www.regency-fire.com ULTIMATE U39 Direct Vent Freestanding Gas Stove MODELS: U39-NG Natural Gas Owners & Installation Manual U39-LP Propane WARNING: FOR YOUR SAFETY If the information in these instructions are not followed exactly, What to do if you smell gas: a fire or explosion may result causing property damage, Do not try to light any appliance personal injury or loss of life. Do not touch any electrical switch: do not use any phone in your FOR YOUR SAFETY building.
REGENCY ULTIMATE Direct Vent Freestanding Gas Stove To the New Owner: Congratulations! You are the owner of a state-of-the-art ULTIMATE Direct Vent Gas Stove by FPI Fireplace Products International Ltd. The Regency Gas Series of hand crafted appliances has been designed to provide you with all the warmth and charm of a woodstove, at the flick of a switch. The models U39-NG, and U39LP of this series has been approved by Warnock Hersey for both safety and efficiency.
TABLE OF CONTENTS Page Safety Label Safety Labels .......................................................................... 4 Installation Specifications .......................................................................... 5 Information for Mobile/Manufactured Home After First Sale .................................................................. 5 Before You Start ....................................................................... 5 General Safety Information .................................
SAFETY LABEL This is a copy of the label that accompanies each ULTIMATE Direct Vent Freestanding Gas Stove. We have printed a copy of the contents here for your review. The safety label is located on the inside of the drop down pedestal door. NOTE: Regency units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
INSTALLATION IMPORTANT: SAVE THESE INSTRUCTIONS The ULTIMATE Direct Vent Freestanding Gas Stove must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the building authority having jurisdiction to determine the need for a permit prior to starting the installation. Note: Failure to follow the instructions could cause a malfunction of the heater which could result in death, serious bodily injury, and/or property damage.
INSTALLATION into a manufactured home the unit must be bolted down to the floor. 4) This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation. 5) This appliance is Listed for Alcove installations, maintain minimum Alcove clearances as follows, minimum width of 48" (1219mm), a maximum depth of 36" (914mm), and minimum ceiling height of 64"(1626mm).
INSTALLATION Minimum ceiling height is 36"/914mm from top of unit. LOUVER INSTALLATION 1) Attach the top & bottom louvers to the side stove panel using 2 screws per side. Note: These flue pipes must not be connected to any other appliance. The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system.
H= Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally from the centerline of the regulator. J= Clearance to service regulator vent outlet *(min. 36"/90cm) K= Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance *(12"/30cm) L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m) M= **Clearance above paved sidewalk or a paved driveway located on public property *(min. 84"/2.
INSTALLATION RIGID PIPE VENTING COMPONENTS LIST All Simpson Dura-Vent components are available directly from FPI.
INSTALLATION RIGID PIPE VENTING SYSTEMS Horizontal or Vertical Terminations Alternate Horizontal Termination Caps WARNING: Do not combine venting components from different venting systems. However use of the the AstroCapTM and FPI Riser is acceptable with all systems. This product has been evaluated by Intertek for using a Dura-Vent Flue Adaptor in conjunction with Selkirk Direct-Temp and Ameri Vent Direct venting systems.
INSTALLATION Vent or Fireplace Products International Ltd. 4) Installation other than as instructed by Simpson Dura-Vent and Fireplace Products International Ltd. Warning: Always maintain required clearances (air spaces) to nearby combustibles to prevent a fire hazard. Do not fill air spaces with insulation.
INSTALLATION Horizontal Venting with Two (2) 90o Elbows One 90o elbow = Two 45o elbows. Option V A) 3' Min. B) 5' Min. C) 8' Min. H + H1 2' Max. 3' Max. 4' Max. With these options, maximum total pipe length is 30 feet with minimum of 8 feet total vertical and maximum 4 feet total horizontal. Please note minimum 1 foot between 90o elbows is required. Lengths do not include elbow indicated Vent restrictor position A (fully open), refer to page 11.
INSTALLATION DV STOVE HORIZONTAL VENT KIT DV Stove Horizontal Vent Kit (2 ft. Part # 946-116 or 4 ft. Part # 946-216) includes all the parts needed to install the U39 with minimum horizontal and vertical vent dimensions. For installations that require longer vertical and/or horizontal vents use the Dura-Vent system as shown on page 15. Qty. Description 1 Rigid Pipe Section (Kit # 946-116: 2 ft. (1.2m) length, Kit # 946-216: 4 ft. (1.
INSTALLATION Note: if the centerline cannot be met, the adjustable sections will have to be cut. e) Cut the 2 ft. or 4 ft. section of rigid pipe to length. Ensure that the pipe length when cut will seat onto both the starter collar and the 90o elbow. Crimped section of rigid pipe seats into the 90o elbow. Only cut the uncrimped side of pipe. Dismantle all pipe sections including vent terminal. 3) Attach the 4" dia.
INSTALLATION DURA-VENT TERMINATION KIT Planning Your Dura-Vent Installation There are two basic types of Dura-Vent Direct Vent System installations: horizontal termination and vertical termination. Confirm the maximum horizontal run and maximum vertical rise from the diagrams on pages 8-13. Note: These are the minimum pieces required. Other parts may be required for your particular installation. See page 13 for a list of vent parts.
INSTALLATION 963 943 943S 953 950 988 942 11"-14 5/8" Adj. Pipe Length-Black 17"- 24" Adj. Pipe Length Black 45O Elbow Galv. 45O Elbow-Black 45O Elbow-Swivel Galv. 45O Elbow-Swivel-Black 90O Elbow Galv. 90O Elbow-Black 90O Elbow-Swivel Galv. 90O Elbow-Swivel-Black High Wind Term. Cap (Vertical) Vertical Term. Cap Horiz. Sq. Term. Cap Horiz. Sq. High Wind Term. Cap Snorkel-14" Rise Term.Cap Snorkel-36" Rise Term.
INSTALLATION Below Grade Installation If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the Snorkel Termination. Refer to Dia. 4. Do not attempt to enclose the Snorkel within the wall, or any other type of enclosure. Note: If installing termination on a siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.
INSTALLATION 4) Assemble the desired lengths of black pipe and elbows necessary to reach from the appliance adaptor up though the Round Support Box. Insure that all pipes and elbow connections are in the fully twistlocked position and sealed. 5) Cut a hole in the roof centred on the small drilled hole placed in the roof in Step 2. The hole should be of sufficient size to meet the minimum requirements for clearance to combustibles of 1-1/4".
INSTALLATION Using a level, make sure the support is vertical. If the support extends above the roof, cut it flush with the top of the roof. Nail the support to the frame opening using (8) 3" spiral nails or #8 x 1-1/2" screws. Note: If you are using a 6" square support you may find it difficult to screw it in place because it is fairly small inside.
INSTALLATION 4) Pass the flex pipe down through the center of the chimney system, and center the adaptor on the top of the chimney pipe. Drill four 1/8" diameter holes through the adaptor and into the chimney top. Insure that you are in fact, drilling into the metal on the chimney. Twist-lock the Termination Cap (Part# 980 or 991) onto the Adaptor. (Diagram 3 and 4). Converting a Masonry Chimney Important: The existing masonry flue opening needs to have an area of at least a 36 sq. in.
INSTALLATION System Data U39 with 40,000 BTU U39-NG: For 0 to 2000 feet altitude U39-LP: For 0 to 4500 feet altitude Burner Inlet Orifice Sizes: Natural Gas Burner #32 Propane #50 Max. Input - Natural Gas/Propane 38,000 Btu/h Diagram 9 9) Slide the Wall Thimble Cover (Part # 940) over the Retro Connector and secure with masonry bolts. Diagram 10.
INSTALLATION CONVERSION FROM NATURAL GAS TO PROPANE THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !! Conversion Kit #730-969 Contains: 7) Unscrew the pilot orifice with the allen key and replace with the LP pilot orifice in the kit. Qty.
INSTALLATION CONVERSION TO LOWER BTU RATING THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !! Natural Gas Conversion Kit 730-920 Contains: Qty. Part # Description 1 904-240 Burner Orifice #37 (Natural Gas) 1 918-034 Decal "Converted to 30,000 Btu" 1 918-033 Instruction Sheet Propane Conversion Kit 730-922 Contains: Qty.
INSTALLATION Caution: Carbon will be produced if the air shutter is closed too much. Note: Any damage due to carboning resulting from improperly setting the aeration controls is NOT covered under warranty. Note: Aeration Adjustment should only be performed by an authorized Regency Installer at the time of installation or service. AERATION ADJUSTMENT The burner aeration is factory set but may need adjusting due to either the local gas supply or altitude.
INSTALLATION 7) Place the Left Top Log D)02-46 on the pin on Log B)02-56 and on top of the cutout on Log A)02-65. 11) Position notch in Front Right Log G)02-48 on Log F)02-47 and push the bottom right edge against the bracket on the burner tray. A)02-65 D)02-46 E)02-45 C)02-44 Cutout Pin 2) Slide the door onto the two hinge pins maksure the two pieces are flush together. See diagram 1. ing 3) Close the door. The latch plate must be centered around the alignment pin. See diagram 2.
INSTALLATION WIRING This heater does not require a 120V A.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/ thermostat will continue to operate. However, a 120V A.C. power supply is needed for the fan/ blower operation. Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges. CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
OPERATING INSTRUCTIONS CAUTION Do not connect the millivolt remote control wires to the 120V wires. 3) Install 3 AAA alkaline batteries in transmitter and 4 AA alkaline batteries in the receiver. Install the receiver and its cover in the wall. Switch the remote receiver to "remote" mode. The remote control is now ready for operation. FINAL CHECK Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly.
OPERATING INSTRUCTIONS Copy of the Lighting Plate instructions NORMAL OPERATING SOUNDS OF GAS APPLIANCES It is possible that you will hear some sounds from your gas appliance. This is perfectly normal due to the fact that there are various gauges and types of steel used within your appliance. Listed below are some examples. All are normal operating sounds and should not be considered as defects in your appliance.
MAINTENANCE MAINTENANCE INSTRUCTIONS 1) Always turn off the valve before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year. When cleaning the logs, use a soft clean paint brush as the logs are fragile and easily damaged. 2) Clean glass (never when unit is hot), appliance, louvers, and door with a damp cloth. Never use an abrasive cleaner.
MAINTENANCE LOG REPLACEMENT Note: Wearing gloves will protect your hands while handling glass. The unit should never be used with broken logs. Turn off the gas valve and allow the unit to cool before opening door to carefully remove the logs. The pilot light generates enough heat to burn someone. If for any reason a log should need replacement, you must use the proper replacement log. The position of these logs must be as shown in the diagram under Log Installation.
MAINTENANCE 7) Tighten side panels nuts using the following procedure: a. tighten top & bottom outside corner nuts (2) b. tighten inside nuts (3) c. tighten top & bottom inside corners (2) 8) Tighten the 10 nuts on center glass retainer. 9) Repeat step 7 for other side panel. To remove U39 fan: 1) Unplug or disconnect power source to stove. 2) Remove all logs and the rear log support, then remove the 10 screws holding the access panel in place. 3) Unclip the black and white wires from the fan motor.
MAINTENANCE REMOVING VALVE If your valve requires maintenance or replacement, use the following instructions: 10) To replace the burner tray assembly, simply reverse these instructions. Note: Always close off the gas supply before removing the valve. 1) Open front pedestal door. You may want to put a soft cloth on the base of the unit so that when the pedestal door is open it doesn't scratch the paint. 5) At this point you should disconnect the gas at the valve.
PARTS LIST U39 MAIN ASSEMBLY Part # 1) 9) 10) 11) 12) 15) 16) 17) 18) 19) 20) 21) 23) 24) 25) 26) 27) 28) 560-920 560-921 560-922 730-560 730-034 730-517/P 910-331/P 910-794 910-330 * 730-039 904-257 560-025 730-530 730-525 560-031 904-258 948-255 * * 910-233 * Description Louver Assy - Gold Louver Assy - Brush Nickel Louver Assy - Black Relief Door Assembly Mounting Plate Gasket Fan Assembly Fan Motor (120 Volt) Power Cord (120 Volt) Fan Speed Control Pedestal Assembly Pedestal Door Pedestal Door Magne
PARTS LIST U39 BURNER & LOG ASSEMBLY Part # 51) 52) 53) 54) 55) 56) 57) 58) Description 910-241 910-190 904-586 910-373 910-372 908-646 650-220 910-330 Burner ON/OFF Switch (3-way) Piezo Ignitor & Nut Knob for Fan Speed Control Knob - Pilot Valve Extension Flame Adjusting Knob Control Panel Decal Control Panel Plate Fan Speed Control (120 V) 730-574/P Valve Assembly - Natural Gas 730-576/P Valve Assembly - Propane 60) 910-378 910-380 Valve S.I.T. - NG Valve S.I.T.
PARTS LIST U39 DOOR ASSEMBLIES Part # 101) 105) 106) 107) 108) 111) 112) 208) 730-923 730-924 730-926 730-932 730-928 650-920 * 940-323/P 936-243 940-322/P * 750-015 940-325/P Description Brush Nickel Mitred Door - Complete Gold Mitred Door - Complete Black Mitred Door - Complete Gold Wrap Door - Complete Gold Panel Door - Complete Door Gasket Kit Ceramic Paper Side Glass Glass Gasket Centre Glass Door Frame Fibre Paper Door Glass Extrusion Wrap Glass *Not available as a replacement part.
NOTES _____________________________________________________________________________________ ____________________________________________________________ __________________________________________________________ ____________________________________________________________ _______________________________________________________ _____________________________________________________ __________________________________________________________ _________________________________________________________ ___________
NOTES _____________________________________________________________________________________ ____________________________________________________________ __________________________________________________________ ____________________________________________________________ _______________________________________________________ _____________________________________________________ __________________________________________________________ _________________________________________________________ ___________
NOTES _____________________________________________________________________________________ ____________________________________________________________ __________________________________________________________ ____________________________________________________________ _______________________________________________________ _____________________________________________________ __________________________________________________________ _________________________________________________________ ___________
WARRANTY Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each original purchaser of a Regency Product. This warranty is not transferable. unitthoroughlybeforeitleavesourfacility.FPIFireplaceProductsInternationalLtd.
Regency fireplace products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our door. Fireplace Products International Ltd. is pleased to extend this Limited Lifetime Warranty to the original purchaser of a Regency Product. See the inside back cover for details. Register your Regency online at http://www.regency-fire.