REMKO ATY ATY 260, ATY 350 Wall - room air conditioner in split design Operation · Technology · Spare parts Edition GB – T08
Contents Safety guidelines 4 Environmental protection and recycling 4 Warranty 4 Transport and packaging 5 Product description 5 Operation 6-13 Shut down 14 Care and maintenance 14-15 Troubleshooting and customer service 16-17 Assembly instructions for technicians 18-21 Installation 21-22 Leakage test 23 Condensation connection 24 Electrical connection 24-25 Electrical circuit diagram 25 Electrical connection diagram 26 Before start up 26 Add refrigerant 26 Start up 27
REMKO ATY Safety guidelines Before using your unit for the first time, carefully read the operating instructions for your unit. It contains useful tips , remarks as well as warnings to avoid danger to personnel and property. Non-observance of these instructions can endanger persons, the environment and the system and therefore lead to loss of any possible warranty claims. ■ ■ ■ ■ Keep these operating instructions and the refrigerant data page near the unit.
Transport and packaging The units are delivered in strong transport packaging. Please check the units immediately at delivery and note any damage or missing parts on the shipping papers and inform the carrier and your contracting party. No warranty can be assumed for later claims.
REMKO ATY Operation The interior unit can be comfortably operated with the standard infrared remote control. The proper data transfer is confirmed by the interior unit with a signal sound. If programming via the infrared remote control is not possible, then the interior unit can also be operated manually. Manual operation Display on interior unit The interior unit can also be operated manually. To do so, press the button on the right side of the unit to activate the automatic mode.
Buttons of remote control 2. Cooling mode In this mode, the cold air in the room is cooled down to the desired temperature. 3. Heating mode In this mode, the warm air in the room is warmed up to the desired temperature. 4. Air circulation mode In this mode, the air in the room is recirculated. 5. Dehumidification mode In this mode, the room is mainly dehumidified, the adjusted temperature is retained. „FAN“ button Buttons of remote control „ON/OFF“ button Press this button to operate the unit.
REMKO ATY Button functions The transmission of the settings is shown by a symbol in the display. ON/OFF button By pressing the ON / OFF button, you can activate or deactivate your unit. The programmed settings and adjustment values before the unit was turned off will appear in the display. ON/OFF / buttons ON/OFF The remote control has its own temperature display. If buttons / are pressed alternately, the display changes to .
AutoMATIK mode In automatic mode, the regulation autonomously selects between heating and cooling operation, when the unit is first turned on. A nominal temperature of 24 °C is preset. The regulating range is between 22 °C and 26 °C. It can be increased or decreased by 1 °C with buttons /. The fan speed cannot be changed. MODE Cooling mode In cooling mode, the air in the room is cooled down to the adjusted nominal temperature. The desired room temperature is set with buttons / in 1 °C increments.
REMKO ATY DEHUMIDIFICATION mode In the dehumidification mode, the room temperature can be adjusted between 18 °C and 30 °C. Due to the low temperature of the refrigerant, the dew point of the air on the condenser is lower. The excess moisture in the air is condensed on the condenser, the room is dehumidified. The fan speed cannot be changed. MODE FAN button The fan speed can be adjusted with this button. A selection can be made between low, medium, high and automatic fan speed.
SLEEP button (covered) With the button a programming function is activated, which causes the nominal temperature in the cooling mode to increase after one hour by 1 °C and after 2 hours by 2 °C . In the heating mode, the nominal temperature is decreased after one hour by 1 °C and after 2 hours by 2 °C.
REMKO ATY Programming TIMER OFF TIMER Unit out of operation Programming TIMER ON/OFF SET Programmed time reached The regulation turns the unit on or off after programming. In operation, all settings are visible on the display. Out of operation, only the timer settings are visible. Unit On Unit Off Example: The regulation turns on at 9:00. The unit is in operation until 16:30. TIMER OFF (Covered) This button is used to program a decremental turn off timer.
I FEEL button (covered) The unit determines the actual temperature inside the wall unit. The temperature near the remote control may deviate from that setting. With the button, the temperature measured on the remote control is transmitted to the wall unit, the nominal temperature does not change. A continuing temperature reconciliation with the actual current temperature of the remote control is made approx. every 5 minutes as long as the function is turned on.
REMKO ATY Taking the unit out of operation Care and maintenance Time-limited shut down Regular care and maintenance ensure problem-free operation and long service life of the unit. 1. Let the interior unit run for 2 to 3 hours in air circulation mode or in cooling operation at maximum temperature setting to remove any residual moisture from the unit. 2. Take the unit out of operation with the remote control. 3. Turn the power supply of the unit off. 4.
3. Push the clips on the filter up and pull it out on the clips (Fig. 4). 4. Clean the filter with a commercially available vacuum cleaner. To do so, turn the dirty side upward (Fig. 5). • • • • • • • • • General Check voltage and current Check function of compressor Check function of fan Contamination of evaporator fins Check refrigerant quantity Check condensation discharge Check insulation Check movable parts 5. Carefully clean off any dirt in lukewarm water and with mild cleaner.
REMKO ATY Troubleshooting and Customer service The units and components are manufactured with the most up-do-date manufacturing methods and are checked several times for proper function. However, should a functional problems occur, please check the function according to the chart below.
Problem display by blinker code Display Cause What to do ? 88 blinks Loss of power for 3 minutes Turn off and on again E1 blinks Communication error Display regulation Contact dealer E2 blinks Air circulation sensor on interior unit is defective / triggered Contact dealer E3 blinks Antifreeze sensor interior unit defective / triggered Contact dealer E4 blinks Evaporator fan motor speed too low / defective Contact dealer E5 blinks No cooling / heating output after approx. 30 min.
REMKO ATY Installation instructions for technicians Important notes before installation NOTE The assembly and installation of the units and components may only be carried out by especially trained technicians. ■ Locate the unit in original packaging as close as possible to the installation point to avoid transport damage. ■ Check the contents of the packaging for completeness and check the unit for visible transport damage. Report any damage immediately to your contracting party and the shipping company.
Wall openings ■ A wall opening of at least 70 mm diameter and 10 mm slope from the inside to the outside must be made for each interior unit. ■ We recommend to pad the hole inside or to cover it for example with a PVC pipe to avoid damage to the lines. ■ After installation, the wall opening should be closed off on the building side with a suitable sealant.
REMKO ATY Set up inside a building ■ Make sure there is sufficient heat discharge, if the exterior unit is set up in the basement, the attic, in secondary rooms or hallways (Fig. 7). ■ Install an additional fan with the same air volume flow as the exterior unit installed in the room, which can compensate for any possible additional pressure losses through air channels (Fig. 7). Ensure a continuing unimpaired air supply from outside, if possible through opposite, sufficiently large air openings (Fig. 7).
Installation Oil return measures NOTE If the exterior unit is located at a higher level than the interior unit, then suitable oil return measures must be made. This is usually done by fabricating an oil lift fitting, which is to be installed for each 2.5 ascending meter. max. 5 m exterior unit 3. Remove the front of the unit by lifting the front in the lower area from the body approx. 10 cm and folding it upward (Fig. 10). 10 Release the unit front 11 Pull off the plug 4.
REMKO ATY Connection of refrigerant lines The on site connection of the refrigerant lines is made inside the unit. If necessary, a reducer or expansion fitting must be installed on the interior units. These fittings are part of the accessory kit provided with the interior unit. After assembly, the connections must be insulated impervious to vapor diffusion. CAUTION The units have been filled at the factory with dry nitrogen to check for leaks.
Leakage test 12 Deburring the refrigerant line Refrigerant line When all connections are made, the pressure gauge station is connected to the corresponding Schrader valve connections, if present: red Deburrer 13 = small valve = Injection pressure blue = large valve = Suction pressure Flanging the refrigerant line Flanging tool After completed connection, the leakage test is carried out with dry nitrogen.
REMKO ATY Condensation connection Electrical connection Due to the dew point shortfall on the evaporator, condensation is created on the interior unit during the cooling operation and on the exterior unit during the heating operation. Below the evaporator is a catch pan, which must be connected with a drain. ■ ■ ■ ■ 11 The building side condensation line must be routed at a down slope of min. 2 % (Fig. 11). If necessary, prepare a vapor proof insulation.
Connection of the exterior unit Connection of interior unit Connection of interior unit Make the connection as follows: To connect the line, proceed as follows: 1. Remove the unit cover. 2. Remove the side wall at the connection. 3. Guide the line through the edge protection ring of the fixed connection plate. Terminal bar / control bar Power supply line 4. Connect the line according to the wiring schematic. 1. Remove the front of the unit, as described in chapter „Device installation“. 2.
REMKO ATY Electrical wiring schematic ■ Check the refrigerant lines and insulation for damage. ATY 260 AT / ATY 350 AT RD Reverse valve Control line D C B A Evaporator fan BU BU BU BK YE C BK RD RD R Compressor Color identification S WH = BU = BR = BK = RD = YE = WH RD Condenser, combined White Blue Brown Black Red Yellow ■ Check the electrical connection between the interior unit and the exterior unit for correct polarity. ■ Check all mountings, suspensions etc.
Start up NOTE The start up may only be made by especially trained technicians and must be documented accordingly. After all components are connected and tested, the system can be put into operation. To ensure proper function, a function test should be made to recognize any irregularities during operation of the units before transfer to the client. Function test of Cooling operating mode 1. Remove the caps on the valves. 2.
REMKO ATY Unit dimensions ATY 260 AT / ATY 350 AT 265 623 245 532 720 All measurements in mm ATY 260 IT / ATY 350 IT 470 495 567 567 148 47 45 25 396 All measurements in mm Dimensional and design changes to advance technical progress are reserved.
Technical data Series ATY 260 Operating mode ATY 350 Wall / room air conditioner combination for cooling and heating Nominal cooling output 1) kW 2,69 3,56 Nominal heat capacity 2) kW 3,05 3,99 B B B B 3,02 3,04 3,43 3,41 Energy efficiency class Cooling EER 1) Energy efficiency class Heating COP 2) Energy efficiency size EER 1) Energy efficiency size COP 2) Operating range (room volume), approx.
REMKO ATY Unit illustration ATY 260 IT / ATY 350 IT 1 3 17 15 13 7 4 5 11 2 10 5 12 7 6 16 14 14 7 9 8 Dimensional and design changes to advance technical progress are reserved. Spare parts list No.
Product illustration ATY 260 AT / ATY 350 AT 1 5 7 10 9 8 11 3 2 4 6 Dimension and design changes to advance technical progress are reserved. Spare parts list No. Description ATY 260 AT ATY 350 AT 1 Front wall 1107421 1107421 2 Fan blade, evaporator 1107422 1107422 3 Fan motor, evaporator 1107423 1107424 4 Evaporator fin 1107425 1107426 5 Side section, right 1107427 1107427 6 Compressor, cpl.
REMKO Throughout Europe … and right around the corner from you! Take advantage of our experience and consulting services Consulting service We constantly keep the expert knowledge of our consultants up-do-date through intensive training. This has earned the reputation that we are more than only a good, reliable supplier: REMKO, a partner who finds a solution to any problem.