Power saver function is designed to conserve battery power when AC power is not or rarely
required by the loads. In this mode, the inverter pulses the AC output looking for an AC load
(i.e., electrical appliance). Whenever an AC load (greater than 50 watts) is turned on, the
inverter recognizes the need for power and automatically starts inverting and output goes to full
voltage. When there is no load (or less than 50 watts) detected, the inverter automatically goes
back into search mode to minimize energy consumption from the battery bank. In “Power saver
on” mode, the inverter will draw power mainly in sensing moments, thus the idle consumption
is significantly reduced.
04 Power Saving Mode
The operating temperature range for the PCL inverter charger series is 0C°-40C° / 32F° -
104F°. If internal power components begin to exceed their safe operating temperature level,
the inverter shuts down to protect itself from damage. This setting controls whether the inverter
charger automatically restarts after the unit cools down or whether the user has to manually
restart the unit.
07 Auto Restart Temperature Fault
If disabled, inverter output will be
available at all times.
If enabled, output of the inverter
will be off until a load greater than
50 watts is detected.
07
Restart disabled
(default)
Restart enabled
60Hz (default)
Auto restart when over
temperature occurs
The factory default frequency for inverters is 60Hz. Normally, manufacturers build electrical
devices for a certain amount of Current, Voltage and Hertz (Cycles) which is mentioned on the
name plate. The Current is dependent of the Voltage and the Hertz supplied to an electric motor
or appliance.
09 Output Frequency
09