REMKO ATY ATY 261 DC, ATY 351 DC Inverter wall - room air conditioner in split - design Operation · Technology · Spare parts Edition GB – V08
Contents Safety notes 4 Environmental protection and recycling 4 Warranty 4 Transport and packaging 5 Equipment description 5 Operation 6-14 Shutdown 15 Care and maintenance 15-16 Troubleshooting and customer service 17-18 Control and resistance 19 Installation instructions for qualified personnel 20-23 Installation 23-25 Monitoring for leaks 25 Condensate drain 26 Electrical connection 26-27 Electrical connection diagram 27 Electrical circuit diagram 28 Before commissionin
REMKO ATY Safety notes Carefully read this manual before putting commissioning the equipment. It provides useful tips and information as well as hazard warnings to prevent injury or material damage . Failure to follow the directions in this manual can result in endangerment to persons, the environment and the equipment itself and will void any claims for liability. ■ Keep this manual and the refrigerant datasheet near the unit. ■ The unit may only be set up and installed by qualified personnel.
Transport and Packaging The equipment is shipped in sturdy transport packaging. Immediately check the equipment on delivery and make note of any damage or missing parts on the delivery note and inform the forwarding agent and your contractual partner. No warranty can be assumed for later claims. Equipment description The ATY 261-351 DC room air conditioning units have a REMKO ATY...AT outdoor component as well as an ATY...IT indoor unit.
REMKO ATY Operation The indoor unit is easily operated using the standard infrared remote control. The indoor unit beeps to acknowledge the correct transmission of data. If it is not possible to program the indoor unit using the remote control, it can also be manually operated. Manual operation Display on indoor unit The indoor unit can also be started manually. To do so, press the button on the right side of the unit to activate the automatic mode. The display illuminates according to the settings.
Buttons on the remote control 3. Heating mode In this mode, the warm air in the room is warmed to the desired temperature. 4. Air circulation mode In this mode, the air in the room is recirculated. "ON/OFF" Button Press this button to start the unit. " "button This button is used to set the desired temperature between 18°C and 30°C. "MODE"button Use this button to select the operating mode. The indoor unit has 5 modes: 1. Automatic mode In this mode, the unit works in cooling or in heating mode. 2.
REMKO ATY Button functions A symbol is shown on the display to indicate that the settings are being transferred. ON/OFF Button By pressing the ON / OFF button, you can activate or deactivate your unit. The programmed settings and adjustment values before the unit was turned off will appear on the display. ON/OFF / Button ON/OFF The remote control has its own temperature display. If buttons / are pressed alternately, the display changes to .
AUTOMATIC MODE In automatic mode, the controller autonomously selects between heating and cooling operation when the unit is first turned on. A nominal temperature of 24 °C is preset. MODE Cooling MODE AUTOMATIC In cooling mode, the air in the room is cooled down to the set nominal temperature. The desired room temperature is set with the ▲/▼buttons in 1 °C increments. If the room temperature is 1 °C above the selected nominal temperature, the indoor unit starts to cool the air in the room.
REMKO ATY Heating MODE In the heating mode, you can heat the room in spring or fall. The desired room temperature is set with buttons / in 1 °C increments. If the room temperature is 1 °C below the selected nominal temperature, then the indoor unit starts to warm up the air in the room. If the adjusted room temperature is exceeded by approx. 0.5°C, then the controller turns the heater function off.
Dehumidification MODE In dehumidification mode, the room temperature cannot be set. Due to the low temperature of the refrigerant, the dew point of the air at the condenser is undercut. The excess moisture in the air is condensed on the condenser, the room is dehumidified. The fan has four speeds. Neither the ion generator nor turbo mode can be selected in this mode.
REMKO ATY SWING Button (covered) The oscillating function of the air discharge fins can be adjusted with this butto. This makes it possible to switch directly between a fixed position and the oscillating function. The air distribution in the room is improved using the swing function. SLEEP Button This button activates a programming function, which causes the nominal temperature in cooling mode to increase after one hour by 1°C and after two hours by 2 °C.
PROGRAMMINGTIMER ON The controller turns the unit on after programming. During operation, all settings can be seen on the display. Out of operation, only the timer settings are visible. Timer on PROGRAMMING TIMER OFF 30 sec. The controller turns the unit off after programming. During operation, all settings can be seen on the display. Out of operation, only the timer settings are visible. Timer off PROGRAMMING TIMER ON/OFF HR/MIN HR/MIN 30 sec.
REMKO ATY INDOOR UNIT DISPLAY SET TURBO C By pressing the "ION" button several times, the "ION" function, the "Turbo" function, or both can be set at the same time. Ion function The unit is equipped with an ion generator to generate negative ions. A high concentration of negative ions is found for example in mountains, near waterfalls and in forests and people perceive this inhaled air as "clean". Only a slight ion concentration is found in interior rooms.
Shutdown Care and maintenance Temporary Shutdown Regular care and maintenance serves to ensure trouble-free operation and long service life of the unit. 1. Allow the indoor unit to run for 2 to 3 hours in air circulation mode or in cooling mode at the maximum temperature setting in order to remove any residual moisture from the unit. 2. Shut down the unit using the remote control.
3. Push the clips on the filter up and pull it out on the clips (figure 4). • • • • • • • • • • General Measure voltage and current Check function of compressor Check fan function Contamination of evaporator fins Check refrigerant fill quantity Check condensation drain Test insulation Check moving parts 4. Clean the filter with a standard vacuum cleaner. Turn the dirty side upward (figure 5). Sealing test for refrigerant circuit 1) see note S.15 2 Open front cover 5.
Troubleshooting and customer service The equipment and components are manufactured using state-of-the-art production methods and tested several times to verify their correct function. If malfunctions should occur, please check the functions as detailed in the list below.
REMKO ATY Problem display by blinker code LED in AT Display No. No. No. 16 17 18 red yellow green ER01 flashes - - - ER02 flashes - - - ER03 flashes - - - ER04 flashes - - ER05 flashes - ER06 flashes Fault description Air circulation sensor on indoor unit is defective / triggered Indoor unit power supply defective Checks Remedial measures Check resistance (see p.
Controller, safety controller and resistance Hot gas sensor, IPM AT sensor Resistance Temp. AT condenser sensor, AT ambient temperature sensor IT vaporiser sensor, IT circulation sensor Resistance Temp. 0 160.73 kΩ 5 125.57 kΩ 0 27.42 kΩ 10 98.78 kΩ 5 22.15kΩ 15 78.23 kΩ 10 18.00 kΩ 20 62.35 kΩ 15 14.72 kΩ 25 50.00 kΩ 20 12.10 kΩ 30 40.33 kΩ 25 10.00 kΩ 30 8.31 kΩ AT compressor Temp. Resistance 0.
REMKO ATY Installation instructions for qualified personnel Important notes prior to installation NOTE The assembly and installation of the units and components may only be carried out by especially trained technicians. ■ Transport the unit in its original packaging as close as possible to the installation location. You avoid transport damages by doing so. ■ Check the contents of the packaging for completeness and check the unit for visible transport damage.
Wall openings Selection of the installation location Wind ■ A wall opening of at least 70 mm diameter and 10 mm slope from the inside to the outside must be made for each indoor unit. The indoor unit is designed for horizontal wall installation in the upper wall area (at least 1.75 m from the upper edge - floor). However, it can also be used in the upperwall area above doors. If the unit is being installed in windy areas, ensure that the warm outlet air discharges in the main wind direction.
REMKO ATY Installation inside buildings ■ Ensure that heat can dissipate adequately when placing the outdoor component in cellars, attics, adjoining rooms or halls (figure 7). ■ Install an additional fan with a rated flow comparative to that of the outdoor component being installed in the room.
Installation Oil return measures NOTE If the outdoor unit is installed at a higher level than the indoor unit, we recommend that suitable oil return measures are taken. Usually an oil pump bend is installed for every 2.5 metres of height difference. Outdoor component max. 5 m Oil pump bend in suction pipe to outdoor component 1 x every 2.5 metres of rise in the line Open display cover 9 Remove screws Installation may only be performed by authorised specialists.
REMKO ATY Connecting the refrigerant lines The on-site connection of the refrigerant lines is undertaken inside the unit. It may be necessary to fit a reducer or flared adapter to the indoor unit. These fittings are included with the indoor unit as an accessory kit. Once installed, the connections should be sealed to prevent vapour diffusion. CAUTION The units are factory filled with dry nitrogen to check for leaks. The pressurised nitrogen is released when the union nuts are loosened.
Monitoring for leaks 12 Deburring the refrigerant line Refrigerant line Once all the connections have been established, the pressure gauge station is attached as follows to the Schrader valve (if fitted): red Deburrer = small valve = injection pressure blue = large valve = suction pressure 13 Flanging the refrigerant line Flanging tool After completed connection, the leakage test is carried out with dry nitrogen.
REMKO ATY Condensate drain Due to the dew point shortfall on the vaporiser, condensation is created on the indoor unit during the cooling operation and on the outdoor unit during the heating operation. Below the vaporiser is a collection tray, which must be connected to a drain. ■ The condensation line is to be installed with a minimum slope of 2 %. (figure 11). If necessary, fit vapour diffusion tight insulation. ■ Lead the condensation line freely to the run-off line.
Connecting the outdoor component Connecting the indoor unit Figure 17 Proceed as follows to connect the cable: 1. Remove the cover from the unit. 2. Remove the side panel next to the terminals. Terminal bar / control bar 3. Feed the cables through the ferrite core supplied in the delivery (figure 17+18). Mains cable Figure 18 4. Feed the cable through the edge protection ring of the fixed connection plate. 5. Connect the cable as shown on the electrical connection diagram. 6.
REMKO ATY Electrical circuit diagram ■ Check the refrigerant lines and insulation for damage. ATY 261 DC AT / ATY 351 DC AT Test Air-intake sensor J1 Condenser sensor Hot gas sensor L in L N N L C A IPM Sensor B J4 J1 N out P out P N N out P out P N Control board W V U IPM inverter power drive W V U W W V V U U Compressor J2 LDC N-Out AC N ■ Check that all fastenings, mountings etc. are firm and at the correct level.
Commissioning NOTE Commissioning is only to be performed and documented by specially trained personnel. Once all the components have been connected and tested, the system can be commissioned . A functional check should be performed to verify its correct function and identify any unusual operational behaviour prior to handing it over to the operator. Function test of Cooling operating mode 1. Remove the caps from the valves. 2.
REMKO ATY Unit dimensions ATY 261 DC AT / ATY 351 DC AT 265 623 245 532 720 All values in mm ATY 261 DC IT / ATY 351 DC IT 470 495 567 567 148 47 45 25 396 All values in mm We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
Technical data Series ATY 261 DC Operational mode ATY 351 DC Inverter-wall room air conditioner combination for cooling and heating Nominal cooling output 1) kW 2,69 (1,00-2,93) 3,52 (1,2-3,87) Nominal heating output2) kW 2,93 (1,00-3,20) 3,87 (1,20-4,10) Energy efficiency class, cooling EER1) A A Energy efficiency class, heating COP2) A B 3,68 3,56 3,64 3,49 495 Energy efficiency ratio EER 1) Coefficient of performance COP 2) Power consumption, annual, (500h) K / H kWh 365 Ope
REMKO ATY Exploded view ATY 261 DC IT / ATY 351 DC IT 1 3 17 15 13 7 4 5 11 2 10 5 12 7 6 16 14 14 7 9 8 We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process. Spare parts list No.
Exploded view ATY 261 DC AT / ATY 351 DC AT 14 12 13 1 14 5 10 14 11 8 7 9 3 4 2 15 16 6 We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process. Spare parts list No. Designation ATY 261 DC AT ATY 351 DC AT 1 Front panel 1107421 1107421 2 Fan blade, condenser 1107422 1107422 3 Fan motor, condenser 1107449 1107424 4 Ribbed condenser 1107444 1107426 5 Side panel, right 1107475 1107475 6 Compressor, cpl.
REMKO ATY 34
Notes 35
REMKO ACROSS EUROPE … and also right in your neighbourhood! Make use of our experience and advice Consultation Thanks to intensive training, our consultants are always completely up-to-date in terms of technical knowledge. This has given us the reputation of being more than just an excellent, reliable supplier: REMKO, a partner helping you find solutions to your problems.