BONDING CONNECTION GROUND PATHS
O
TEMPORARY BONDING CONNECTION DURING ARRAY MAINTENANCE
When removing modules for replacement or system maintenance, any module left in place that is secured
with a bonding Midclamp will be properly grounded. If a module adjacent to the end module of a row is
removed or if any other maintenance condition leaves a module without a bonding mid clamp, a temporary
bonding connection must be installed as shown
• Attach Ilsco SGB4 to wall of rail
• Attach Ilsco SGB4 to module frame
• Install solid copper wire jumper to Ilsco lugs
MODULE REMOVED
BONDING MID
CLAMPS MAINTAIN
GROUND PATH
TEMPORARY
BONDING
CONNECTION
ELECTRICAL CONSIDERATIONS
SOLARMOUNT is intended to be used with PV
modules that have a system voltage less than or
equal to that allowable by NEC. For standard
system grounding a minimum 10AWG, 105°C
copper grounding conductor should be used to
ground a system, according to the National
Electric Code (NEC). It is the installer’s
responsibility to check local codes, which may vary.
See below for interconnection information.
INTERCONNECTION INFORMATION
There is no size limit on how many SOLARMOUNT
& PV modules can be mechanically interconnected
for any given conguration, provided that the
installation meets the requirements of applicable
building and re codes.
GROUNDING NOTES
The installation must be conducted in accordance
with the National Electric Code (NEC) and the
authority having jurisdiction. Please refer to these
resources in your location for required grounding lug
quantities specic to your project.
The grounding / bonding components may overhang
parts of the array so care must be made when
walking around the array to avoid damage.
Conductor fastener torque values depend
on conductor size. See product data sheets for
correct torque values.
PERIODIC INSPECTION: Conduct periodic
inspections for loose components, loose fasteners or
any corrosion, immediately replace any affected
components.
Ilsco SGB-4
SOLID COPPER WIRE
Ilsco SGB-4
REQUIRED ONLY FOR TEMPORARY
BONDING DURNING ARRAY MAINTENANCE