Service manual

40
Remeha Avanta 18v
59970LTGBW7H024a
59970LTGBW7H026b
3 to 4 mm
>1 min
59970LTGBW7H0234
59970LTGBW7H026
3.1.2 Checking the condensate siphon
Check the condensate siphon. Remove any dirt residues
and refill with clean water to the mark.
3.1.3 Checking the ignition electrode
Check the ionisation /ignition electrode for:
- deposits (remove any white deposits with abrasive cloth);
- the adjustment of the ignition electrode (between 3 and 4
mm);
- the quality of the gasket and condition of the porcelain (this
should not be cracked);
Check the ionisation current after 1 minute on the display
code fl, see par. 2.10.6.
If the read-out value is lower than 3 or higher than 9µA, check
cable and connections are sound if OK
replace the ignition electrode.
The ignition cap is fixed on the ignition electrode and therefore
cannot be removed.