© 2018 Relion Battery, LLC. All rights reserved. Relion Battery is not liable for damages that may result from any information provided in or omitted from this publication, under any circumstances. Relion Battery reserves the right to make adjustments to this publication at any time, without notice or obligation.
Charging Instructions 06.13.18
CHARGING INSTRUCTIONS
RELiON LITHIUM IRON PHOSPHATE (LiFePO4) BATTERIES
To ensure your Lithium Iron Phosphate (LiFePO) battery provide its maximum life, follow these Charging Instructions. When
charging LiFePO make sure that you are not using a charger meant for other lithium ion chemistries, which are typically set to a
higher voltage than required by LiFePO batteries. A lead-acid battery charger can be used if the voltage settings are within the
parameters of LiFePO batteries.
Charger Inspection
Check that your charger cables are insulated and free of breakage. Charger terminal connectors should be clean and properly
mate with the battery terminals to ensure a good connection and optimum conductivity.
Charging Guidelines
When to Charge your LiFePO4 Battery
If LiFePO batteries are not fully discharged, they do not need to be charged after each use. LiFePO batteries do not get damaged
when left in a partial state of charge (PSOC). You can charge your LiFePO batteries after each use or when they have been
discharged up to 80% (20% SOC). If the Battery Management System (BMS) disconnects the battery due to low voltage, at 100%
depth of discharge, remove the load to reconnect the battery circuit and charge immediately. Please note that we recommend
storing batteries at 50% state of charge (SOC) to minimize irreversible capacity loss.
Charging Temperature
LiFePO batteries can safely charge between -20°C to 55°C (-4°F to 131°F). However, at temperatures below 0°C (32°F) the charge
current must be reduced, until the temperature is >0ºC (32ºF), as follows:
1. 0°C to -10°C (32°F to 14°F) charge at 0.1C (10% of the battery capacity)
2. -10°C to -20°C (14°F to -4°F) charge at 0.05C (5% of the battery capacity)
LiFePO batteries do not require temperature compensation for voltage when charging at hot or cold temperatures.
All Relion LiFePO come with a BMS that protects the battery from over-temperature. If the BMS disconnects due to high
temperature, wait until the temperature reduces and the BMS reconnects the battery circuit before using or charging the battery.
Please refer to your battery data sheet for the BMS high temperature cut-o value.
Charging with Lead-Acid Battery Chargers
Most lead-acid battery chargers can be used with LiFePO batteries as long as they are within the appropriate voltage guidelines.
AGM and Gel algorithms typically fall within the LiFePO voltage requirements. The voltage for flooded battery charging algorithms
are often higher than LiFePO requirements, which will result in the BMS disconnecting the battery at the end of the charge cycle
and possibly result in the charger displaying an error code. If this happens, it is generally a good practice to replace your charger
for one with a LiFePO charge profile. Since the BMS protects the battery, using lead-acid chargers will typically not damage the
battery.