Full Product Manual

15
Troubleshooting
Check all connections to ensure they are secure and clean
Check polarity of the battery connection and make sure the battery generates at least 6V
Ensure the solar panels are exposed to sufficient light ideally position them to face the
sun directly
If charge controller states that there is short-circuit, please ensure that the panels are
connected correctly, and that the wires at the terminals are not touching each other.
If one of the status LED is off and a battery is connected, check that the battery terminals
have good connection and that the polarity is correct. Check that the voltage doesn’t
exceed the rated input voltage shown in Table 7-1 on Section 7.
If the charge controller is not charging, ensure that the panel’s polarity, and check for loose
connections.
Maintenance
For best controller performance, it is recommended that these tasks be performed from time to
time.
1. Check that controller is mounted in a clean, dry, and ventilated area.
2. Check wiring going into the charge controller and make sure there is no wire damage or
wear.
3. Tighten all terminals and inspect any loose, broken, or burnt up connections
4. Make sure readings in the LEDs are consistent.
Fusing
Fusing is a recommended in PV systems to provide a safety measure for connections going from
panel to controller and controller to battery. Remember to always use the recommended wire
gauge size based on the PV system and the controller.
NEC Maximum Current for different Copper Wire Sizes
AWG
16
14
12
10
8
6
4
2
0
Max.
Current
10A
15A
20A
30A
55A
75A
95A
130A
170A
Table 5