Access Control Design Guide
59
D Appendix D: Site Schematic Check List
This appendix lists the items that should be marked on the Site Schematic (see page 8).
General
Mark the following:
The locations of any doors or elevators to be access controlled
The locations of any monitor points or auxiliary output devices
Walls and any other relevant building features
If appropriate for drilling or mounting, the construction of any relevant walls or floors
Database Units and Controllers
Mark the following:
The type and location of each database unit and controller
The cabinet types to be used, and details of the boards that share the same cabinet
The cable types and routing paths to readers, door furniture, controllers, other database units in the
same chain, the SMS PC, monitor points and auxiliary outputs
The location of the network socket, telephone socket (for modem communications) or PC (for serial
communications), as appropriate for the first database unit in a chain
The address of each database unit (one to 32) and controller (one to 8)
The communications method to be used for communications from the first database unit in the chain to
an SMS PC
The IP address of each NIC-4 and NIC-WI (if applicable)
The port usage bit-switch settings
The modules required:
NIC-4 – specify encryption or non-encryption model, and the port (COM D or COM E)
NIC-WI – specify the port (COM D or COM E)
One-port RS232 – specify the port (COM D or COM E)
WIM
I/O Module
RS485 Module
The power source for each cabinet