Man. Pressure 6.4" WC (1.59kpa) Max. Manifold Pressure 10" WC (2.49 kpa) Orifice Size #53 DMS Minimum Input 19,500 Btu/h (5.
INSTALLATION WIRING DIAGRAM This heater does not require a 120V A.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/thermostat will continue to operate. However, a 120V A.C. power supply is needed for the AC Adaptor. (Do not cut the ground terminal off under any circumstances.
INSTALLATION OPTIONAL ACCENT LIGHTING WIRING DIAGRAM Wall Mounted Switch L1 L2 Hot Neutral Optional Accent Lights Receptacle in Unit 36 HZ42E Regency Horizon™ Gas Fireplace
INSTALLATION AC POWER ADAPTOR INSTALLATION (FOR SUREFIRE SYSTEM) An optional AC power adaptor may be installed as a constant power source for the SureFire system. NOTE: AC power adaptor is not required when using GTMF Remote IMPORTANT: Recommend removing the 4-AA batteries in the SureFire receiver. This will avoid battery leakage and power drainage. 4-AA Battery pack may be re-installed into receiver during power outages.
INSTALLATION Optional WALL THERMOSTAT A wall thermostat may be installed if desired, connect the wires as per the wiring diagram. Use table below to determine the maximum wire length. Note: Preferable if the thermostat is installed on an interior wall. ® Regency offers an optional programmable thermostat but any 250-750 millivolt rated nonanticipator type thermostat that is CSA, ULC or UL approved may be used. CAUTION Do not wire millivolt wall thermostat wires to 120V wire.
INSTALLATION GT REMOTE INSTALLATION DFBC = digital fireplace burner control 5) Locate the DFC wire from the receiver wire harness and connect to the DC supply wire from the DFBC. 1) Remove the faceplate and glass door to access to DFBC & battery pack tray. 2) Lift DFBC and battery pack up and out. HZ42E HZ42STE 3) Disconnect connector from battery holder and remove from tray – (battery holder is attached by Velcro to tray).
INSTALLATION GTM REMOTE INSTALLATION DFBC = digital fireplace burner control 6) Locate the DFC wire from the receiver wire harness and connect to the DC supply wire from the DFBC. 1) Remove the faceplate and glass door to access to DFBC & battery pack tray. 2) Lift DFBC and battery pack up and out. HZ42E HZ42STE Disconnect connector from battery holder and remove from tray – (battery holder is attached by Velcro to tray).
INSTALLATION 9) Install the ground wire to the ground lug just behind and to the left of the valve on the HZ42E and to the right of the valve on the HZ42STE. HZ42E HZ42STE 14) Install the receiver in the wall or if that is not possible - to the tray. HZ42E HZ42STE 10) Install 4 - AA batteries into the receiver, ensure correct polarity. 15) HZ42E Only: Manoeuvre the tray into the base of the unit using the stops to guide how far back the tray sits.
INSTALLATION OPTIONAL REFLECTIVE PANEL INSTALLATION Before installation, panels must be handled and cleaned as per instructions noted below: Stainless Steel Panels Black Enamel Panels • Stainless panels must be inspected for scratches and dimples prior to installation. All claims to be recorded at this time. Claims for damage after installation will not receive consideration. • Black Enamel panels must be inspected for scratches and dimples prior to installation. All claims to be recorded at this time.
INSTALLATION OPTIONAL LIGHT INSTALLATION 4) Remove the glass door - see instructions in manual. HZ42 Accent Light Assembly Kit # 596-959 1 910-814 Plug wiring + gasket 2 910-997 Halogen Bulb 5) Remove the glass crystals/optional ceramic stones or pebbles- if installed. 2 940-363 Amber Glass 6) Remove the inner panels if installed - see instructions in manual. 1 Light Assembly Includes gaskets (x2) 1 918-828 Instruction Sheet 7) Remove the bottom cover - shown below.
INSTALLATION 10) Feed the plug wiring through the opening in the firebox - secure light assembly mounting plate and gasket with 4 screws from the cover plate in step 9. 14) Place gasket over the inside perimeter of the light diffuser box. 15) From outside the firebox -Install light assembly box and gasket into opening created from the removal of the cover plates open end up - as shown below.
INSTALLATION 19) 20) Install socket and bulb into light diffuser as shown below. 3) Pull out light diffuser. Secure socket to light diffuser with one screw - as shown below. 4) Remove one screw securing the socket end of the diffuser and separate the 2 parts - as shown below. 21) Repeat steps 12-20 to install 2nd light diffuser . 22) Plug light assembly into receptacle located in the lower left corner inside the unit, attach ground wire to ground lug - located forward of the receptacle.
INSTALLATION GLASS CRYSTALS OR OPTIONAL STONES INSTALLATION ON BURNER Spread the Glass Crystals or Stones evenly over the burner. Ensure the crystals/stones do not overlap excessively as this will affect the flame pattern. IMPORTANT NOTE: Only the supplied approved Glass Crystals and Stones are to be used with these fireplaces. Use of any other type of glass crystals or stones can alter the unit's performance, any damage caused by the use of any unapproved glass or stones will not be covered under warranty.
INSTALLATION Glass Crystals shown on Burner For Units HZ54E, , HZ42ST, HZ42STE, HZI234E, HZ42E, HZ42, HZ30E, HZO42, HZO42 (AUS) PTO30, PTO60, Plateau Series Optional Spa Stones + Glass Crystals shown on burner.
INSTALLATION GLASS DOOR INSTALLATION Hook top of door onto top flange Flush Door Diagram 1 Diagram 2 Diagram 3 48 HZ42E Regency Horizon™ Gas Fireplace
INSTALLATION FACEPLATE INSTALLATION 1) Hook the flange on the back of the faceplate over the top edge of the glass door - as shown below. The bottom panel of the faceplate installs on the unit with 2 slides. These slides are located in the bottom of the unit - already installed within the outer slide. The inner slides need to be removed to install them on the brackets. 3) Pull out inner slide from the outer slide.
INSTALLATION 7) Secure each bracket with 4 screws in locations shown below. Top of lower faceplate HZ42ST - install slider with flat side facing inwards -secure with 2 screws in locations shown. Screw locations. 8) Install the inner slide removed from Step 4 to the bracket. Note: Installation locations of the slide are different for the HZ42 and HZ42ST - read instructions carefully.
OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS LIGHTING PROCEDURE 1) Read and understand these instructions before operating this appliance. IMPORTANT To ignite or reignite the pilot, you must first remove the glass door. 2) Check to see that all wiring is correct and enclosed to prevent possible shock. 3) Check to ensure there are no gas leaks. 1) Press and release on ON/OFF button once on the remote control or ON/OFF switch. 4) Make sure the glass in the glass door frame is properly positioned.
OPERATING INSTRUCTIONS COPY OF LIGHTING PLATE INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Natural Gas and Propane Installation Codes, CSA B149.1. WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
MAINTENANCE MAINTENANCE INSTRUCTIONS GENERAL VENT MAINTENANCE 1) Always turn off the gas and electrical supply before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year. Conduct an inspection of the venting system semi-annually. Recommended areas to inspect as follows: 2) Clean appliance and door with a damp cloth (never when unit is hot). Never use an abrasive cleaner.
MAINTENANCE GLASS DOOR REMOVAL 1) Turn the unit off and allow it to cool down to room temperature. 2) Turn off the gas supply to the unit. 3) Remove the faceplate by lifting it up off the glass door. Faceplate Glass Door 4) Remove the glass door. a) Remove the 3 screws shown below at the bottom of the glass door. b) Swing the door out 45o from the bottom and lift up and out.
MAINTENANCE VALVE ASSEMBLY REPLACEMENT 1) Turn the unit off and allow it to cool down to room temperature. 6) Lift out firebox base cover. 2) Turn off the gas and power supply to the unit. 3) Remove the faceplate by lifting it up off the glass door. 7) Remove three screws from locations shown below to release burner. Slide burner to the left to release from the orifice and lift out see inset. Faceplate Glass Door 4) Remove the glass door.
MAINTENANCE BULB REPLACEMENT 9) Partially lift out valve tray. 1) Slide out bottom faceplate panel. 2) Remove 4 screws securing light diffuser mounting plate - see below. 3) Pull out light diffuser. Gas Line 10) Disconnect the inlet gas line and remove the valve assembly. 11) Replace valve assembly and reverse steps. 4) Remove one screw securing the socket end of the diffuser and separate the 2 parts - as shown below. 5) Replace bulb.
PARTS LIST MAIN ASSEMBLY Part # Description 2) 910-078 910-363 910-366 Battery AA White Wall Switch White Switch Plate Wire 3) 596-008 Bottom Cover NG / LP 4) 596-525 596-530 5) 596-574/P 596-576/P 6) 911-004 911-005 7) 911-006 911-007 8) 904-593 904-345 9) 948-484 Burner Assembly -NG Burner Assembly-LP Valve Assembly -NG Valve Assembly-LP 886 Sit Valve - NG 886 Sit Valve - LP Pilot Assembly - NG Pilot Assembly - LP Orifice # 40 (NG) Orifice # 53 (LP) Slide Hinge 904-658 430-011 596-047F 596-048 596
PARTS LIST Part # Description 10) 596-907 596-908 Reflective Stainless Steel Inner Panels Black Enamel Inner Panels 11) 586-914 586-916 586-917 Faceplate Black Faceplate Sunset Bronze Faceplate Brushed Stainless 946-671 946-672 946-673 946-674 Cobalt Blue Glass Crystals Natural River Pebbles White River Pebbles Ceramic Spa Stones 946-680 946-681 946-683 946-684 910-574 910-576 910-572 GT Proflame Remote Control GTM Proflame Remote Control GTM NG Modulator GTM LP Modulator GTM Wire Harness Cover Wal
WARRANTY Regency® Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our facility. Regency® Fireplace Products is pleased to extend this limited lifetime warranty to the original purchaser of a Regency® Product. This warranty is not transferable.
Register your Regency® warranty online www.regency-fire.com Reasons to register your product online today! • View and modify a list of all your registered products. • Request automatic email notification of new product updates. • Stay informed about the current promotions, events, and special offers on related products.