when part of a module is shaded and the rest is exposed to the sun. 
These currents can cause the affected cells to get very hot and 
could even damage the module. To protect module from such high 
reverse currents 
   All modules rated greater than 55 Watt have bypass diode already 
integrated in the junction box.  
  In the unlikely event of diode failure Renogy recommends a 
qualified service technician be employed to determine if diodes 
have failed and to make replacement.
 5.3 General Installation 
  The modules are equipped with PV wiring connectors that comply 
with the Standard for Connectors for use in Photovoltaic Systems, UL 
6703, see module literature for appropriate mating connectors. 
  Do not use modules of different configurations in the same system. 
Several modules are connected in series and then in parallel to form 
a PV array, especially for application with a high operation voltage. If 
modules are connected in series, the total voltage is equal to the sum 
of individual voltages. For applications requiring high currents, 
several photovoltaic modules can be connected in parallel; the total 
current is equal to the sum of individual currents. 
  Module is supplied with Multicontact connectors (PV-KBT4 and PV-
KST4) to use for system electrical connections. Use the National 
Electric Code to determine system wiring size (refer to NEC clause 
310), type and temperature rating of conductors to be connected to 
the module’s connectors. Wiring connected to the module’s wiring 
should be #12 AWG (minimum) and must be temperature rated at 
90°C (minimum). 
  In Canada installation shall be in accordance with CSA C22.1, Safety 
Standard for Electrical Installations, Canadian Electrical Code, Part 
1. 
  The cross section area of cable and the capacity of connector must 
be selected to suit the maximum system short circuit current, 
otherwise the cable and connector will be overheated under large 
current. Refer to NEC for details. 
  Module overcurrent protection, rated for DC use fuses 
5.4 Grid Connected Electrical System 
  The DC electrical energy generated by photovoltaic systems may 
also be converted to AC and connected to a utility grid system. As 
local utilities’ policies on connecting renewable energy systems to 
their grids vary from region to region, consult a qualified system 
designer or integrator to design such a system. Permits are 
normally required to install such a system and the utility must 
formally approve and inspect such a system before it can be 
connected to the grid
. 
6. Commission and Maintenance 
Renogy recommends that all work in commissioning and maintenance of 
a system must be performed by a qualified solar PV technician! 
6.1 Testing, Commissioning, and 
Troubleshooting 
  Test all electrical and electronic components of your system before 
commissioning it. Follow the instructions in the guides supplied with 
the components and equipment. 
  Testing modules connected in series before they are connected to 
system. 
  To determine Voc and Isc in the following tests, the module(s) must 
be exposed to the sun and not connected to a load. Observe 
personal safety when making these measurements. 
  Check the open-circuit voltage (Voc) of every series module using a 
digital multimeter (Fluke 170 series are recommended). The 
measured system Voc should correspond to the sum of the Vocs of 
the individual module. You will find the rated voltage in the technical 
specifications of the type of the module used and in the tables at the 
end of this Installation Guide. If the measured value is significantly 
lower than the expected value, proceed as described under 
“Troubleshooting an excessively low voltage”. 
  Determine the short-circuit current (Isc) of every series circuit. It can 
be measured directly by connecting the digital multimeter connected 
in the two terminals of series circuit or module, Attention, the rated 
scale of the ammeter or the rated current of load should more than 
1.25 times than the rated short-circuit current of series module. You 
will find the rated current in the technical specifications of the type 
of module used. The measured value can vary significantly, 
depending on weather conditions, the time of day and shading of 
the module. 
To identify the commonly low voltage and excessively low voltage, the 
commonly how voltage mentioned here is the decrease of open-circuit 
voltage of the module, which is caused by the temperature rising of solar 
cells or lower irradiance. Excessively low voltage is typically caused by 
improper connections at the terminals or defective bypass diodes. 
  First, check all wiring connections to make sure it is not open-circuit 
or is not connection well. 
  Check the open-circuit voltage of each module: 
  Fully cover the modules with an opaque material. 
  Disconnect the wiring at both terminals of the modules. 
  Remove the opaque material from the module to be checked and 
measure the open-circuit voltage at its terminals. 
  If the measured voltage is only half of the rated, this indicates a 
defective bypass diode. Refer to ‘Testing and replacing bypass 
diodes’. 