Instructions / Assembly

POWER INLET ASSEMBLY
CAT. NOS: PK20, PK30, PK50
INSTALLATION INSTRUCTIONS
IMPORTANT: Installation of this power inlet and related wiring must be done by a qualified electrician
in compliance with all applicable electrical codes.
Specifications:
Reliance Power Inlet Power Inlet Cord Connector
Model Rating Configuration Configuration
PK20 20 A., 125/250 VAC NEMA L14-20 NEMA L14-20R
PK30 30 A., 125/250 VAC NEMA L14-30 NEMA L14-30R
PK50 50 A., 125/250 VAC CS6375 CS6364 or CS6364N
In this package, you will find the following parts:
Installation:
This power inlet assembly is designed to mount in a 2-1/2 inch trade size knockout opening in any Panel/Link
®
Series Reliance Transfer Panel, or comparable enclosure.
1. Locate and remove any convenient 2-1/2 inch trade size (3-inch diameter) knockout opening.
It may be on the side or bottom of the enclosure, but must be located a sufficient distance from
adjacent equipment or obstructions to permit insertion of the power cord connector from the
generator.
2. Raise the hinged cover and temporarily prop it in a 90 degree open position by inserting the 5/8
in. wide shim between the cover and the base, just beneath the hinge. This will permit easy
access to the mounting screws. See following diagram.
Mounting Bracket
(this is the only component
installed inside the enclosure)
Gasket
Shim
Hinged Cover
Assembly
Flanged
Power Inlet
Screws (3)
8-32 x 3/4"