User Manual

17
Error Codes
Maintenance
Fusing
1. Check that controller is mounted in a clean, dry, and ventilated area.
2. Check wiring going into the charge controller and make sure there is no wire damage or wear.
3. Tighten all terminals and inspect any loose, broken, or burnt up connections.
For best controller performance, it is recommended that these tasks be performed from
time to time.
DescriptionError Number
E0
E01
E02
E06
E07
E08
E10
E13
E14
No error detected
Battery over-discharged
Battery over-voltage
Controller over-temperature
Battery over-temperature
PV input over-current
PV over-voltage
PV reverse polarity
Battery reverse polarity
EN
AWG
16 14 12 10 8 6 4 2 0
Max. Current
55A30A20A15A10A 75A 95A
130A 170A
Parallel
Fusing is a recommendation in PV systems to provide a safety measure for connections
going from panel to controller and controller to battery. Remember to always use the
recommended wire gauge size based on the PV system and the controller.
NEC Maximum Current for different Copper Wire Sizes
Fuse from Controller to Battery
Fuse from Solar Panel(s) to Controller
Ex. 200W; 2 X 100 W panels
Ex. Adventurer = 30A fuse from Controller to Battery
Controller to Battery Fuse = Current Rating of Charge Controller
Fuse = minimum of 11.5 * 1.25 = 14.38= 15A fuse
Total Amperage = Isc1 + Isc2 = (5.75A + 5.75A) * 1.25