User Manual

33
95
To modify battery set-points in Program 95 and Program 96, The dry contacts control needs to
be enabled. This allows control over the auto generator function.
The PCL inverter charger series have functions to automatically start and stop a generator for
supplementing charge. The Auto Generator feature starts the Generator with the use of
Normally Closed (NC) contacts of the relay that “opens” when the battery voltage drops to the
programmed value of Program 96, Low Battery Voltage Set-point. The Normally Open (NO)
relay “closes”, and the auto generator start commences the generator to start charging the
battery bank. When the battery is recharged and its voltage rises to the programmed value of
Program 95, High Battery Voltage Set-point The NC (closes) contacts and NO (open) contacts
of relay reset and the Generator will stop / shut down the Generator automatically. The PCL unit
will then transfer back to “Inverting Mode”.
96 Low Voltage Trip for Dry Contacts
97 Dry Contact Control
When dry contact switch from NC to NO, battery voltage
arrive to setting voltage, dry contact point switch to NC.
This setting can not be than fast charge voltage.higher
setting range is from 13.0V to 15.5V for 12V Increment of
each click is 0.1V for 12V
V
BATT
96
When battery voltage arrive to Setting point, the dry
contact switch from NC to NO. This setting can not be
lower than low battery voltage cut off point. setting
range is from 10.5V to 12.5Vfor 12V
Increment of each click is 0.1V for 12V
V
BATT
97
If inverter is set in dce, dry contact function enable
and 95,96 can be set up in program.
is
Dry contact control
If inverter is set in dcd, dry contact function is disable, ,96 can
not be set up in program.95