4.2 Top Down Clamps 
Clamps are an approved method of mounting for Renogy modules. A 
clamp holds two modules in a row. The centerline of the clamps must be 
in-line with the module mounting holes and installed according to code. 
4.3 Grounding 
The frame of the PV module, as well as any exposed non-current carrying 
metal parts of fixed equipment that can be energized must be grounded to 
avoid electrical shock. Renogy recommends grounding all PV module 
frames to ensure the voltage between the conductive equipment and the 
earth ground is zero in all circumstances. 
Appropriate grounding consists of using an appropriately sized EGC or 
racking system that can be used for integrated grounding. Renogy panels 
implement a coated aluminum frame for corrosion resistance. The frame 
rails have pre-drilled holes marked with the grounding sign. Do not drill 
additional holes into the frame rails. 
  Note that the stainless steel washer is used between the grounding 
wire and the module frame. This is for avoiding corrosion due to 
dissimilar metals. 
  The module frame must be properly grounded (refer to NEC clause 
250). The grounding wire must be properly fastened to the module 
frame to assure good electrical contact. Use the recommended type, 
or an equivalent, connector for this wire. 
  If the support frame is made of metal, the surface of the frame must 
be electroplated and have excellent conductivity. 
  We recommend the lay-in lug (Cat. No. GBL4-DBT; rated for 
600Volts; company: ILSCO; UL number is E34440 ) when 
grounding. First strip 16mm insulating jacket from the end of the 
ground wire (4-14 STR.) carefully to avoid nicking or cutting 
conductors, insert the wire into the slot of the lug (see the picture), 
and screw down the slotted screw. 
  Next, assemble the recommended ILSCO grounding lug to the 
aluminum frame using stainless steel M3 or M5 screw and hardware 
as shown below. Note: there are two different size grounding holes, 
the smaller of which is being phased out. 
  Further, buildup of hardware for mounting the grounding lug are the 
same—except for the M3 screw, an added flat washer is mounted 
directly under the M3 screw head. The star washer is fitted directly 
under the grounding lug and makes electrical contact by penetrating 
the anodized coating of the aluminum frame, The screw assembly is 
further fitted with a flat washer, then a split lock washer and finally a 
nut to secure the entire assembly, as shown. Recommended torque 
of M3 or M5 screw assembly is 0.8NM or 1.5 NM. 
5. Electrical Installation 
5.1 Cables and Wiring 
Renogy  modules are equipped with two (2) stranded, PV-rated, output 
MC4 cables. The positive connector is a male connector and the negative 
connector is a female connector. These wires by themselves are rated for 
series connections, but could be adapted to hold parallel connections with 