Condensing Boilers High efficiency wall hung condensing boiler with ultra low NOx emission QUINTA RANGE OUTPUTS Q30: 5.6 - 28 kW Q45: 7 - 40 kW Q65: 11 - 61 kW Q85: 14.4 - 84.
Introduction Remeha Quinta Range are compact wall hung condensing boilers. Lighter and more efficient, their small dimensions make them ideally suited for modular arrangements. An optional optimising/ weather compensating control system is available to ensure maximum efficiency. The boilers can be installed on both new and retrofit installations. Boiler description The Remeha Quinta Range are wall hung, condensing boilers which may also be installed free standing on a suitable frame (option).
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15.
Advantages at a glance • High efficiency: 110% NCV at 40/30ºC (99% GCV) • Boiler control: a) Modulating (18-100%) b) High/low (18-100%) c) On/off • Premix burner for clean combustion • Low NOx < 25ppm (02=0%, dry) • Quiet operation <48 dBA • Digital display Operating principle Combustion air is drawn into the closed air box, by a variable speed fan, through the air inlet connection from the plant room (open flued) or from outside via the concentric flue system (room-sealed).
Boiler type Quinta 30 Quinta 45 Quinta 65 Quinta 85 Quinta 115 General Casing colour BS RAL 9016 Boiler control options (External input) On/off, High/low, Analog 0-10V (Two wire control) Communicating Modulation Nominal output (80/60ºC) kW 5.6 - 28.0 8.0 – 40.0 12.0 – 61.0 14.1 - 84.2 Nominal output (40/30ºC) kW 5.9 - 29.6 8.9 – 43.0 13.3 – 65.0 15.8 - 89.5 18.4 - 114 Nominal input (GCV / Hs) kW 6.3 - 31.6 9.1 – 45.7 13.6 – 68.8 16.2 - 95.3 19.1 - 123.
Typical installation Showing Quinta 45/65/85/115 (Quinta 30 flow and return connection are reversed) Single boiler Single boiler with low loss header With DHW-Remeha priority - Quinta 45/65 Multiboiler 6 For Quinta 85/115 use a DHW primary pump
Based on 80°c/60°c Flow Boiler side 20°ΔT/System Side 11°ΔT No.
Conventional flue Bird guard and reduction cone Calculation data – conventional flue max eq. length eq. length bend 45° eq. length bend 90° Quinta 30 80mm Quinta 45 80mm Quinta 65 100mm Quinta 85 100mm Quinta 115 100mm 40 1.2 4 33 1.2 4 27 1.4 4.9 24 1.4 4.9 19 1.4 4.9 m m m CLV system (twin pipe - two zone) Bird guard and reduction cone Bird guard Calculation data – different pressure zones max eq. length eq. length bend 45° eq.
General Low water protection (flow and content) The Remeha Quinta Range is supplied as standard with electronic control and flame ionisation safety controls, with a specially designed microprocessor at the heart of the control system. The Remeha Quinta Range are supplied with a low water protection on the basis of temperature measurement. By modulating back at the moment that the water flow threatens to fall too low, the boiler is kept operating for as long as possible.
Boiler control The Remeha Quinta Range can be controlled using one of the following methods Modulating (two wire control) When using the optional Remeha compensating controllers the heat output modulates between the minimum and maximum value on the basis of the boiler flow temperature sensor. This applies to both single and multiple boiler installations, under the dictates of a room and/or outside temperature sensor. Celcia 20 - Optimising room/outside weather compensating control for single boiler.
Frost protection Temperature control Install the boiler in a frost-free room. The builtin frost protection system is activated as follows: Below 7°C - system pump is switched on if connected to boiler. Below 3°C - boiler is switched on, when the flow temp reaches 10°C the boiler and pump switch off. With a Remeha temperature sensor or with a standard (volt free) DHW thermostat. Note: will only provide a setting and read out facility with the sensor option.
Remeha House Molly Millars Lane Wokingham Berkshire RG41 2QP T: 0118 978 3434 F: 0118 978 6977 E: boilers@broag-remeha.com www.remeha.co.uk The data published in this technical sales leaflet is based on the latest information (at date of publication) and may be subject to revisions. It should be read in conjunction with our full technical brochure (available on request).