Technical information

Remeha Quinta 85
28
End point (10 Volt): adjustable between +51°C and (( (+299)°C, factory default
)0 (100)°C.
This value sets the required flow temp at 10 Volt signal input (restricted by the max
flow set point).
NOTE: These settings are only applicable when boiler control operation parameter
(A) has the x value set to 4.
6.7 Read-out mode (X00)
To check boiler set points and values.
Using the ‘m’-key, press repeatedly until !(flashing dot) appears in the ‘code’-display.
Then select the required code @, # or $ etc. using the ‘s’-key.
Code Description
Read-out
(example)
!
Actual flow temperature
80
@
Actual return temperature
70
#
Actual DHW temperature
(only with sensor connected)
58
$
Actual outdoor temperature
(only with sensor connected)
05
%
n/a
3&
^
Flow temperature (set point)
80
&
Actual heat demand status
1x = demand;
0x = no demand
*
Calculated HTG cut-in temperature
67
(
Actual flow temperature rise [0.1 °C/sec]
02
A
n/a
Table 10 Read-out mode user level
6.8 Fan speed mode (<00)
Using the ‘m -key, press repeatedly until ‘code’-display shows alternate flashing half
digits.The value in the t-display shows the actual fan speed using two alternate
double digits as table: