Operation Manual

REMKO ATY
26
Series ATY 261 ATY 351
Operating mode Wall-mounted air-conditioning unit for cooling applications
Nominal cooling output
1)
kW 2.67 3.56
Energy efficiency class, cooling
1)
B C
Energy efficiency ratio EER
1)
3.06 2.87
Operating range (room volume), approx. 80 110
Working range, indoor unit °C +16 to +32
Adjustment range, cooling °C +18 to +30 +18 to +30
Refrigerant R 410A
Max. operating pressure / per refrigerant circuit
kPa 4200 / 4200
Air flow rate per stage m³/h 360/390/420 380/410/440
Noise output per stage
3)
dB(A) 33/36/40 35/37/41
Voltage supply V/Hz 230 / 1~ / 50
Protection degree IP X0
Nom. electrical power consumption, cooling
1)
kW 0.03 0.04
Nom. current consumption, cooling
1)
A 0.16 0.20
Refrigerant connection, injection pipe Inches(mm) 1/4 (6.35)
Refrigerant connection, suction pipe Inches(mm) 3/8 (9.52) 1/2 (12.70)
Condensation connection mm 16 16
Dimensions Height mm 567 567
Width mm 567 567
Depth mm 148 148
Weight kg 12.0 12.0
Serial number 775... 776...
Computerised part no. 1621261 1621351
Technical data
1) Air inlet temperature TK 27°C / FK 19°C, outdoor temperature TK 35 °C, FK 24 °C, max. air flow rate in combination with RXM 226 / RXM 335
2) Distance 1 m free air