3.6 Walk Test
The 4734 Walk Test mode allows the system to be tested without causing alarm reports. Fol-
low the procedure below to perform a walk test.
1. Press 2 TEST followed by Code 0 or Code 1.
2. The display will show WALK TEST or your customized walk test message (see Section
5.12 of this manual).
3. Arm individual areas or the entire installation. Then violate the sensors by walking
through the armed areas. The system will operate as normal except that it will not report
alarms to the central station, and alarm tones will not be sent to the external bell. The
alarm conditions will be displayed on the touchpad LCD and annunciated on the internal
speakers.
NOTE The system will remain in the same armed/disarmed state after you exit Walk Test Mode, so be
sure to arm or disarm it as desired.
4. Interior zones may be armed or disarmed during the test to verify operation of the INT key
and options.
5. Test the exit and entry zones to verify the delay times you have programmed.
6. View the alarm memory to see that the desired areas have been activated.
7. To exit Walk Test Mode, press MUTE MUTE on any touchpad.
Section 4: Using the 4734 Built-In Programmer
The 4734 includes a built-in programmer that can program all system operating parameters.
The programmer is simple to use and includes help displays for entering data. The 4734's built-
in programmer can be accessed using any 4000 series touchpad, Section 4.7 of this manual
shows diagrams of the built-in programmer’s menu structure.
Before you begin programming, write your option selections down in the programming record,
(P/N 150675). For descriptions of the options available with the 4734 Access Expander, see
Section 5 of this manual.
Programming can also be performed using the Model 5540 Downloading Software. See Sec-
tion 6 of this manual for instructions.
4.1 Entering Program Mode
1. To go into Program Mode, press 1 1 TEST followed by Code 0.
Code 0 (installer's code) is granted access to all system options. (The factory programmed
value for Code 0, the installer's code, is 1234.) Other codes are granted access to the first
four program menus if the PG or “program” access option is enabled for that code. When
Program Mode is active, the display lists the available menus one by one.
2. Press the number of the menu that includes the options you wish to program. Press TEST.
The first line of the touchpad display will show the option name and the most recently pro-
grammed value for that option. The second line will show the available choices.
3. To exit the current menu, press MUTE. To leave Program Mode from the main manual,
press MUTE; to leave Program Mode from within a menu, press MUTE MUTE (twice).