REGENCY Model 4734 Access Control Expander Installation Manual Part Number 150807, Rev.
Interactive Technologies, Inc. 2 2 6 6 S e c o n d S t r e e t N o r t h N o r t h S a in t P a u l , M N 5 5 1 0 9 - 2 9 0 0 T : 6 5 1 / 7 7 7 - 2 6 9 0 F : 6 5 1 / 7 7 9 - 4 8 9 0 TE C H N O L O G IE S Security Automation Fire Protection Access Control ITI and Regency are registered trademarks of Interactive Technologies, Inc. X-10 is a registered trademark of X-10 (USA), Inc. ITI © 1998. All rights reserved.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 FCC Notices FCC Part 15 Information to the User Changes or modifications not expressly approved by Interactive Technologies, Inc. can void the user’s authority to operate the equipment. FCC Part 15 Class B This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Table of Contents Section 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Section 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.1 4734 Installation . . . . .
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Table of Contents Section 4 Using the 4734 Built-In Programmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 4.1 Entering Program Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 4.2 Stepping Through the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 4.3 Programming the Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Table of Contents 5.17.1 Open/Close Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 5.17.2 Exception Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 5.17.3 Open/Close Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 5.17.4 Auto Open/Close . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 5.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 List of Figures Figure 1 Model 4734 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 2 Model 4181 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 3 1 1 TEST Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 List of Tables Table 1 Software Updates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Table 2 Panic Key Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Table 3 Touchpad Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Table 4 Text and Characters .
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Section 1: Introduction The Model 4734 Control Expander is a plug-on unit that provides greatly enhanced software features, event storage memory, and user-friendly operation for the Model 4720 Control/Communicator. The 4734 replaces the control microprocessor on the 4720 (or on the obsolete Model 4721 Area Control Software). It allows full use of up to two zone expanders for a system maximum of 80 zones.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Section 2: Installation NOTE 1. Because the 4724 and 4734 have different options, you cannot convert a 4724 into a 4734 by replacing a chip. 2. The 4734 is for use with the 4720 Revision M circuit boards; the 4734-2 is for use with the 4720 Revision N or later circuit boards. When referring to both the 4734 and the 4734-2, these instructions use the convention “4734/4734-2.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 Revised 5/98 7 Model 4720 Adapter (P/N 130315 or 130316) Pin 1 Model 4734/4734-2 **Control Chip 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 8457G19A.DSF Figure 1: Model 4734 Installation *If you are upgrading a Rev. M 4720 board: Use 4734 Access Expander Use 130315 Adapter *If you are upgrading a Rev.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 2.3 Zone Expanders For more information on wiring zone expanders, see the 4720 Installation Manual (P/N 150476). In some situations, zone expanders operate differently with a 4734 system than they do with a 4720 only. The instructions below describe such differences (or refer to additional sources of information). 2.3.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Plug the Model 4181 into a 120 VAC, 60 Hz wall outlet to the panel. Use a 4-wire modular phone cable (P/N 130071, supplied) to connect the 4181 to the modular jack (P5) on the 4734 as shown in Figure 2. The maximum length of the cable is 20 feet. The 4181 is optically isolated from the powerline.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) 2.4.2 Revised 5/98 Suppliers Of X-10 Modules X-10 modules can be obtained from ITI. If you need to order X-10 modules, contact ITI’s Order Entry at 1-800-777-4841. 2.5 Software Updates When placing the 4734 into an existing 4720 installation, you may need to replace the software (as shown in the table below) to support the additional capabilities of the 4734.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) ■ 3.2.2 Revised 5/98 In a large system or during heavy use, display response may be slower than normal. For example, if 15 users are displaying Event Memory at the same time, the displays will be slower than normal. Entry or exit delay displays may be updated less often than once per second if the system is heavily loaded.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 3.4 Touchpad Operation 3.4.1 Touchpad Designations The Model 4734 Access Expander allows the system to use both door/card access and intercom features in the same installation. Each touchpad location (up to 15) has several programmable options. Touchpads designated as door stations will allow codes to be used for door access. A programmable option allows single-swipe access and disarm at door stations.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) 3.4.2 Revised 5/98 Touchpad Operation The Model 4734 Access Expander provides the following additional touchpad functions: Table 3: Touchpad Functions To gain access at a card reader or touchpad at a controlled access door, just present the card or press DOOR and enter the PIN at the touchpad.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 3.6 Walk Test The 4734 Walk Test mode allows the system to be tested without causing alarm reports. Follow the procedure below to perform a walk test. 1. Press 2 TEST followed by Code 0 or Code 1. NOTE 2. The display will show WALK TEST or your customized walk test message (see Section 5.12 of this manual). 3. Arm individual areas or the entire installation.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 4.2 Stepping Through the Program By pressing TEST, you can view the current option settings in a menu. The option description appears on the top line, followed by the current setting. The bottom line shows which keys can be used at that step of the program. In some cases, the key name will be followed by a word that explains how the key is used.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Hints: 1. To enter capital letters, press the number that corresponds to the letter's position in the alphabet. e.g., 0 1 for “A” and 2 6 for “Z.” 2. To enter numbers as part of the text, press 6 followed by the desired number, e.g., 6 0 for “0,” and so on. 3. The numbers 96-99 will cause a “beep” character of varying duration to be entered into the text.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) 4.5.2 Revised 5/98 Display Macros There are several “macro” message characters that activate special displays and may be embedded within any message. Be aware that the displays take a certain number of characters each. When using the 5540, the macro characters are preceded with a \ (backwards slash) character. In the built-in programmer, macro characters are preceded by the character ¥.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) 4.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 7 TEST #0CODE #1CODE . . . 8457G31A.DSF Figure 4: 7 TEST Menu Structure Section 5: Programming Options Description This section explains the options that can be programmed for the 4734. The options are listed here are as they appear on the touchpad display when the built-in programmer is used. The menu structure for the Model 5540 Downloading Software is slightly different.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 START#0:00:00 Using military time, key in the beginning time for the window. END#0:00:00 Key in the ending time for the window. NOTE Time windows may cross midnight. DAYS#0:SMTWTFSH Select the days on which the window will be active by toggling the digits 0 through 7 on and off.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 CODE#2:000000 Program the secret code or card PIN for this access code. The code can be from four- to sixdigits in length. If a card reader is connected, present the card to the reader. NOTE Do not begin any codes with the same digits that are used for the duress trigger. The duress trigger is programmed under SYSTEM (Menu 5). 5.3 Profiles (Menu 2) NUMBER: Select the profile to program (0-15).
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 WIN GRP#0:32 Select the time window group (programmed in WINDOW GROUPS, Menu 11) during which this user profile may be used. To make it possible to use a profile all the time, select ALWAYS (3 2). To make it impossible to use a profile at any time select NEVER (3 3). NOTE These options apply to all users using this profile.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Table 6: Default Mode Selections Selection Default Mode 0 The system will default to the DISARMED mode and will NOT generate an Open Report to the central station. 1 The system will default to the DISARMED mode and WILL generate an Open Report. 2 The system will default to the ARMED mode and will automatically bypass (shunt) any zones that are not ready to be armed.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 EXP ZONES#2:0 Enter the number of zones used on Zone Expander #2. RESD CODE#2:0223 If Zone Expander #2 is an RF zone expander, enter its residence code. Skip this step if NOT using an RF zone expander. ARM MENU:NO Causes the Interactive Arm Menu, normally used in split arm systems, to be active in all systems when a code is entered.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 KEY BEEPS SPK:NO If the installation includes a touchpad without a PZT beeper, you can use this option to send the beeps from the touchpad to the internal speakers; however, they will sound at all internal speakers. E/E BEEP PZT:YES Select this option if you wish to have the entry/exit tones sounded on the PZT beeper. (These tones are always audible on the internal speakers.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 DISPLAY RATE:3s Select a speed in the range of 1-4 seconds. This option controls the rate at which all displays are updated. FAST RESTORE:NO When this option is selected, the system reports restores as soon as the alarm has been restored, instead of waiting for the shutdown time. DURESS:NO This option allows the use of the 4734’s DURESS feature.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 NO PULS BELL:NO Select yes for steady fire bell output. (Used for strobes.) 5.7 Access Options (Menu 6) REP DG:NO (report door access granted) This option causes the system to send a report indicating that the door was accessed using a valid code number. The event is also printed.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 If a pause is needed, such as after dialing “1” for a long distance number, enter an “A” (0 1). If an internal phone system is being used in which you must dial a special digit to establish an outside line (and wait for a second dial tone), enter a “D” (0 4) after the digit to establish the outside line. The procedure for entering alphabetic and other characters is explained in Section 4.5 of this manual.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 UP/DOWNLOAD:YES Select YES to enable remote uploading and downloading. When the panel receives a signal for downloading it will dial the computer phone number and use the account number that is programmed for Account #4. FAIL ATTM:5 Enter the number of attempts (1-15) that the communicator will try to dial out before it gives a dialer-failed signal.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 DAY TRBL#1:NO If this option is selected, the zone will be supervised only while the zone is disarmed. Day trouble loop response is always .062 seconds. Day Troubles will not restore, until silenced from a touchpad. Typical day trouble zones are window foils or emergency exits. If you select DAY TRBL for a zone, you must also select N.C. for that zone. Do NOT pick both 24HR TRBL and DAY TRBL.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 INTERIOR:NO Interior zones can be bypassed as a group using the INT key. Select this option if the zone will be an interior zone. BYPASS#1:NO Select this option if you want to be able to bypass (shunt) the zone. If you do not select this option for a particular zone, you will not be able to bypass that zone. NOTE Fire zones must NOT be bypassable.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 SIL. ALM#1:NO (silent alarm) When this option is selected, alarm conditions will not be annunciated audibly, but will be reported to the central station. NOTE Holdup zones must be selected as SIL. ARM. REP.DLY#1:NO Select this option to create a delay between the time that an alarm condition is sensed by the zone and the time that the system reports the alarm.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 REP OP/CL#1:NO Select this option if you want the system to send Normal and Exceptional Open and Close Reports to Phone #1. REP DOOR#1:YES Select this option if you want door access information to be reported to Phone #1. REP TEST #1:YES Select this option if you want test signals to be reported to Phone #1. (Event memory reports if selected will also report to TEST accounts.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 L ALM/TST#1:NO Select this option to enable the listen-in function only with alarms and tests on this number. LN 1 ONLY#1:NO Select this option if you wish to use Phone Line #1 ONLY with Phone #1. You would typically do this only if using a direct line or if using a WATTS line. LN 2 ONLY #1:NO Select this option if you wish to use Phone Line #2 ONLY with Phone #1.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 RING:12345678 Select the intercom/telephone stations (1-8) where the telephone will ring when there is an incoming call, by toggling the digits 1 through 8 ON (digit displayed) and OFF. LISTEN:12345678 Select the intercom/telephone stations (1-8) that will be audible at the central station during listen-in. The listen-in feature will be ONE WAY during holdup alarms.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) NOTE Revised 5/98 For all options including the system messages, pressing the CHM key will restore the factoryprogrammed default for that option.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 5.14 Timers (Menu 13) SHUTDOWN:90s Decide the number of seconds that you want the audible alarms to be active. Then divide this number by 10 and enter the result (1-255). EXIT:30s Enter (in seconds) the length of the exit delay (1-255). ENTRY1:30s Enter (in seconds) the length of the entry delay for zones controlled by Entry Delay #1 (1-255).
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 In a split arming system, the user goes into the AREA Menu (Menu 16) by entering an access code. The LCD shows a continuous display of key prompts to help the user arm and disarm individual areas. If a key is not pressed during the time period you have programmed in the MENU TIME option, the system exits the AREA Menu.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) 2. Multiply the per day number of seconds that the clock gains or loses by 6.07 to get the adjustment factor. 3. If the clock is fast (gains time), subtract the adjustment factor from the current value of TIME CALB. 4. If the clock is slow (loses time), add the adjustment factor to TIME CALB. 5. If the resulting number is: ■ less than zero, add 256 to get the new value for TIME CALB.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 STATION:#2 Select the next touchpad for which options are to be programmed (up to 15 touchpads) 5.16 Key Zones (Menu 15) STATION:#0 Select the touchpad for which you want to program the panic key zones (0-15 touchpads). NOTE Station #0 options are not used. Begin programming with Station #1. KEY:UNUSED Select the panic key to program. Although the display shows “KEY:UNUSED,” there is no “UNUSED” key.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 NO SHUTD#1:NO If this option is selected, the bell will not shut down until the panel is disarmed. The display now advances to the next touchpad panic zone. 5.17 Area Options (Menu 16) SPLIT ARM:NO This option must be selected in order for the area control features to operate.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 AUTO NO FRC:NO (4) When selected, Auto Close will cause alarms on any Not Ready Zones. AUTO OC:-------Enter areas that will Auto Open or Auto Close. AREA NAME#1: Select a name for each area being used (16 characters maximum). Area names are displayed when accessing area arming and with the zone status to show which area the zone is in. (Areas were programmed in ZONE OPTIONS, Menu 8.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 5.19 Programmable I/O Statements (Menu 18) The 4734’s programmable I/O capability allows you to configure auxiliary output devices to act as indicators of internal status conditions or to respond to the internal conditions in some way. NOTE It is easier to program the I/O statements using the Model 5540 Downloading Software (Section 6.5.2 of this manual).
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 5.19.2 Program Operations The 21 program operations are listed in the following table, along with the functions they perform. Of the 21 operations, five require additional data. These five operations are listed below: ■ 9:GET1, ■ 10:GET8, ■ 11:GETC, ■ 12:PUT1, and ■ 13:PUT8. To select an operation, enter the number shown beside the operation on the display, then press TEST.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Table 14: Programmable I/O Statement Operations Operation 10:GET8 What It Does Takes eight status bits that are grouped together from the 4734’s memory and place them on top of the stack. 12:PUT1 Additional Information Needed $@0000 The address of the group of eight status bits in the 4734’s memory. Takes a constant number and places it on top of the stack.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Table 15: Status and Port Addresses Names Operations Functions AARMED[1-8] AACAREA ACHIME[1-8] ACODE2[1-8] @$B0-7.0 @$564.0-7 @$B0-7.3 @$B0-7.4 GET1 GET1 GET1 GET1 Area armed Last group of area granted door access Area chime activated Area Code2 activated AENTRY[1-8] AEXIT[1-8] AINST[1-8] ALMAREA 0.-7 @$B8-F.1 @$B8-F.0 @$B0-7.2 @$79.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Table 15: Status and Port Addresses Names Address.Point Operations Functions SILENC SMKPWR SPECL SYSTR @$28.3 @$EE.7 @$28.1 @$28.5 GET1 GET1 GET1 GET1 Silenced trouble Smoke power on Special alarm System trouble TEE[1-8] TER15 TER16 TER18 @$2D-$34 @$EE.4 @$EE.3 @$12.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 EXAMPLE 2: The following statement will cause Terminal 16 on the 4720 to produce an active low output whenever there is an intrusion alarm in any area. GET1 @$28.2, PUT1 @$EE.3 EXAMPLE 3: The following statement will cause the X-10 Module Address #1 from the first house code to be activated whenever Area #1 (or a non-area system) is in entry or exit delay.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 5.19.5 Factory Programmed Default I/O Program The following table shows the factory programmed default I/O program, along with an explanation of what it does. Table 16: Default I/O Program Statement Effect 1 GET1 @$B0.0 2 PUT1 @$8E.0 3 GET1 @$B1.0 4 PUT1 @$8E.1 5 GET1 @$B2.0 6 PUT1 @$8E.2 7 GET1 @$B3.3 8 PUT1 @$8E.3 9 GET1 @$B4.0 10 PUT1 @$8E.4 11 GET1 @$B5.0 12 PUT1 @$8E.5 13 GET1 @$B6.0 14 PUT1 @$8E.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 5.20 Default Options (Menu 19) DEFAULT ALL? If you select this option, all options will return to their factory-programmed default values. WARNING! Selecting this option resets all options to their factory default values.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) 4. Revised 5/98 As computer keys are pressed, they are buffered and shown after the “Keys:” heading at the top of the status window. The keystrokes are not actually sent to the panel, until ENTER is pressed on the keyboard. After the keystrokes have been sent, the “Keys:” area is blank. The display will take up to four seconds to respond to the keys sent to the panel because of the relatively slow transmission rate.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 screen, followed by “Press ESC to terminate, Waiting for Answer...” Several seconds will elapse before the call goes through and the screen indicates that downloading is taking place. 6.4.2 Printing the Options To print the data from a particular options menu, go to the menu and press F3. 6.4.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Outputs are generated on three types of devices: 1. Model 4720 panel Terminals 15, 16, and 18: Terminals 15 and 16 are open collector outputs that switch low when activated (negative voltage; -12 VDC, 50 mA maximum). Terminal 18 switches high when activated (positive voltage; +12VDC, 20 mA maximum). The following figure shows how each of these terminals would be connected to an output device.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Table 17: Logical Operators Operator “ON” Output Is Generated When... A AND B Both Condition A and Condition B are in effect (for example, Area #1 is armed and Area #2 is armed). A OR B Either A or B or both is in effect. A XOR B Either A or B is in effect, but not both. NOT (A) The specified condition is not in effect. A=B A and B are in the same state (in effect or not in effect).
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) 6.5.2 Revised 5/98 I/O Programming Procedure-5540 Software To program the I/O statements using the 5540 software, go to the Programmable I/O Menu (selection L of the Edit Accounts Menu). The inputs and outputs are programmed through a series of control statements that you enter into this menu. These statements take the form: 1 OUTPUT = STATUS. The OUTPUT label refers to the device on which an output is generated.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Table 20: Output Designations Label RLY[1] Outputs on 4180 Module 1, Connector P2 RLY[2] RLY[3] Outputs on 4180 Module 1, Connector P3 Outputs on 4180 Module 2, Connector P2 RLY[4] Outputs on 4180 Module 2, Connector P3 RLY[1].0 RLY[1].1 Outputs on 4180 Module 1, Connector P2, Pin 8 Outputs on 4180 Module 1, Connector P2, Pin 7 ... RLY[1].7 Outputs on 4180 Module 1, Connector P2, Pin 1 RLY[2].
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Table 21: Programmable I/O Status Labels (Read Only)1 Label2 Data Type Function AARMED[1-8] ACCAREA.0-7 ACHIME[1-8] ACODE2[1-8] AENTRY[1-8] AEXIT[1-8] AINST[1-9] ALMAREA.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Shown below are three examples of programmable I/O statements that can be used on the 4734 to obtain customized status outputs. EXAMPLE 1: The following statment will cause Terminal 15 on the 4720 to produce an active low output whenever there is a fire alarm in any area.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 REGENCY® ONE YEAR LIMITED WARRANTY Interactive Technologies, Inc. (ITI) warrants that Regency products manufactured by ITI (Regency Product) will be free from defects in material and workmanship for one (1) year from the date of purchase by the original purchaser.
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Revised 5/98 Index Symbols # RINGS:1 . . . . . . . . . . . . . . . . . . . . . . . . . .25 #0:------+16 . . . . . . . . . . . . . . . . . . . . . . . . . .31 #0:------+24 . . . . . . . . . . . . . . . . . . . . . . . . . .31 #0:------+8 . . . . . . . . . . . . . . . . . . . . . . . . . . .31 #0:0------+0 . . . . . . . . . . . . . . . . . . . . . . . . . .31 #1:------+0 . . . . . . . . . . . . . . . . . . . . . . . . . .
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) DEFAULT ALL? . . . . . . . . . Default Options (Menu 19) . . . defaults . . . . . . . . . . . . . . . . DELAYED BYPASS:YES . . . Dialer (Menu 7) . . . . . . . . . . DIALER:YES . . . . . . . . . . . DIRECT LN#1:NO . . . . . . . . DISARM#0:YES . . . . . . . . . display macros . . . . . . . . . . . DISPLAY RATE:3s . . . . . . . DOOR DISARM:NO. . . . . . . DOOR ONLY#1:NO . . . . . . . DOOR OPEN:60s . . . . . . . . .
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) Key Zones (Menu 15) . KEY:UNUSED . . . . . . . . . . . . . . . . . . . . . . . 36 . . . . . . . . . . . . . . . . . . 36 L L ALM/TST#1:NO . . . . . . . . . limited warranty . . . . . . . . . . . LINE 2 EN:NO (line 2 enable) . . LINE FRQ:60 . . . . . . . . . . . . . LINE MON:NO. . . . . . . . . . . . LISTEN IN#1:0 . . . . . . . . . . . . LISTEN:12345678 . . . . . . . . . . LN 1 ONLY#1:NO . . . . . . . . .
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) PROFILE#2:0 . . . . . . . . . . . . . . . . . . . . . . . .16 Profiles (Menu 2) . . . . . . . . . . . . . . . . . . . . . .17 Program Mode . . . . . . . . . . . . . . . . . . . . . . . .10 program operations . . . . . . . . . . . . . . . . . . . . .40 PROGRAM#:YES . . . . . . . . . . . . . . . . . . . . .17 Programmable I/O Statements (Menu 18) . . . . . .39 programmer menu structure . . . . . . . . . . . . . . . . . .
Regency® Model 4734 Access Control Expander Installation Manual (P/N 150807, Rev. A) touchpads designations . operation . . . troubles . . . . . . . TYPE#1:FIRE . . . TYPE: . . . . . . . . Revised 5/98 ......................8 . . . . . . . . . . . . . . . . . . . . 8, 9 . . . . . . . . . . . . . . . . . . . . . 38 . . . . . . . . . . . . . . . . . . . . . 27 . . . . . . . . . . . . . . . . . . . . . 36 U UP/DOWNLOAD:YES . . . updates, software . . . . . . . . uploading event memory . . . user profiles .