www.regency-fire.com P121 / P121LC / P121RC / P131 Zero Clearance Direct Vent Gas Fireplace Owners & Installation Manual STYLE MODEL See Thru P121-NG1 Natural Gas P121-LP1 Propane Left Corner P121LC-NG1 Natural Gas P121LC-LP1 Propane Right Corner P121RC-NG1 Natural Gas P121RC-LP1 Propane WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
To the New Owner: Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY. The P121/ P121LC/P121RC/P131 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch. The model P121/P121LC/P121RC/P131 has been approved by Warnock Hersey for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow.
TABLE OF CONTENTS Page Page Safety Label Safety Label ............................................................... 4 Installation Manufactured Mobile Home Requirements ................ 2 Important Message ..................................................... 5 Before You Start ......................................................... 5 General Safety Information ........................................ 5 Installation Checklist ................................................... 5 Specifications ........
NOTE: Regency units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one. For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter licensed in the Commonwealth of Massachusetts. For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length. For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.
INSTALLATION IMPORTANT: SAVE THESE INSTRUCTIONS The Panorama P121/P121LC/P121RC/P131NG1 or P121/P121LC/P121RC/P131-LP1 Direct Vent Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation.
INSTALLATION SPECIFICATIONS P121-1 See Thru Note: These units are non-load bearing.
INSTALLATION P121LC-1 Left Corner Unit Note: These units are non-load bearing.
INSTALLATION LOCATING YOUR GAS FIREPLACE 1) When selecting a location for your stove, ensure that the clearances are met as outlined on page 9. A) P121-1 See Thru 2) Provide adequate clearances for servicing. 3) The appliance must be installed on a flat, solid, continuous surface (e.g. wood, metal, concrete). This may be the floor, or raised up on a platform to enhance its visual impact.
INSTALLATION CLEARANCES The clearances listed below are Minimum distances unless otherwise stated (refer to diagrams on page 8): Clearance to Combustibles from: Back 0" (0mm) Side 0" (0mm) Floor 0" (0mm) CAUTION REQUIREMENTS: The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoffs may NOT be recessed into combustible construction. Determine the total thickness of the finished floor (eg.
INSTALLATION FRAMING AND FINISHING 1) For ease of installation, frame your fireplace after it is positioned and the vent system is installed. Remember to install the top standoffs. See page 11 for assembly. Use 2x4's and frame to local building codes. CAUTION: Verify your fireplace dimensions, framing methods and finished wall facing details before framing. Determine the total thickness of facing material - drywall plus ceramic tiles, slate, etc.
INSTALLATION FACING & FINISHING REQUIREMENTS This fireplace is supplied with a 3" metal extension trim above the fireplace. The extension trim may be replaced if the framing is faced with a noncombustible material placed flush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.) UNIT ASSEMBLY PRIOR TO INSTALLATION The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped into position.
V E V M V B Vent terminal . F V V A G B C V A V B B V A K B H j N V Area where terminal is not permited A V 18" L A Note: - A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. - Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor. - If the vent termination is accessible, a certified guard shall be installed.
INSTALLATION RIGID PIPE VENTING COMPONENTS LIST All Simpson Dura-Vent components are available directly from FPI.
INSTALLATION VENTING ARRANGEMENT - HORIZONTAL TERMINATIONS Regency Direct Vent System (Flex) Horizontal Terminations Only These venting systems, in combination with the P121-1/P121LC-1/P121RC-1/P131-1 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram on page 12.
INSTALLATION RIGID PIPE VENTING SYSTEMS Horizontal or Vertical Terminations The minimum components required for a basic horizontal termination are: 1 1 1 1 1 1 Simpson Duravent Adaptor Horizontal Termination Cap 45o Elbow Rigid Pipe Adaptor Wall Thimble Length of pipe to suit wall thickness (see chart) Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap.
INSTALLATION RIGID PIPE VENTING ARRANGEMENTS - HORIZONTAL TERMINATIONS REGENCY DIRECT VENT SYSTEM (FLEX) (Propane & Natural Gas) The diagram below shows examples of horizontal termination arrangements using one, two, or three 90o elbows (two 45o elbows equal one 90o elbow). Note: 1) A maximum of three 90o elbows are permitted. 2) Minimum distance between elbows is 1 ft. (305mm).
INSTALLATION Horizontal Venting with Two (2) 90o Elbows Option A) B) C) D) E) F) V 1' (305mm) Minimum 2' (610mm) Minimum 3' (914mm) Minimum 4' (1.22m) Minimum 5' (1.5m) Minimum 6' (1.86m) Minimum H + H1 2' (610mm) MaximumH2 5' (1.5m) Maximum 8' (2.4m) Maximum Max. 11' (3.35m) Maximum 14' (4.27m) Maximum 15' (4.5m) Maximum With the above options, maximum total pipe length if 37 feet with minimum of 6 feet total vertical and maximum 15 feet total horizontal.
INSTALLATION RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS (Propane & Natural Gas) • • • • Vent must be supported at offsets Maintain clearances to combustibles as listed on page 9. Firestops are required at each floor level and whenever passing through a wall. Must use optional rigid pipe adaptor when using rigid pipe vent systems (Part# 510-994). The P121-1/P121LC-1/P121RC-1/P131-1 is approved for a maximum 35 ft. (10.
INSTALLATION Vertical Venting with Two (2) 90o Elbows A) Option 1' (305mm) Minimum V + V1 B) 2' (610mm) Minimum C) 3' (914mm) Minimum D) 4' (1.22m) Minimum E) 5' (1.5m) Minimum F) 6' (1.86m) Minimum Vertical Venting with Two (2) 90o Elbows Option A) B) C) D) 4' (1.22m) Maximum H 6' (1.86m) Maximum 9' (2.7m) Maximum 12' (3.6m) Maximum 15' (4.5m) Maximum 17' (5.
INSTALLATION Vertical Venting with Three (3) 90o Elbows Option A) B) C) D) V + V1 2' (610mm) Minimum 3' (914mm) Minimum 4' (1.22m) Minimum 5' (1.5m) Minimum H + H1 3' (914mm) Maximum 6' (1.86m) Maximum 9' (2.7m) Maximum 12' (3.6m) Maximum With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal. Please note minimum 1 foot between 90o elbows is required.
INSTALLATION 1) Maintain the 1-1/4" clearances (air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfaces. Do not pack air spaces with insulation. Check pages 17-19 for the maximum vertical rise of the venting system and the maximum horizontal offset limitations. Diagram 3 7) Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble (Part # 942) over the vent pipe.
INSTALLATION steep roof pitches, the vertical height must be increased. A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem. 7) Ensure vent is vertical and secure the base of the flashing to the roof with roofing rails, slide storm collar over the pipe section and seal with a mastic. 8) Install the vertical termination cap by twistlocking it.
INSTALLATION CONVERSION KIT FROM NATURAL GAS TO PROPANE MODEL #730-969 FOR P121-1/P121LC-1/P121RC-1/P131-1 USING SIT 820 NOVA GAS VALVE THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !! Conversion Kit Contains: Qty.
INSTALLATION P121/P121LC/P121RC/P131-NG1 System Data For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1. The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point. For 0 to 4500 feet altitude Burner Inlet Orifice Sizes: When using copper or flex connectors use only approved fittings. Always provide a union so that gas lines can be easily disconnected for servicing.
INSTALLATION LOG INSTALLATION 1) Carefully remove the logs from the box and unwrap them. The logs are fragile, handle with care - do not force into position. Read the instructions below carefully and refer to the diagrams. If logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot operation. 2) Place Log 326 on the front right side of the burner. Ensure that the notches on the far right side of the log fit into the grate posts.
INSTALLATION Repeat step 3 on the opposite side of the burner. Repeat step 5 on the opposite side of the burner. 329 327 327 329 4) Embers should be placed in front of Log 326 and Log 327 and also down the middle between the logs as shown in the image below. 6) Place Log 328 on the middle right side of the burner. Ensure that the log fits over the 2nd grate post from the right. 328 Caution: Do NOT cover burner ports. Grate Post Repeat step 6 on the opposite side of the burner.
INSTALLATION GLASS DOOR REMOVAL 1) Remove the 8 screws that secure the glass door. FINISHING TRIM LOUVERS & GRILLS 1) Slide the Side Finishing Trim up into the slot in the top flange of the fireplace. Push tight against the magnet at the base of the unit. 1) Attach the screws provided to the top left and right corners. NOTE: Do not tighten the screw entirely, ensure that some room is left to be able to hang the grill or louver over the screw. Slide Trim into slot.
INSTALLATION Option 1: REMOTE CONTROL Option 2: WALL SWITCH Option 3: WALL THERMOSTAT Can be used with Option 2 or 3 but not both. Can be used with Option 1 or 3 but not both. Can be used with Option 1 or 2 but not both. Use the Regency Remote Control Kit approved for this unit. Use of other systems may void your warranty. 1) Run the supplied 15' of wire through the back gas inlet opening. Be careful not to damage wire.
INSTALLATION WIRING DIAGRAM three wire power cord can also be used and plugged into a suitable receptacle. White FAN 1 (*by others) ON OFF Nut Black Ground Wire Black (*Supplied by others - install according to local code) Grounding Lug Detail FAN 2 (*by others) Pilot Assembly Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges.
OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS 1) Read and understand these instructions before operating this appliance. 2) Check to see that all wiring is correct and enclosed to prevent possible shock. 3) Check to ensure there are no gas leaks. 4) Make sure the glass in the door frame is properly positioned. Never operate the appliance with the glass removed. 5) Verify that the venting and cap are unobstructed. 6) Ensure that the brick panels are installed. 7) Verify log placement.
OPERATING INSTRUCTIONS Copy of the Lighting Plate Instructions Burner Tray: The burner tray is positioned directly under the burner tube(s) and logs and is made of a different gauge material from the rest of the firebox and body. Therefore, the varying thicknesses of steel will expand and contract at slightly different rates which can cause "ticking" and "cracking" sounds. You should also be aware that as there are temperature changes within the unit these sounds will likely re-occur.
MAINTENANCE MAINTENANCE INSTRUCTIONS 2) Remove the Cap, and shine a flashlight down the Vent. Remove any bird nests, or other foreign material. 1) Always turn off the gas valve before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year. When cleaning the logs, use a soft clean paint brush as the logs are fragile and easily damaged.
MAINTENANCE REMOVING VALVE 8) Remove the Side Base Brick Panels and finally the Long Base Brick Panels. 1) Shut off the gas supply. 13) Undo the pilot tube from the valve with a 7/16" wrench. 14) Undo the quick drop out thermocouple nut on the valve with a 9mm (metric) wrench. 2) Remove the louvers and trim kit. Remove the front door. 15) Remove the Piezo igniter wire and push button assembly. 3) Remove the logs, embers. 16) Undo the "gas out" flare nut with a 13/16" wrench.
MAINTENANCE INSTALLING VALVE 1) Attach the valve to the valve bracket with the 6 (m5x8 metric) screws provided. 2) Reconnect the "gas out" flare fitting with an 11/16" wrench. 3) Reconnect the "gas out" flare nut with a 13/16" wrench. FAN REPLACEMENT 1) Shut off power. 6) Replace fan. 2) Remove top louvers. 7) Repeat for opposite side/corner. 3) Unplug power wires. 8) Reverse steps 1 - 5 for installation. 4) Remove 4 screws securing fan to mounting bracket.
PARTS LIST P121-1 (SEE THRU) MAIN ASSEMBLY Part # 1) 2) 9) 10) 11) 17) 24) 360-528 360-538 360-529 360-539 360-046 360-047 430-001 360-086 * Description Door Assy Front - Tempered Door Assy Front - Ceramic (Optional) Door Assy Side - Tempered Door Assy Side - Ceramic (Optional) Nailing Strip - Top - Front Nailing Strip - Top - Side Standoff - Top Gasket - Relief Door Relief Door Assembly Part # Description Part # 135) 360-069 Heat Shield - Side 360-926 146) 360-033 360-034 150) 360-123 151) 904
PARTS LIST P131-1 (PIER) MAIN ASSEMBLY Part # 1) Description Part # Description Part # Description Door Assy Front - Tempered Door Assy Front - Ceramic (Optional) 141) 360-031 Column Finishing Trim 181) * Extension Trim - Pier 146) 360-035 Finishing Trim Door Assy Side - Tempered Door Assy Side- Ceramic (Optional) 149) 360-122 150) 360-123 151) 904-258 Magnet Bracket - Corner Magnet Bracket - Front Magnet 204) 360-940 206) 910-171 224) 360-942 Dec.
PARTS LIST P121RC-1 (RIGHT CORNER) MAIN ASSEMBLY Part # Description Part # Description Part # 1) 360-528 360-538 Door Assy Front - Tempered Door Assy Front - Ceramic (Optional) 98) 910-366 99) 910-363 100) 910-367 910-882 Switch Cover Plate Wall Switch Switch Receptacle Plastic Box Wire - Valve to Burner Switch 2) 360-529 360-539 Door Assy Side - Tempered Door Assy Side - Ceramic (Optional) 138) 360-063 141) 360-031 Heat Shield - Front Column Finishing Trim Description 173) 360-932 360-934 3
PARTS LIST P121LC-1 (LEFT CORNER) MAIN ASSEMBLY Part # Description Part # 1) 360-528 360-538 Door Assy Front - Tempered Door Assy Front - Ceramic (Optional) 2) 360-529 360-539 Door Assy Side - Tempered Door Assy Side - Ceramic (Optional) 9) 360-046 10) 360-047 11) 430-001 Nailing Strip - Top - Front Nailing Strip - Top - Side Standoff - Top 17) 360-086 24) * Gasket - Relief Door Relief Door Assembly 32) 33) 34) 35) Brick Panel - Base - Side Brick Panel - Base - Front Brick Panel - Side Brick P
PARTS LIST P121/P121LC/P121RC/P131-1 BURNER ASSEMBLY & LOG SET Part # Description 360-930 41) 904-326 42) 904-327 43) 904-328 44) 904-329 Log Set Front Right Log Front Left Log Middle Left Log Middle Right Log 360-574/P 56) 910-378 Valve Assembly Valve S.I.T.
NOTES ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ______________________________________
NOTES ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ______________________________________
NOTES ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ______________________________________
WARRANTY Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of a Excalibur Product. This warranty is not transferable.
Regency fireplace products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our door. Fireplace Products International Ltd. is pleased to extend this Limited Lifetime Warranty to the original purchaser of a Regency Product. See the inside back cover for details. Register your Regency online at http://www.regency-fire.