Instruction Manual

24
Regency Bellavista™ B41XTCE Gas Fireplace
INSTALLATION
HORIZONTAL TERMINATIONS
FLEX VENT 5" X 8"
These venting systems, in combination with the B41XTCE Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by
Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent
Termination Locations" section.
Regency
®
Direct Vent (Flex) System 4 foot Termination Kit (Part# 946-615) or 10 foot Termination Kit (Part# 946-616) includes all the parts
needed to install the B41XTCE with a either a top or rear vent.
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency may be used for Flex installations.
3) Regency
®
Direct Vent System (Flex) is only approved for horizontal terminations.
NOTE: If longer runs are required the FPI Direct Vent system (Flex) #946-616 includes
all parts needed to install the B41XTCE with a maximum 10' run.
FPI Kit # Length Contains:
#946-615 4 Feet 1) 8” exible liner (Kit length)
2) 5” exible liner (Kit length)
3) spring spacers
4) thimble
5) AstroCap XL termination cap
6) screws
7) tube of Mill Pac
8) plated screws
9) S.S. screws #8 x 1-1/2” drill point
10) vinyl siding standoff
#946-618 6 Feet
#946-616 10 Feet
IMPORTANT
Must use Rear Venting De ector
packaged with unit in rear vent
horizontal termination applications.