Install Instructions

SENSORS FOR THE SOLA HYDRONIC CONTROL
66-1184—01 2
SPECIFICATIONS
Honeywell offers a variety of sensor types for the SOLA
Hydronic Control. Bare leadwires and Molex splice connectors
are available. Sensors may be used for either insertion (into a
well) or strap-on applications.
Complementary parts such as immersion wells, mounting
clamps and spring clips can be found in form number 68-
0040, Immersion Wells and Compression Fittings. The
immersion wells and other complementary parts must be
ordered separately.
1
Mating connector and terminals: Molex 0039013028 and 0039000039. Mating connector and terminals must be purchased by
customer.
2
Mating connector and terminals: Molex 0039014031 and 0039000039. Mating connector and terminals must be purchased by
customer.
3
Sensors may be used for Stack limit sensor if the temperature specifications are not exceeded for the sensor.
4
The dual element sensor common is the marked lead. Leads A and B are interchangeable.
Table 1. S
OLA Hydronic Control Sensors
Sensor
Function Description
Temperature
Range Termination Part Number Installation Information
Inlet
Header
Outdoor
Single Element NTC
10KOhm ± 1% at 25°C
β=3950 for 25°C to 66°C
-40°F to +266°F
-40°C to +130°C
6 in. leads with
female Molex
0039013029
splice connector
1
32003971-002 2.620 ± 0.015 in. insertion
0.375 ± 0.002 in. bulb
diameter
Bulb material copper
Inlet
Header
Outdoor
Single Element NTC
10KOhm ± 1% at 25°C
β=3950 for 25°C to 66°C
-40°F to +266°F
-40°C to +130°C
42 in. leads, wires
skinned and
retained
198799Z 2.620 ± 0.015 in. insertion
0.375 ± 0.002 in. bulb
diameter
Bulb material copper
Header
Outdoor
Single Element NTC
10KOhm ± 1% at 25°C
β=3950 for 25°C to 66°C
-40°F to +266°F
-40°C to +130°C
42 in. leads, wires
skinned and
retained
32003971-003
Kit includes
sensor,
anchors,
mounting
screws, wire
nuts, clip, tie
straps
2.620 ± 0.015 in. insertion
0.375 ± 0.002 in. bulb
diameter
Bulb material copper
Outlet
DHW
Stack
3
Dual Element NTC
4
10KOhm ± 1% at 25°C
β=3950 for 25°C to 66°C
-40°F to +266°F
-40°C to +130°C
6 in. leads with
female Molex
0039014037
splice connector
2
50001464-006 1.181 ± 0.015 in. insertion
0.370 ± 0.005 in. bulb
diameter
Bulb material brass
Outlet
DHW
Stack
3
Dual Element NTC
4
10KOhm ± 1% at 25°C
β=3950 for 25°C to 66°C
-40°F to +266°F
-40°C to +130°C
42 in. leads, wires
skinned and
retained
50001464-007 1.181 ± 0.015 in. insertion
0.370 ± 0.005 in. bulb
diameter
Bulb material brass
Table 2. Control Sensor Wire Sizes
Application Recommended Wire Size
Recommended Part
Number(s)
Maximum Leadwire
Distance
Inlet
Header
Outdoor
22 AWG two-wire twisted pair, insulated for low voltage. Belden 8443 or equivalent 50 feet
15.24 meters
Outlet
DHW
Stack
22 AWG two-wire twisted pair with ground. Belden 8723 shielded
cable or equivalent
50 feet