Submittal Sheet

By using this Resideo literature, you agree that Resideo will have no liability for any damages arising out of your use or modification to, the
literature. You will defend and indemnify Resideo, its affiliates and subsidiaries, from and against any liability, cost, or damages, including
attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
www.resideo.com
Resideo Technologies, Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
33-00563------01 M.S. 12-20 | Printed in United States
© 2020 Resideo Technologies, Inc. All rights reserved.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.
Technical Data
Supply Voltage: 1 x 115 V 10%/6%
Table 3. Supply Voltage.
Minimum
Maximum
Amp
0.05
0.72
Watt
5
45
Inlet Pressure:
Minimum inlet pressure in relation to liquid temperature.
Table 4. Inlet Pressure.
Liquid Temperature
Minimum Inlet Pressure
150 ºF (65 ºC)
3.0 ft (0.91 m)
167 ºF (75 ºC)
4.4 ft (1.34 m)
194 ºF (90 ºC)
9.2 ft (2.8 m)
230 ºF (110 ºC)
36.1 ft (11 m)
Operating Temperatures:
To avoid condensation in the control box and stator, the liquid
temperature must always be higher than the ambient
temperature.
Table 5. Operating Temperatures.
Ambient
Temperature
Liquid Temperature
Minimum
Maximum
32 ºF (0 ºC)
35.6 ºF (2 ºC)
230 ºF (110 ºC)
50 ºF (10 ºC)
50 ºF (10 ºC)
230 ºF (110 ºC)
68 ºF (20 ºC)
68 ºF (20 ºC)
230 ºF (110 ºC)
86 ºF (30 ºC)
86 ºF (30 ºC)
230 ºF (110 ºC)
95 ºF (35 ºC)
95 ºF (35 ºC)
194 ºF (90 ºC)
104 ºF (40 ºC)
104 ºF (40 ºC)
176 ºF (80 ºC)
Display:
PCVF-ECM2020 Performance Curves:
AUTO: Circulator adapts to system demand over time.
PC1: Lowest proportional-pressure curve
PC2: Highest proportional-pressure curve
PC3: Lowest constant-pressure curve
PC4: Highest constant pressure curve
III: Highest constant speed
II: Medium constant speed
I: Lowest constant speed
0 10 VDC Operation: