Install Instructions

INSTALLATION INSTRUCTIONS
66-1184-01
Sensors for the SOLA Hydronic Control
APPLICATION
Both single and dual element 10KOhm resistive temperature
sensors are used with the Honeywell
SOLA Hydronic Boiler
Controls. Single element sensors provide only operation
temperatures to the
SOLA control. Dual element sensors may
provide both the operation and/or redundant limit
temperatures to the controller. Sensors may be used with
compatible Honeywell immersion wells.
FEATURES
NTC resistive 10KOhm ± 1% at 25°C temperature
sensors.
•Sensor β=3950 for 25°C to 66°C (β=thermistor material
constant relative to its resistance versus temperature)
Single element sensors for boiler Inlet, Header and
Outdoor temperature sensing functions.
Dual element sensors for boiler Outlet, Domestic Hot
Water and Stack operation and limit temperature
sensing functions.
32003971-003 sensor kit contains sensor and hardware
for strap-on or outdoor mounting of sensor.
Some models have Molex splice connectors for quick
field connection.
Sensors may be used for either strap-on or insertion
type applications.
Compatible immersion wells and accessories
available. Refer to Honeywell form number 68-0040 for
more information.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications .................................................................... 2
General Information .......................................................... 3
Installation ......................................................................... 3
Checkout .......................................................................... 5