User's Manual

21
Defrost Function
Step
Procedure / Description LED indication
1
“Defr” message and heat icon will be displayed if
room temperature is below 41°F / 5°C.
All heaters will be forced On, except in cool mode.
Out of Temperature Range Control Function
Step
Procedure / Description LED indication
1
“Cold” message and heat icon will be displayed if
room temperature is below 32°F / 0°C.
All heaters will be forced On, except in cool mode.
2
“Hot” message and cool icon will be displayed if
room temperature is above 99°F / 37°C.
All heaters will be forced Off.
Cooler will turn on if running in cool mode.
Energy Saving Mode
User can enable/disable energy saving mode by using Z-Wave BASIC set command only. You may
refer to the user manual of Z-Wave primary controller.
- Enable energy saving mode, Basic set value = 0x00 (Off)
(Energy saving mode will be mapped to off mode)
- Disable energy saving mode, Basic set value = 0xFF (Resume)
(Comfort mode will mapped to resume mode)
Short Cycle Start Up Protection
To protect the compressor / heat pump, those outputs are forced off until a 3 minutes countdown
finishes. Those outputs can be activated according to the room temperature after 3 minutes.