Installation manual

10
F5100 Regency Freestanding Woodstove
INSTALLATION
6"
[152mm]
10"
[254mm]
Max. 36"
Horizontal
Min. 36"
V
ertical
Rise
WALL EXIT CLEARANCE FACTORY BUILT CHIMNEY
When a metal prefabricated chimney is used, the manufacturer's installation instructions must be followed. You must also purchase and install the ceiling
support package or wall pass-through and "T" section package, fi restops (where needed), insulation shield, roof fl ashing, chimney cap, etc. Maintain proper
clearance to the structure as recommended by the manufacturer. The chimney must be the required height above the roof or other obstructions for safety and
proper draft operation.
Minimum vertical of 36" before any offset.
Horizontal Maximum of 36" with 1/4" rise per foot.
NOTE: Recommend using 2-45º instead of 90º to improve draft
and performance.
6"
[152mm]
Min. 36"
Vertical
Rise
Max. 36"
Horizontal
10"
[254mm]
MASONRY CHIMNEY
Ensure that a masonry chimney meets the minimum standards of the
National Fire Protection Association (NFPA) by having it inspected
by a professional. Make sure there are no cracks, loose mortar or
other signs of deterioration and blockage. Have the chimney cleaned
before the stove is installed and operated. When connecting the
stove through a combustible wall to a masonry chimney, special
methods are needed.
Minimum vertical of 36" before any offset.
Horizontal Maximum of 36" with 1/4" rise per foot.
NOTE: Recommend using 2-45º instead of 90º to improve draft
and performance.