Install Instructions

INSTALLATION INSTRUCTIONS
69-1641EF-02
AT20, AT40, AT72D, AT87, AT88
AT Transformers
APPLICATION
The AT20, AT40, AT72, AT87 and AT88 Transformers are
step-down transformers used primarily for powering 24
Vac control systems. They can be used in any 24 Vac
application that does not exceed the transformer volt-
ampere (VA) rating.
The Transformers will replace all equivalent Resideo and
competitive transformers with similar primary voltage
requirements, equal or smaller VA ratings and similar
mounting configurations.
Transformer voltage ratings (primary and secondary),
wiring connection type, and fusing are listed in Table 1.
The transformers are Underwriters Laboratories Inc.
component recognized and Canadian Standards
Association listed and meet NEC Class 2 not wet, Class
3 wet requirements as specified by NEMA Standard
DC-20.
SPECIFICATIONS
Models:
See Table 1.
Table 1. Transformer Model and Electrical Specifications.
a
Transformer complies with 24 volt NEMA Standard DC-20.
b
Available with female quick-connect terminals on all leadwires.
c
Thermal fuses in primary on 208V/240V models for overload protection.
Model
Primary Secondary
Output at
100 Percent
Power Rating
Overload
Protection
Voltage and
Frequency Wiring Connection Voltage Wiring Connection
AT20
a
120 Vac, 50/60 Hz Two 9 in. (229 mm)
leadwires
24 Vac Two 9 in. (229 mm)
leadwires
20 VA Energy
Limited
c
AT40
a
120 Vac, 50/60 Hz 40 VA
240 Vac, 50/60 Hz
AT72D
a
120 Vac, 50/60 Hz Two screw
terminals
240 Vac, 50/60 Hz Three 9 in. (229
mm) leadwires
AT87A
a
120 Vac, 50/60 Hz Two 13 in. (330
mm) leadwires
50 VA
208 Vac, 50/60 Hz
240 Vac, 50/60 Hz
AT88A 120Vac, 50/60 Hz Two 12 in. (305
mm) leadwires
24 Vac Two 12 in. (305
mm) leadwires
75 VA Fuse in
secondary
208/240 Vac, 50/60
Hz
400 Vac, 50/60 Hz
480 Vac, 50/60 Hz