RL78/L12    CHAPTER 11 A/D CONVERTER 
R01UH0330EJ0200 Rev.2.00      369 
Dec 13, 2013 
11.7.4 Setup when temperature sensor output/internal reference voltage output is selected (example for software 
trigger mode and one-shot conversion mode) 
Figure 11-26. Setup when temperature sensor output/internal reference voltage output is selected 
PER0 register setting
The ADCEN bit of the PER0 register is set (1), and supplying the clock 
starts. 
• ADM0 register 
FR2 to FR0, LV1, and LV0 bits:  These are used to specify the A/D 
conversion time. 
• ADM1 register 
ADTMD1 and ADTMD0 bits:  These are used to specify the software 
trigger mode. 
ADSCM bit: Sequential conversion mode/one-shot conversion mode 
• ADM2 register 
ADREFP1, ADREFP0, and ADREFM bits: These are used to select the 
reference voltage. 
ADRCK bit: This is used to select the range for the A/D conversion 
result comparison value generated by the interrupt signal 
from AREA1, AREA3, and AREA2. 
ADTYP bit: 8-bit/10-bit resolution 
• ADUL/ADLL register 
  These are used to specify the upper limit and lower limit A/D conversion 
result comparison values. 
• ADS register 
ADISS and ADS4 to ADS0 bits: These are used to select the 
temperature sensor output voltage or 
internal reference voltage. 
The ADCE bit of the ADM0 register is set (1), and the system enters the 
A/D conversion standby status. 
The reference voltage stabilization wait time (1 
μ 
s) is counted by the 
software. 
The A/D conversion end interrupt (INTAD) is generated. 
Note
The conversion results are stored in the ADCR and ADCRH registers. 
After counting up to the reference voltage stabilization wait time B ends, 
the ADCS bit of the ADM0 register is set (1), and A/D conversion starts 
Start of setup 
The A/D conversion end interrupt (INTAD) will be generated. 
After ADISS is set (1), the initial conversion result cannot be used. 
The ADCS bit of the ADM0 register is set (1), and A/D conversion starts. 
First A/D conversion time 
The reference voltage stabilization wait time indicated by stabilization 
wait time count A is required when the value of the ADREFP1 and 
ADREFP0 bits is changed. 
If change the ADREFP1 and ADREFP0 = 0, 0 or 0, 1:  No wait 
If change the ADREFP1 and ADREFP0 = 1, 0:  Setting prohibited
Second A/D conversion time 
• ADM0 register setting 
• ADM1 register setting 
• ADM2 register setting 
• ADUL/ADLL register setting
• ADS register setting 
(The order of the settings is 
irrelevant.) 
ADCE bit setting 
Reference voltage stabilization
wait time count B 
Start of A/D conversion 
End of A/D conversion 
ADCS bit setting 
Storage of conversion results in 
the ADCR and ADCRH registers
End of A/D conversion
ADCS bit setting 
Start of A/D conversion 
Reference voltage stabilization
wait time count A 
Note  Depending on the settings of the ADRCK bit and ADUL/ADLL register, there is a possibility of no interrupt signal 
being generated. In this case, the results are not stored in the ADCR, ADCRH registers. 
Caution This setting can be used only in HS (high-speed main) mode. 
<R> 