INSTALLATION INSTRUCTIONS
62-3075EFS-03
®
CUS
AM-1 Series™
PROPORTIONAL THERMOSTATIC MIXING AND DIVERTING
VALVE STANDARD AND “C” TEMPERATURE RANGE MODELS -
NPT, UNION SWEAT, THREAD, CPVC AND PEX MODELS
APPLICATION
The AM-1 Series™ family of quality valves in a variety of
temperature ranges and connections, for master mixing or
diverting applications.
SPECIFICATIONS
Temperature Range:
C Model: 70°F–120°F (21°C–49°C)
Standard Model: 70°F–145°F (21°C–63°C)
Connections:
Straight-through design (HOT and COLD at same level).
Construction:
Nickel plated brass construction. EPDM o-rings. Made in
USA.
Lead Free Plumbing Code Compliance: The wettable sur-
faces of lead free models contain less than .25% of lead by
weighted average
Operating Pressure: 150 psi (1034 kPa) maximum.
Operating Temperature: 212 °F (100 °C) maximum.
Patent Information: U.S. Patent No. 6,079,625.
INSTALLATION
IMPORTANT
Mounting must comply with all local codes.
NOTE TO INSTALLER:
This product should be installed by a
qualified individual, in accordance with local codes and
ordinances. It is the responsibility of the installer to properly
select, install and adjust these devices as specified in these
instructions. For installations which require compliance with
Building/Mechanical/Plumbing Codes, the appropriate AM-1
Series™ valve must be chosen and installed, and the
discharge temperature set and locked according to these
instructions. AM-1 “C” Series models with the temperature
range, 70°F–120°F (21°C–49°C) and "Standard" models with
temperature range 70°F–145°F (21°C–63°C) are ASSE
®
1017 (point of source application) certified, and CSA
®a
and
IAPMO
®
listed. These models shall be used to supply water to
tubs, showers, bathing facilities and other outlets. These
valves should be installed where they will be accessible for
cleaning, servicing or adjustment.
ASSE 1017 Applications—Point of
Source
These AM-1 Series models can be installed in any position
consistent with the intended use. For domestic hot water
supply, the valve must be installed as shown in Fig. 1. There
shall be no shut-off valves installed between the cold water
line and the cold water connection on the AM-1 Series valve.
Check valves shall be installed as indicated for NPT models;
all AM-1 models with union fittings are supplied with integral
check valves on both the hot and cold ports. A cold water
service valve may be installed, as indicated, between the cold
water supply line to the distribution system and the cold water
line supplying both the water heater and the AM-1 Series
valve.