REMKO BL BL 261, BL 351 Wall - room air conditioner in split design with quick-release coupling system Operation · Technology · Spare parts Edition GB - D04
Contents Safety notes 4 Environmental protection and recycling 4 Warranty 4 Intended use 4 Transportation and packaging 5 System description 5 Operation Decommissioning 12 Care and maintenance 12-13 Troubleshooting and customer service 14-15 Installation instructions for qualified personnel 16-19 Installation 19 Connection of quick-release couplings 20 Leak testing 21 Pumping down to vacuum 21 Condensate draining and ensured discharge 21 Electrical connection 21-22 Electrical
REMKO BL Safety notes Carefully read this operating manual before starting the unit for the first time. It contains useful tips and notes as well as hazard warnings to prevent injury or material damage ! . Failure to follow the directions in this manual not only presents a danger to people, the environment and the system itself, but will void any claims for liability. ■ Keep this operating manual and the refrigerant data sheet near to the unit.
Transportation and packaging The units are delivered in strong transport packaging. Immediately check the units on delivery and make a note of any damage or missing parts on the delivery note. Inform the forwarding agent and contractual partner. No warranty can be assumed for later claims. Cooling circuit diagram for the outdoor component Condenser fan Reverse flow valve Compressor Floor consoles, wall consoles and condensation pumps are available as accessories.
REMKO BL Operation The indoor unit is easy to operate using an infrared remote control. This is supplied as standard. The indoor unit beeps to acknowledge the correct transmission of data. If it is not possible to program the indoor unit using the remote control, it can also be operated manually. Manual mode Display on indoor unit The indoor units can be commissioned manually. After the air inlet screen has been opened, the inner recessed key can be pressed and automatic mode can be activated.
Keys on the remote control 2. Cooling mode In this mode, the warm air in the room is cooled down to the desired temperature. "TIMER OFF" key Press this key to program the automatic switch-off time of the unit within the next 24 hours. 3. Dehumidification mode In this mode the room is mainly dehumidified and the adjusted temperature is maintained. "HR" key Press this key to set the hours. 4. Heating mode In this mode, the warm air in the room is warmed to the desired temperature.
REMKO BL Key functions A symbol is shown on the display to indicate that the settings are being transferred. Stand by of remote control The remote control standby mode is signalled by the blinking dot on the remote control. RESET key The remote control can be reset by pressing the RESET key in the battery compartment. The time can then be programmed (see "CLOCK key"). RESET CLOCK Key HR/MIN CLOCK Your air conditioner is activated and deactivated by pressing the ON / OFF key.
▲/▼ Keys The ▼ key can be used to reduce the desired target temperature, the ▲ key can be used to increase it. In automatic mode, the temperature can be increased or decreased by 1°C. In dehumidification mode, no temperature adjustment can be made.
REMKO BL DEHUMIDIFICATION MODE In dehumidification mode, the target temperature is set to 24°C. Due to the low temperature of the refrigerant, the temperature of the air at the condenser falls below the dew point. The excess moisture in the air is condensed by the vaporiser, the room is dehumidified. The fan speed is permanently set to the lowest setting in order to achieve a maximum level of dehumidification. The compressor switches on and off in intervals between 17°C and 24°C.
SLEEP Key A programming function is activated with this key, which increases the target temperature in cooling mode by 1°C after one hour and by 2°C after 2 hours. In heating mode, the target temperature is decreased by 1°C after one hour by 2°C after 2 hours. The unit switches off automatically after 8 hours. SLEEP TIMER Key SLEEP SLEEP The activation and switch-off time can be programmed with this key.
REMKO BL Manual air distribution There are individually adjustable fins for adjusting the horizontal air distribution on the air discharge side. ! Manual air distribution ATTENTION Moving interior parts such as the fan may to cause injury during operation! Only make adjustments after swing operation has been turned off. Shift lever left Decommissioning Care and maintenance Temporary Decommissioning Permanent decommissioning 1.
TIP This ensures the operational reliability of your system! • • • • • • • • • • General Measure voltage and current Check function of compressor/fans Check function of fan Dirt on condenser/vaporiser Check refrigerant fill quantity Check condensate drain Cleaning the housing on the indoor unit Inspect insulation Check moving parts Sealing test for cooling circuit 1. Disconnect the supply voltage to the equipment. 2. Open and fold the air inlet guard on the front side upwards. 3.
REMKO BL Troubleshooting and customer service The units and components are manufactured using state-of-the-art production methods and tested several times to verify their correct function. However, if malfunctions should occur, please check the functions as detailed in the list below. Please inform your dealer if the unit is still not working correctly after all function checks have been performed! Malfunctions Fault The unit does not start or switches itself off.
Fault indication by flashing code Display Cause Required action E1 Indoor unit probe air circulation defective Contact specialist dealer E2 Indoor unit probe frost protection defective Contact specialist dealer E4 Cooling mode: No cooling output after 30 minutes Heating mode: No heating output after 30 minutes Contact specialist dealer E5 Cooling mode: Frost protection has responded Heating mode: Overheating protection has tripped Contact specialist dealer E6 Bridge inner control cable inter
REMKO BL Installation instructions for qualified personnel Important notes prior to installation ■ Transport the unit in its original packaging as close as possible to the installation location. This helps to prevent damage during transportation. ■ Check the contents of the packaging for completeness and check the unit for visible transport damage. Report any damage immediately to your contractual partner and the shipping company.
Wall openings Selection of installation location Wind ■ A wall opening of at least 70 mm diameter and 10 mm incline from the inside to the outside must be made for each indoor unit. Indoor unit If the unit is being installed in windy areas, ensure that the warm outlet air discharges in the prevailing wind direction. If this is not the possible, it may be necessary to install a windbreak (to be provided by the customer). Ensure that the windbreak does not adversely affect the air intake to the unit.
REMKO BL Installation inside buildings ■ Ensure that heat can dissipate adequately when placing the outdoor component in cellars, lofts, adjoining rooms or halls (figure 4). ■ Install an additional fan with a rated flow comparative to that of the outdoor component being installed in the room and which can compensate any additional pressure loss in ventilation ducts (figure 4).
Installation Oil return measures NOTE If the outdoor component is installed at a higher level than the indoor unit, suitable oil return measures must be taken. Usually, an oil pump bend is installed for every 2.5 metres of height difference. Oil return measures Outdoor component Unit installation The indoor unit is attached by means of a wall bracket, taking into consideration the air discharge side located in the lower part. 1.
REMKO BL Connection of quickrelease couplings The refrigerant pipes should be connected by the customer on the right-hand side of the outdoor component. The pre-filled refrigerant pipes are connected to the outdoor component by means of the quickconnector system. Once installed, the connections must be insulated to prevent vapour diffusion. The following instructions describe the installation of the refrigerant pipes of the indoor unit to the outdoor component.
Leak testing Once all the connections have been made, the pressure gauge station is attached to the Schrader valve as follows (if fitted): red = small valve = injection pressure blue = large valve = suction pressure Following connection of the quickrelease couplings, the connections are checked using leak detection spray and suitable devices for leaktightness. If leaks are found, the connections have not been made properly.
REMKO BL Control cables should be screened if laid in areas exposed to strong magnetic fields. ■ Details concerning the electrical protection of the system are provided in the technical data. ■ Connection of the outdoor component Proceed as follows to connect the cable: 1. Remove the cover from the unit. 2. Remove the side panel next to the terminals. Connecting the indoor unit 2 a 10 m long control cable are already connected to the indoor unit.
Electrical drawings BL 261, BL 351 IT Swing motor Vaporiser fan motor SM FM Exterior conductor Neutral conductor Earth conductor Compressor (red) Condenser fan (white) Reverse flow valve (black) Display L N AC-N 3 1 2 AC-L COMP Receiver Probe air circulation Probe vaporiser Transformer BL 261, BL 351 AT Condenser fan Condenser fan (white) 1 Reverse flow valve (black) 2 Compressor (red) 3 Reverse flow valve BK S Exterior conductor BU R Earth conductor Neutral conductor BK BU N L
REMKO BL Before commissioning Following a successful leak check, the unit can be started again without the pipes needing to be pumped down to a vacuum. Perform the following checks prior to commissioning the unit for the first time and after any interventions affecting the cooling circuit.
Function test of the cooling and heating modes 1. Remove the protective caps from the valves. 2. Start the commissioning procedure by briefly opening the shut-off valves on the outdoor component until the pressure gauge indicates a pressure of approx. 2 bar. 3. Use leak detection spray or suitable devices to check that all the connections are tight. 4. If no leaks are found, fully open the shut-off valves by turning them anti-clockwise using a spanner. If leaks are found, remedy the faulty connection.
REMKO BL Unit dimensions BL 261, BL 351 AT 250 780 280 540 510 BL 261, BL 351 IT 790 275 200 All dimensions are given in mm We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
Exploded view of BL 261 IT, BL 351 IT 11 10 9 7 1 6 4 8 5 2 3 12 Spare parts list No. We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process. Designation BL 261 IT BL 351 IT From serial number 801D51-... 807D51-...
REMKO BL Exploded view of BL 261 AT, BL 351 AT 8 12 9 5 4 1 3 2 6 13 10 7 11 Spare parts list No. Designation BL 261 AT BL 351 AT From serial number 801D81-... 807D81-...
Technical data Series BL 261 Operating mode BL 351 Wall / room air conditioner combination for cooling and heating Nominal cooling output 1) kW 2.69 3.59 Nominal heating output kW 2.96 4.24 A A 3.32 3.23 A A 2) Energy efficiency rating, cooling 1) Energy efficiency ratio EER 1) Energy efficiency rating, heating 2) Energy efficiency ratio COP 3.70 3.66 Power consumption, yearly, (500h) C/H kWh 405 / 400 555 / 580 Operating range (room volume), approx.
EC – Declaration of Conformity in accordance with the Machinery Directive, Annex II 1A Original Declaration of Conformity We hereby declare that the devices named below, produced and sold by us, satisfy the relevant basic requirements of the EC guidelines, the EC safety standards and other product-specific EC standards. Name of Manufacturer: REMKO GmbH & Co. KG Klima- und Wärmetechnik Im Seelenkamp 12 D - 32791 Lage Name of the CE representative: REMKO GmbH & Co.
REMKO INTERNATIONAL ... and also right in your neighbourhood! Benefit from our experience and advice Consultation Thanks to intensive training, our consultants are always completely up-to-date when it comes to technical expertise. This has given us the reputation of being more than just an excellent, reliable supplier: REMKO, a partner, who helps to solve problems.