Advisor Master Programming Guide P/N (EN) 1070480 (EN) • REV B • ISS 21MAY13
Copyright Trademarks and patents © 2013 UTC Fire & Security Americas Corporation, Inc. All rights reserved. Interlogix, Advisor Master name and logo are trademarks of UTC Fire & Security. Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products. Manufacturer UTC Fire & Security Americas Corporation, Inc. 1275 Red Fox Rd., Arden Hills, MN 55112-6943, USA Authorized EU manufacturing representative: UTC Fire & Security B.V.
Content Programming sequence 1 Basic set up 1 Advanced set up 2 How to program the options 4 Accessing the installer programming menu 4 Programming the menu options 5 First startup 6 Siren calibration 6 1-Zone database 7 Zone number 7 Zone settings 7 2-Area database 28 Select the area to program 28 Area settings 28 3-RAS database 39 RAS to be polled 39 Select RAS to program 39 RAS settings 39 4-DGP database 48 DGPs to be polled 48 DGP settings 48 5-Alarm groups 50 Alarm group number 50 Alarm group settings
11-Version 109 Select device 109 12-LED test 110 13-Timezones 111 Select timezone 111 Timezone settings 112 14-Defaults 113 Select default option 113 15-Alarm group restrictions 115 Alarm group restriction options 115 Restriction number 117 Configuring alarm restriction 117 16-Event to output 121 Output number 121 Configuring event to output 121 17-Auto arm/disarm 123 Auto arm/disarm program 123 Configuring auto arm/disarm 123 Using alarm group restrictions in conjunction with auto arm/disarm 124 18-Vaults
25-Display last card 137 26-Reserved menu 137 27-Reserved menu 137 28-To remote devices 138 Select the device type 138 Select the device to program 138 29-Computer connection 139 Computer connection settings 139 30-Printer 145 Printer settings 145 31-Battery testing 147 Select battery test program 147 Programming battery test 147 Select battery test 148 32-Custom LCD message 149 33-Program next service 150 Maintenance date 150 Maintenance message 150 34-Program system event flags 151 System event flag setti
51-Engineering reset 166 52-Voice reporting 167 Reporting code no. 167 Voice message no.
Programming sequence Advisor Master is a versatile control panel with many options to set up the system with necessary requirements. When programming it is easy to lose track if one does not use a good method. Using a good method also provides for an efficient way of programming. Basic set up The basic set up involves all settings to put an ATS control panel with the most common programming in operation. 1. Draw the floor plan and label all zones, equipment, areas etc.
Advanced set up The above steps are required to set up any basic system. Items that are not required can be skipped. Additionally the following items can be programmed: 1. In most cases assigning more then one area to a zone is used to program common areas. For special common area functions like being able to only disarm the common area, area linking is required. Program area linking using menu 19-Area linking. 2.
If the programming of the system is done, the system has to be tested. Menus providing support in testing are: Table 1: User menus 1-Panel status Provides system information. 2-Active zones Shows zones not in normal state (e.g. active or tampered). 3-Zones in alarm Shows any zone in alarm. 4-Inhibited zones Shows any inhibited zone. 5-History Lists all events that occured. 6-Test report Use this menu to perform an arm or disarm test. 10-Inhibit zone Inhibit any zone.
How to program the options For information on which keys to use while programming, please refer to these pages. Accessing the installer programming menu The ATS system is programmed from the Installer programming menu. Before accessing the programming menu the system must be disarmed. Note: Depending on system options, an additional authorization can be required. For more details, see: • “Installer dual code” en page 84. • “PIN of the day option” on page 89. See also Advisor Master Manager Manual.
You can easily move between the menu options by pressing the following keys: • • • • Enter or #: To scroll forwards one menu option at a time. Menu or * or : To scroll backwards one menu option at a time. Menu number and Enter or #: To jump directly to the menu option. 0 and Enter or #: Exit the Programming menu and return to the User menu. Different keys with the same function: • • Enter or #: These keys have the same function. [#] is used on LED keypads or 40 character LCD keypad (ATS115x or ATS112x).
Some programming menus need certain values to be entered, while others are used to select Yes/No. Programming lines containing Yes/No options often also allow the 0 key to be pressed. Use this key to skip a number of options. The display will indicate if the 0 key can be used on the second line. Programming menus like “Poll RAS”, “Poll DGP” or “Entry time” show the status of the current values. To update the values, press Menu.
1-Zone database Zone Database Zone: In this programming section all parameters are programmed regarding the zones. Each zone is a physical input on the control panel, a DGP or a plug-in expander. Zone number Select the appropriate zone number to program. Every zone has a number between 1 and 256, depending on the location in the system. Note: A list of zone numbers can be found with the Advisor Master Installation Guide.
Note: Camera count zone types (23 to 26 and 36 to 39) must always be connected directly to the ATS control panel zones and not to DGP zones. Table 3: Zone types Zone type Description 0. No zone type programmed Does not generate any alarm. 1. Disarmed alarm Generates an alarm when the area is disarmed and reports it to the central station. Generates no alarm if the area is armed. Example: Hold-up button. 2. Armed alarm Generates no alarm when the area is disarmed.
Zone type 8. Description Dis. delay/Arm Gen. Alm Generates an alarm when the area is disarmed but does not report it to the central station until the delayed alarm timer has expired or a second delayed alarm is activated. Generates a general burglar alarm when the area is armed. Example: Hold-up button on a counter where more than one hold-up button is used. You need to program the Disarmed Alarm Delay Time. See “6-Timers” on page 62 for more information. 9.
15. Zone type Description Firedoor Generates a local alarm when the area is disarmed. Automatically activates an audible alert on arming stations assigned to the same areas (regardless of the event flag programming). The only event flag activated (as specified in the zone database) is the zone event flag. This local alarm can be reset by entering "Enter, Enter, 0, Enter" or "user code, Off, area, Enter" on the arming station to stop the audible alert and cancel the event.
24. Zone type Description Camera 2 Count Used to increment the film counter for camera 2 by connecting a normally open contact across the zone. The counter increments if the zone switches from open to short. Can only be used with zones on the ATS control panel. 25. Camera 3 Count Used to increment the film counter for camera 3 by connecting a normally open contact across the zone. The counter increments if the zone switches from open to short. Can only be used with zones on the ATS control panel.
33. Zone type Description 24Hr Alarm & Inhibit This zone type requires different wiring. The zone can have the following states: • Shorted: generates an alarm • Normal: no alarm • Active: inhibit (no alarms generated) • Open: tamper alarm Example: Designed for shopping centres where only one zone is available for each shop. A keyswitch is used to inhibit the zone. 34. Area Dis/AlmGrp Restr.
40. Zone type Description Dis. Susp. Delay/Arm Alm If the area is disarmed it has the following functions: • Shorted: Activates cameras in the areas that are assigned to the zone. When the zone switches back to normal, the cameras continue to operate for the suspicion time. • Normal: No alarm. • Active: Generates an alarm but does not report to the central station until the delayed alarm timer has expired or a second delayed alarm is activated.
44. Zone type Description Firedoor with AlmGrp Restr. Generates a local alarm when the area is disarmed but does not report it to the central station. This alarm can only be acknowledged by entering "user code, Off, area, Enter" on the arming station Generates an alarm when the area is armed but the zone can be disabled when two users with alarm group restrictions have entered their user code (not necessarily in the same area). Example: Fire door or emergency door.
57. Zone type Description Technical Report & Screen When the zone is activated or tampered, it reports to the central station and puts the zone event text on the display. A restore is sent when the zone switches to normal state. Example: Temperature alarm on freezer Note: You need to program the zone event text. See “7System options” on page 70. 58. Technical Screen When the zone is activated, opened or shorted, it puts the zone event text on the display.
Zone type Description 70. Keybox This zone type is linked to the KeyBox timer. It acts as a 24hour alarm. When the KeyBox zone is active (KeyBox door/lid will not be opened during exit or KeyBox timer), it reports an alarm to the ARC. 71. Lock monitor The input is primarily used to prevent area arming when in a not sealed state. 72. GVE zone The purpose of this input is to signal a verified spiritual (Geistliche) User identification (e.g. valid PIN), which is the first step in disarming sequence.
Zone name 1: Office 4 Door 2 Contact TextWord 1: Once the correct zone number is selected, the zone needs to be given a name. The name identifies the zone to the end-user in case an alarm has occurred or on arming the zone is still activated. Without a proper name, the end-user would not be able to check for any problems that might arise in a particular zone.
transmitted depends on the chosen protocol and the selected class and subclass. The class holds the basic reporting range (medical, fire, panic). The subclass is used to provide differentiation in the event being reported. E.g. The panic class holds Contact ID codes 120 to 122 or SIA events PA and HA. See Table 14 on page 180. See “9-Communication options” (page 94), “42-Reporting class database” (page 161), and “Reporting” on page 180.
Engineer reset for tampers NO-Engineer Reset on Tamper *-Change 0-Skip Select Yes to enable engineer reset for tamper alarm in this zone. The user can not arm the area the zone belongs to, until an engineer reset has been performed. Yes: Engineer reset enabled for tamper alarms in this zone. No: No engineer reset. How to perform an engineer reset Whenever an engineer reset is required, the panel will display a 4-digit code.
Area / alarm group assignment For zones to perform correct actions when active, an area or an alarm group has to be linked to the zone. Whether an area or alarm group has to be programmed depends on the zone type (types 6, 31, 34, and 35 require an alarm group). Area The zone needs an area to be able to send alarm information to an area and a central station and to be able to reset when an alarm occurs.
There are five test procedure options, each identified by a reference number. This reference number is used to program a testing procedure. See Table 4 below for a description of each test type. Notes • This record is invalid unless the test mode is correctly programmed in the “7System options” (see page 70). • During the arm test, the testing event flag (event flag 16) will be activated during half the “Testing event flag” time (see “6-Timers”, page 62).
Zone event flag No Zone Event Flag Event Flag: You can program event flags that are activated by a zone. Up to 15 event flags can be assigned to an individual zone. An event flag is activated when the zone is in alarm (except for the zone event flag). The circumstances that cause a zone to generate an alarm depend on the zone type. The event flags activated by an alarm depend on: • Which event flags have been assigned to the zone.
Note: For the Internal siren event flag to operate, you must also program the Internal siren event flag number in the area database for each of the areas that activate internal sirens and that are assigned to the zone. Refer to “2-Area database” on page 28. See also “Zone event flag” on page 22. External siren event flag YES-External Siren, Program in DB *-Change 0-Skip Select if the external siren event flag should be activated. The External siren event flag is assigned in the Area database.
Trigger EF 2, armed alarm YES-Event Flag 2, Armed Alarm *-Change 0-Skip Yes: Event flag 2 is triggered when the zone generates an alarm and the area is armed. No: Event flag 2 will not be triggered. See also “Zone event flag” (page 22). Trigger EF 3, armed alarm See “Trigger EF 2, armed alarm” above. Trigger EF 4, armed alarm See “Trigger EF 2, armed alarm” above. Trigger EF 5, armed alarm See “Trigger EF 2, armed alarm” above.
Trigger EF 11, armed alarm See “Trigger EF 2, armed alarm” on page 24. Trigger zone EF if active NO-Trigger Zone Event Flag if Active *-Change 0-Skip Yes: The zone event flag is triggered when the zone is active, regardless of the status of the area(s) assigned to the zone. No: The zone event flag is only triggered when the zone generates an alarm. See also “Zone event flag” (page 22).
See also “Zone event flag” (page 22). Print zone when active NO-Print Zone When Active *-Change 0-Skip Yes: Activation of the zone has to be printed or sent to a computer. No: Activation does not have to be printed or sent to a computer. How to program See “How to program” on page 5 for information on which keys to use. Engineer walk test YES-Engineer Walk Test *-Change 0-Skip Yes: Zone will be configured to be included in the engineer walk test.
User walk test YES-User Walk Test *-Change 0-Skip Yes: Zone will be configured to be included in the user walk test. No: Zone will not be configured to be included in the user walk test. Note: Default will be Yes. Anti-mask detector YES-AntiMask Detector *-Change 0-Skip When this option is set to Yes, additional alarm windows are monitored for detector mask and fault conditions. For EN 50131 Grade 2, the lower alarm window, nominally 2,35 kΩ, is monitored for a combined masking and fault conditions.
2-Area database Each area can be programmed with a number of options, like the area name, entry- and exit times, event flags etc. Before going any further, select the area to program. Select the area to program Area Database Area No: Enter the area number to program. Area settings Area name Area Name: 0260, Workshop Text No: Every area can be programmed with a name to identify the area. The words are selected from a list already held by the ATS system.
Entry time Area 1 : > Exit Time 60 Entry Time 30 Entry time: Every area has its own entry timers. When entering the premises via a entry/exit zone, the entry time starts. A user can disarm the area while the entry time is running without generating an alarm. Each area can be programmed with one entry time. The entry times apply to zone types 3, 4, 13, 14, 41, and 42 (all entry/exit or access). The entry time however can only be started with zone types 3, 13, 41, and 42 (entry/exit).
Area active event flag Area 1 Active No Event Flag Event Flag: Used to indicate if any zone in the area is active, excluding zones that can be used to change the status of an area, that are used for camera’s or that are of zone type Unused. See also “External siren event flag” on page 29. Inhibited event flag Area 1 Inhibited No Event Flag Event Flag: A zone in this area has been inhibited. See also “External siren event flag” on page 29.
Entry timer event flag Area 1 Entry Timer No Event Flag Event Flag: Activates when an entry time for the area is running. See also “External siren event flag” on page 29. Warning timer event flag Area 1 Warning Time No Event Flag Event Flag: Activates to indicate that: • An alarm group restriction timer is running and the area is about to be armed. • A testmode is in progress and the test is about to end. See also “External siren event flag” on page 29.
the timer and is reset when either the timer time elapses or the area is successfully armed. It is also possible to initiate a walktest to reset the detector when acknowledging pending alarms. It is used with PIR detectors with an anti-mask feature. An output is assigned to the anti-mask reset event flag which is wired to the detectors. When this output is activated, the detectors must be triggered by a walk test in order for them to become normal after the output is de-activated (after 30 minutes).
Area disarmed time Area Disarmed Time: 0 Mins Enter Mins: When using alarm group restrictions, one of the options available is to disarm an area for a disarmed period. If the Area Disarmed time is not ‘0’, then this time will be used. See 15-Alarm group restrictions on page 115. Note: If the Disarmed time for the Alarm group Restriction is set to 0, to specify that the area will not re-arm, the "Area Disarmed Time" does apply for that area (see 6-Timers on page 62 for more information).
A&B alarm reporting (ACPO) NO-A&B Alarm Reporting (ACPO) *-Change 0-Skip Special facility for ACPO to be able to transmit verfied alarms. When the first zone activates, an alarm will be transmitted to the central station. If a second zone activates within the A to B time, a verified alarm will be transmitted. Otherwise a normal alarm will be transmitted. Yes: Use verified A&B reporting. No: No A&B alarm reporting. See “A to B alarm delay (ACPO)” (page 66).
Disarm complete event flag Disarm Complete No Event Flag Event Flag: Disarm complete event flag indicates completion of disarming. Alert indicator event flag Alert Indicator No Event Flag Event Flag: When an event occurs requiring text to be displayed on the user interface during the disarmed state, the alert indicator activates. Panic alarm event flag Panic Alarm No Event Flag Event Flag: An event flag corresponding to the state of the PA Area Alarm Timer running state (one per area).
• Activates if corresponding zone has the Anti-Mask detector option enabled. See “Anti-mask detector” on page 27 for more details. Panic Alarm (Hold-up) A Panic Alarm (Hold-up) A No Event Flag Event Flag: This event flag is activated when the area identifies a first panic alarm. Panic Alarm (Hold-up) B Panic Alarm (Hold-up) A No Event Flag Event Flag: This event flag is activated when the area identifies a confirmed panic alarm.
Part set external siren NO-Part Set External Siren *-Change 0-Skip Yes: A Part Set alarm will activate the External siren. No: A Part Set alarm will not activate the External siren Note: if the zone causing the alarm is assigned to a multiple areas and any of these areas has the Part Set External Siren enabled, the external siren will sound.
Disable part set B-alarms NO-Disable Part Set B-Alarms *-Change 0-Skip Note: This menu is only applicable if Part Set reporting is set to Yes. Yes: Alarm confirmation (BV) reporting is disabled when Part Set armed. First alarm report type (BA) is reported for all intruder alarms The B confirmed alarm event flag and the ‘Engineer reset on B alarm’ are also disabled. No: Normal Alarm confirmed reporting for Part Set.
3-RAS database Arming stations are devices used to provide system control, such as arming or disarming of areas. Depending on the type of arming station, additional functions can be available, such as LCD displays, menus to set time and date etc. The term RAS is an abbreviation for Remote Arming Station. RAS to be polled 1, 2, 3: 4 Poll RAS: Each arming station has to be polled, in order to be used. Add RAS’s for polling by entering the dipswitch address it has been given.
Menu alarm group RAS: 2 Alm-Grp: 2-Master RAS or Door Menu Alm-Grp: The menu alarm group determines which actions are allowed on a RAS. If no alarm control is allowed, this can be achieved in the menu alarm group. The menu alarm group can also have more areas than the area alarm group. The user can have no alarm control over those areas, but can for example see the status of zones in these areas.
Table 5: Programming the arming stations Programmable function Arming stations ATS1100 ATS1110 ATS1111 ATS1105 ATS1115 ATS1116 ATS1151 ATS1155 ATS1156 ATS1197 ATS1170 LCD arming station Y Y N N Toggle Area status N N O [1] O Enter key opens door only O O O N Door event flag on alarm codes O O O N Display shunted zone on LCD O O N N Arm/disarm using one key O [2] O [2] N N Cards auto disarm N O N O Card always arms/disarms N O N O Reset from RAS without code O O
Table 6: Using card readers for alarm control Function Programming options Toggle area Card auto Card Notes always Card, OFF disarms Card, ON arms No No No Card disarms Card arms Yes No Yes ATS1105, ATS1115, ATS1116, ATS1151, ATS1155, ATS1156, ATS1197 only Enter key opens door only YES-ENTER Key Opens Door Only *-Change 0-Skip Yes: When using LCD arming stations, using the On and Off key for alarm control results in a clearer user interface.
Arm/disarm using one key NO-Arm/Disarm Using One Key *-Change 0-Skip Yes: Provides an option to arm or disarm areas by pressing the number of the area without Enter, after having entered the user code. No: Normal alarm control. Note: This option is only available for areas 1-8. See Table 5 on page 41 for further information on options available to arming stations. Cards auto disarm NO-Cards Auto Disarm *-Change 0-Skip Yes: Allows cards to disarm areas without using the Off key.
AG restriction disarm only NO-AlmGrp Restriction Disarm Only *-Change 0-Skip Yes: Users with alarm group restrictions can only disarm or delay automatic arming. It cannot be used for alarm group restrictions with arm and reset. No: There is no restriction. See Table 5 on page 41 for further information on options available to arming stations. Entry/exit buzzers YES-Entry/Exit Buzzers *-Change 0-Skip Yes: Enable buzzer for entry/exit timers. No: No entry/exit timers on buzzer.
Disable status LED's YES-Disable Status LED's *-Change 0-Skip This option disables the optical indicators on the BUS device card readers. The option to enable or disable the status LED's will have to be set by the user because not all non-LCD BUS devices are card readers therefore this option will have to be set based on the hardware connected. If this option is set to Yes, the panel, when polling / commanding the card reader RAS, it will not set any of the LED bits in the packet.
RAS tamper (ACPO) area RAS Tamper (ACPO) Area 1 Area: Allocates the RAS to an area for alarm and tamper. The default is set to Area 1.
Enable chime YES-Enable Chime *-Change 0-Skip The RAS chime is triggered by any of the following input: Event flag, Zone activation, Zone shunting, Keys sequence. The chime is only activated on the RAS that has chime option enabled. For more information, see System Options > “Enable chime” on page 87. Timed lockout by wrong badges NO-Timed Lockout By Wrong Badges *-Change 0-Skip: If the Timed Lockout by Wrong Badges option is set to Yes, 10 wrong badges will cause a RAS lockout as well as wrong codes.
4-DGP database This menu enables or disables DGP’s (Data Gathering Panels). Also the type of DGP can be programmed. DGPs to be polled 1, 2, 3: 4 Poll DGP: Each DGP has to be polled, in order to be able to exchange data with the ATS control panel. Add DGP’s for polling by entering the dipswitch address it has been given. DGP’s that do not have to be polled can be deleted by entering the dipswitch address again. The display shows the DGP’s currently recorded.
• • • • 4-IADS DGP: ATS1290 5-Advanced DGP: ATS1203, ATS1204, ATS1201E, ATS1203E, ATS1204E, ATS1210LE, ATS1211E 6-Bank DGP: ATS1280 7-Advanced wireless DGP: ATS1234, ATS1235 DGP Tamper (ACPO) Area DGP Tamper (ACPO) Area 1 Area: Allocates the DGP to an area for tamper. The default is set to Area 1. DGP battery test event flag The event flag is set for the duration of a battery test cycle for both manually initiated battery tests and scheduled tests.
5-Alarm groups This program block is used to record information about alarm groups. What is an alarm group? An alarm group provides means to users, zones and arming stations to control the ATS system regarding alarm functions (also called alarm control). Alarm groups have areas, menu options, panel options and timezones. Alarm groups are assigned to users, and to each piece of equipment on which the user performs a function (arming stations, doors 17 to 64, and area control zone types 6, 31, 34 and 35).
Table 7: Default settings for alarm groups Number Name User menu options 1. No access All set to No 2. Master RAS or door All set to Yes 3. Master code access All set to Yes except 25 4. 8 area master RAS (1-8) All set to Yes except 25 5. 8 area master RAS (9-16) All set to Yes except 25 6. Master user All set to Yes except 25 7. Manager All set to Yes except 19 8. Master Installer All set to No 9. Master Service All set to Yes except 25 and timezone 25 10.
from a list of words that you have programmed yourself (see “10-Program text” on page 102). The display shows the current alarm group name, preceded by its reference number). Areas assigned 1,2,3,5,7,8,9, Area: Assign the areas to be controlled by the alarm group. An alarm group can only control the functions of areas that are assigned to it. User alarm group No-Can this GRP Be Assigned To Users *-Change 0-Skip: Define if the alarm group can be assigned to users, or only to zones and RAS’s.
List of areas NO-Prompt With List of Areas *-Change 0-Skip: Select whether the areas assigned to a user are displayed during the arm/disarm procedures. Yes: After the user has entered a PIN and pressed On or Off, the areas assigned to the user are displayed. The user can then select from the arm/disarm options (e.g., specific areas, all areas, etc.). This feature is useful when a user can control several areas but usually only arms/disarms specific areas.
Disable auto-uninhibit NO-Disable Auto-Uninhibit *-Change 0-Skip: Determines that inhibited zones are uninhibited on disarming the area the zone belongs to. Yes: Disarming the area will not automatically uninhibit zones in the area. Used for cleaners, etc. No: Disarming the area will automatically uninhibit zones. Press 0 to go to the user menu items available. Note: “Auto uninhibit on disarm” on page 73 in “7-System options” has to be set to Yes.
Auto inhibit active zones NO-Auto Inhibit Active Zones *-Change 0-Skip: Determines if active zones on arming have to be automatically inhibited. Yes: When the arming starts, all active zones are automatically inhibited and the system is armed without causing an alarm. No: The system cannot be armed if there are active zones, unless Forced Arming is set to Yes (see next menu item). Press 0 to go to the user menu items available.
No: Modem access with VT100 terminal (or terminal emulation software) is not allowed by a user with this alarm group. Press 0 to go to the user menu items available. Alarm group restriction 1 No –User Has Alm/Grp Restriction 1 *-Change 0-Skip: Alarm group restrictions give certain restrictions to alarm groups. Only 1 restriction is available per alarm group. However, every alarm group can use the same restriction. Alarm group restrictions restrict alarm control to timed disarm or arm/reset.
See also “15-Alarm group restrictions” on page 115 and “Alarm group restriction 1”. AlmGrp restriction 8, Counter No –User Has Alm/Grp Restr 8 - Counter *-Change 0-Skip: Operates as alarm group restriction 1, but on disarming it will increase a counter. When the area is armed using this alarm group it will decrease the counter. When the counter reaches 0, it will arm the areas in the alarm group. Yes: The alarm group restrictions are activated. No: The alarm group restrictions are not activated.
PIN Code: 1111 Code: The user enters his new PIN. PIN Code: 1111 Code: 1234 Followed by entering: PIN Code: 1234 Code: The user can change the code again, or press Enter to exit. If the “Change own PIN only” option is set to Yes and if the System Option “Disable code from displaying” is set to Yes, then the display will show the following: PIN Codes Can Not Be Displayed Code: The user can then enter his new PIN and will be asked to confirm.
Each user menu is displayed and must be set to Yes for it to be available to the alarm group. The user menus available for selection are: Table 8: User menu options available 1. Panel status 15. Time & date 2. Active zones 16. Isolate/de-isolate RAS/DGP 3. Zones in alarm 17. Authorization Service In 4. Inhibited zones 18. Reset cameras 5. History 19. Installer programming 6. Test report 20. Door and floor groups 7. Service menu 21. Holidays 8. Film counters 22. Open door 9.
Notes • The alternate alarm group can also be programmed with an alternate alarm group and so on - up to three alarm groups (the original plus two alternates). If a function is denied by the timezone of one alarm group, the next will be checked, etc. • When alternate alarm groups are active and these have alarm group restrictions, the alternate alarm group restrictions apply. See also 15-Alarm group restrictions on page 115.
Items that prevent setting but may be overridden by the Grade 4 level 2 user: • • • Detector masked Detector fault AC mains fail (this includes any DGP) Items that prevent setting but may be overridden by the Grade 4 level 3 user: • • • • • • Detector masked Detector fault AC mains fail (this includes any DGP) Battery low or missing (this includes any DGP) All signalling paths in fault All warning devices and all signalling paths in fault User Can Override Line Fault NO-User can override Line Fault *-Ch
6-Timers Program all system wide timers in this section. Notes • Timers are accurate on ±1 of the value entered. So a timer set for 20 seconds, will end somewhere between 19 and 21 seconds. Consequently, avoid using values of 1 second or 1 minute. • If a timer is set to 0, that timer will not be used. Timer settings AG restriction 1 disarmed time Alm/Grp Restr.1 Disarmed is (Min).
AG restriction 7 disarmed time Alm/Grp Restr.7 Disarmed is (Min). 0 Time: After the disarmed time has expired, not only the area(s) are armed, but also an emergency alarm will be sent to the central station. See “AG restriction 1 disarmed time” on page 62 and “15-Alarm group restrictions” on page 115. AG restriction 8 disarmed time Alm/Grp Restr.8 ** NOT USED ** Time: The disarmed time for alarm group restriction 8 does not have any significance, because the system ignores any values entered here.
Notes • Always set the warning time to a time shorter than any Alarm group restriction disarmed time. • See “15-Alarm group restrictions” on page 115 and “AG restriction 1 disarmed time” on page 62. Disarmed alarm delay time Disarmed Alm Delay Time Set To (Sec). 60 Time: Determines the delay time (0 to 255 seconds) before an alarm from a delayed disarmed alarm is reported to the central station. The delay time is ignored if another delayed zone type has already been activated.
Individual zone test time Individual Testmode Time (Min). 5 Time: Enter the maximum time (0 to 255 minutes) to perform a test on an individual zone, using user menu Test zone. Note: See the manager guide, user menu Test zone for more information. Doors unlock time Door(s) Unlock Time (Sec). 5 Time: The time doors will unlock (using the door event flag). This time value is common for all door event flags from RAS’s connected to the ATS system, i.e. doors 1 to 16.
Siren delay set to Siren Delay Set to (Min) Time: This option allows you to set the delay time (0 to 255 minutes) before the sirens actually activate after an alarm has occurred. This can be used for recording any sounds before the siren activates. The siren delay is set to 0. Mains fail delay time Mains Fail Delay Time (Min). 10 Time: The delay time (0 to 255 minutes) before a Mains Fail is reported to the central station. Enter a value of “0” for no delay.
system user can also activate the screen saver manually by pressing the CLEAR key at the Enter Code prompt. RAS card & PIN timeout RAS Card & PIN Timeout (Sec). Time: Allows you to set the delay time (0 to 255 seconds) between badging the card and entering the PIN (default is 8 seconds). Double knock interval (min) Double Knock Time: Interval (Min). If enabled for a particular zone, Double Knock Interval specifies the maximum permitted time a zone may remain active.
Abort time (sec) Abort Time (sec). 30 Time: An additional system “Abort Timer” for entry fault reporting is implemented to create an additional delay of 30 seconds (programmable from 0 to 255) after the entry time has been expired before the entry fault is reported. RAS lockout time RAS Lockout Time (sec). 90 Time: Allows you to set the time, for which the RAS becomes locked after a code tamper. The allowed range is 1 to 255 seconds. See also “Timed lockout by wrong codes” on page 44.
Panic A to B delay Panic A to B delay (Hours) Time: Panic A to B delay (Min) Time: The time for which the system awaits for a second alarm (“B”). If the second alarm occurs within this delay time, this will be reported as a verified panic alarm. Alarm condition can be initiated: • By two separate hold-up devices • By one hold-up device, confirmed by a tamper or a fault from the same area The allowed range is 0:00 to 20:00 (hh:mm).
7-System options Program options common to the complete system. Configuring system options Areas selected for total disarm 16 Disarm Areas: 24-hour zone types (Disarmed Alarm or Firedoor) can be completely disarmed using this menu. If the areas entered here are disarmed, 24-hour zone types are inhibited. For best functionality, assign a common area to the 24-hour zone type (its own area and the area programmed here). Disarm the programmed area to disable the zone(s).
Film out level Film Out Is Set To 1100 Film Level: The film level number programmed is the film frame count. When this frame count is reached, an out of film is reported to the central station. This option is related to the camera count zone types 23 to 26 and 36 to 39. Note: Relates to zone types 23 to 6 and 36 to 39 (camera count). See “1-Zone database” on page 7. Test mode 1, Enable Auto Test Option: The test mode determines if or when an arm or disarm test has to be performed.
Do not enter values here for output controllers fitted to DGP’s. Zone event text Zone Text: 0103, Gate Text No: When zone types 57 and 58 are active, this zone event text will be displayed on LCD keypads. The text is taken from the text word library and is programmed as a reference number. A free programmable text can be programmed using “10Program text” on page 102. The zone event text only appears when the zones are active, for example “Freezer open”.
the speed is too slow, long texts might take too long to show. The default value 0, which is equal to 8. Any value from 9 to 15 decreases the text rotation speed. Any value from 1 to 7 increases the text rotation speed. Note: This option can only be programmed for LCD arming stations, like ATS1100 or ATS111x. Dual zone NO-Dual zone *-Change 0-Skip Determines if dual zone is used. For dual zone to operate, every zone needs additional end-of-line resistors.
Yes: One zone at a time is displayed even though there may be more than one in the list of zones to be displayed. The user must scroll through the zones. eg. Active 2. Building 1 Workshop PIR. No: Zones are displayed as a list of numbers and it is necessary to select the zone number to display the individual zone name. eg. Active 1, 2, 3. Press 0 to skip further options and leave system options. Username file YES-Username File *-Change 0-Skip Determines if users have names with their PINs programmed.
Note: Remember to program the users alarm group with “Reset system alarms” set to Yes. See “5-Alarm groups” on page 50. Siren testing NO-Test Siren *-Change 0-Skip Enable a siren test when the arm test is started. Yes: The sirens are tested for three seconds when the arm test is started. No: Sirens are not tested when the arm test is started. Press 0 to skip further options and leave system options. See “Test mode” in “7-System options” on page71.
Disable code from displaying NO-Disable PIN Code From Displaying *-Change 0-Skip Disable display of the PIN when programming users Yes: PINs are not visible (except for master installer). The display shows “PINs can not be viewed”. No: PINs are visible to. Press 0 to skip further options and leave system options. See also Advisor Master Manager Manual regarding programming codes.
Yes: Details of the first alarm are displayed instantly on the LCD arming station. Details of other alarms can be viewed on the LCD arming station by pressing the Enter key twice. No: Details of all alarms can be viewed on the LCD arming station by pressing the Enter key twice. Press 0 to skip further options and leave system options.
Press 0 to skip further options and leave system options. See also Advisor Master Manager Manual for more information on users and user flags. Delayed disarmed alarm lockout NO-Delayed Disarmed Alm Lockout *-Change 0-Skip This is only applicable to latching delayed disarmed alarms. If set to Yes, an alarm can only be cancelled if the zone is in normal state. Therefore a latching disarmed alarm is locked out until the alarm device is taken out of its latched state (reset).
Report multiple alarms NO-Report Multiple Alarms In Zone *-Change 0-Skip The system is able to report multiple alarms that occurred in a zone (depending on the reporting format). Yes: Report multiple alarms as a separate alarm for each alarm that occurs. No: Only report the first alarm. Every next alarm that occurs will not be reported. Press 0 to skip further options and leave system options.
Engineer reset for system tampers NO-Engineer Reset for System Tamper *-Change 0-Skip If an engineer reset is required on system tamper alarms, set this option to Yes. A user can not arm any area until an engineer reset has been performed. Yes: Engineer reset required on system tampers. No: No engineer reset required. Press 0 to skip further options and leave system options. Ignore battery fault when arming NO-Ignore Battery Fault when arming *-Change 0-Skip Enables to arm the system without any battery.
User offset User Offset Set to 0 Enter Offset The offset is used to report user ID’s to management software. The offset is 0 to 65535. When a user ID is sent to the management package, this offset is added or subtracted. The control panel itself uses the user ID without offset. End of line resistor code End Of Line Resistor Code 0 Code: The End of line resistor code is used to set the correct value for the end of line resistor used. By default this is set to 4,7 kΩ.
both are active, thus generating a DC voltage at the siren output.
Soak test days Days for Soak Test Days: This option sets the numbers of days for the soak test period. It can be set from 0 days to 255 days. Refer to “Enable soak test” on page 19 for more information. The default is set to 7 days. ACPO NO-ACPO *-Change 0-Skip When this option is set, all alarms triggered within the entry time, provided an entry/exit zone is triggered first, will be dealt with as an “A” Alarm. They will not be reported to the CS before the entry time has elapsed.
Installer dual code YES-Installer Dual Code *-Change 0-Skip This option enables installer access authorisation by valid system user. If this option is set to Yes, then a second, user code must be entered before access to any menu is granted. The second code must be a valid user code with no access to the installer menu. Enter User Code Code: The second user must have Alarm System Control and not have access to menu 19.
Exceptions This text will not appear after reporting PANIC, HOLD-UP Alarms (HA) reports or disarming by a Duress PIN. Also when a LINE FAULT is concurrently active, this text will not appear. Screen saver YES-Screen saver *-Change 0-Skip Allows the user to enable or disable the screen saver. Yes: Screen saver is enabled. No: Screen saver is disabled.
Eng Rst on ACPO system B tamper YES-Eng Rst on system B tamper *-Change 0-Skip Enables engineer reset lockout for ACPO system B-tamper/offline. Security grade The Security grade option allows the panel behaviour to change based on the grade level of the installation.
Enable PA siren on FTC NO-Enable PA Siren on FTC *-Change 0-Skip When set to Yes, and a Line Fault, or Fail-To-Communicate, condition exists, the operation of a silent panic alarm changes to that of an audible panic alarm. When the Line Fault, or FTC, restores, the silent panic alarm reverts to silent operation.
• Programme the activating device for chime. Options: programme in the area database a Chime activated RAS number (see “Chime on RAS” on page 38), or assign the chime event flag to the keypad buzzers in System flags (see “Keypad buzzer event flag” on page 153), or assign the Chime event flag to an output number. Synchronize DGP users records YES-Synchronize DGP users records *-Change 0-Skip Synchronization allows restoring user record in DGP user database, if the card number is missing.
• Watchdog fault • Exit fault • Other alarm system component fault The default is Yes. PIN of the day option Caution: Once this option is switched to Yes, it cannot be switched back to No. YES-PIN Of The Day Option *-Change 0-Skip If PIN of the day option is set to yes, the installer can only enter the system with a response code, which can be obtained from the appropriate security manager. The code is calculated basing on the PIN of the day that is generated for the particular session.
Override battery fault YES-Override Battery Fault *-Change 0-Skip If set to Yes, the user can manually override battery fault when arming. The default value is Yes. Override signalling fault YES-Override Signalling Fault *-Change 0-Skip If set to Yes, the user can manually override reporting fault when arming. The default value is Yes. Override siren fail YES-Override Siren Fail *-Change 0-Skip If set to Yes, the user can manually override siren fault when arming. The default value is Yes.
Override RAS fault YES-Override RAS Fault *-Change 0-Skip If set to Yes, the user can manually override RAS fault when arming. Note this does not apply for RAS offline scenario. (Offline RAS must be isolated by installer to proceed arming). The default value is Yes. Override DGP fault YES-Override DGP Fault *-Change 0-Skip If set to Yes, the user can manually override DGP fault when arming. Note that the overriding does not work if DGP is offline.
RF jamming set sirens NO-RF Jamming Set Sirens *-Change 0-Skip If set to Yes, the RF jamming attempt activates: • • Internal siren and alarm LED in disarmed state. Internal and external sirens and alarm LED in armed state. Number of attempts for PIN of the day Number Of Attempts For PIN Of The Day: Enter the number of attempts that can be made to enter a responce code before the keypad becomes locked and the code tamper occurs. 0 means that attemts are unlimited.
8-Auto reset Auto reset is a function to automatically reset alarms from an ATS control panel. Auto reset settings Auto reset time Auto Reset Time (Mins): 15 Time (Mins): The display shows the existing reset time. This is the amount of time that elapses between the alarm occurring and reset. Reset alarm group Reset Alm-Grp: 35, Low priority Areas Alm-Grp: The control panel has to know which areas to auto reset. Using an alarm group does this. See also “5-Alarm groups” on page 50.
9-Communication options This menu is used to program all system-wide communication options. Configuring communication options PABX number *-Pause, Ph No: PABX: A PABX number hold a number that precedes any other number being dialled. Used only if the dialler is connected via a PABX to the telephone network. How to program a telephone number Press one of these keypad buttons to: • • • • Number, Enter: Enter the telephone number. Menu: Insert a pause or “T” in the telephone number.
No: Use pulse dialling. Enable PSTN line fault monitor NO-Enable Line Monitor *-Change 0-Skip A line monitor will detect if the line voltage on the telephone network is within limits. If not, a telephone line failure will occur. Yes: Enable the line monitor. No: Line monitor is disabled. Press 0 to skip further options and move to central stations.
200 baud reverse area OP/CL No– 200 Baud Reverse Area Open/Close *-Change 0-Skip If set to No, disarm events are reported as type “A” and arm events are reported as type “R” (Default) If set to Yes, disarm events are reported as type “R” and arm events are reported as type “A” X25 TEI value X25 TEI Value Value: The X25 TEI value for the ISDN-D channel connection. The range is from 1 to 63.
Note: Setting is ignored if “Enable buzzer on mains/line fault” on page 84 is set to Yes. GSM line fault YES-Enable GSM Line Fault Monitoring *-Change 0-Skip: Enables GSM Line Fault Monitoring. Note: The panel requires a reset in order for the change to take effect. Select the central station Central Station 1..4 CS No: Enter the central station to program. Select the reporting format Disabled Format No: Every central station can report using a different format.
Enter the 1st phone number *-Pause, Ph No: Ph1: Every central station can report to 2 telephone numbers: 1 main and 1 back-up number. Enter the main number here. See also “PABX number” (page 94). Enter the 2nd phone number *-Pause, Ph No: Ph2: Every central station can report to 2 telephone numbers: 1 main and 1 back-up number. Enter the back-up number here. See also “PABX number” (page 94).
Yes: Use BELL modem tones for (X)SIA reporting. No: Use CCITT modem tones for (X)SIA reporting. Press 0 to skip further options and move to central stations. Dual reporting NO-Dual Tel Line:Reporting *-Change 0-Skip If an acknowledge should be received from both phone numbers, set this option to Yes. Yes: Use dual reporting. No: Use normal reporting. Press 0 to skip further options and move to central stations.
X25 line type X25 Line type - 0 Value: Sets the polling time of the line. • • 0: Permanent 15 minutes polling. 1: Permanent 90 seconds polling.
• • Nri11/ZR123: New event, Area 11, ZR on input 123. Nri00/RR316: New event, power-up X25 D-Bit YES-X25 D-Bit *-Change 0-Skip Specifies the X25 D-Bit option ON or OFF for an ISDN-D network configuration. Yes: D-Bit option for an ISDN-D network is ON. No: D-Bit option for an ISDN-D network is OFF. Notes • • Default setting for The Netherlands is ON. Default setting for Belgium if OFF.
10-Program text The ATS control panel uses a library of pre-programmed words that are used when programming the names or texts into the system (e.g.: zone names, area names, etc.) These words form part of the variable text that appears on the LCD display. All the words in the library are identified by a reference number, which ranges from 001 to 899. See Table 9 on page 104 for the list of pre-programmed words available. Not all words can be in the library.
How to access customised text Press one of these keypad buttons to: • • • Menu: Scroll through the list of programmable words 800 or 900 to 999. Enter: Return to the Programming menu. ?, Enter: Enter the reference number of the customised word you want to change/add. How to program or modify text Press one of these keypad buttons to: • • • ?, Enter: Enter each letter and press Enter to move to the next position. Menu: Save and display the word.
Word library Table 9: Word library A B C 104 001 Above 008 Area 009 Arming 002 Access 332 Area One 421 Art 003 Accountant 333 Area Two 265 Assistant 264 Accounts 334 Area Three 367 Assistant Manager 417 Accounts Manager 335 Area Four 369 Assistant Manager Day 004 Across 336 Area Five 422 Assistant Principal 404 Admin 337 Area Six 423 Assoc Administrator 418 Administration 338 Area Seven 010 At 272 Air Conditioning 339 Area Eight 011 ATM 005 Alarm 340 Area Nine 308 Atrium 00
D E F 041 Ceiling 051 Cold 432 Covered Area 042 Cellar 052 Combination 061 Covering 043 Central 428 Commerce 522 Curtain 426 Central Bulk Store 053 Commercial 269 Custody 431 Centre 054 Communication 062 Customer 274 Dairy 066 Dining 503 Double 433 Dark Room 296 Digital 275 DOTL 304 Data 067 Dispatch 070 Downstairs 063 Delayed 435 District Facility 071 Driveway 266 Desk 068 Dock 072 Drug 064 Detector 069 Door 436 Dry Craft 434 Developmental 465 Doors 074 DUALTEK 065 DG
446 GLA 391 Group 17 549 Guard Patrol Limited 447 GLA/Stage 392 Group 18 279 Gun 105 Glass 393 Group 19 315 GYM 328 Goods 394 Group 20 H 107 Hall 109 Heat I 444 Hallway 364 High Level User Master 382 Holdup Button 108 Hand 527 High SSO 451 Home Economics 327 Hatch 110 Holdup 114 Internal 111 In 112 Input 524 Isolate 280 Inertia 452 Instrument Store 281 Inner 113 Interior J 453 Janitor 115 Jewelry 365 Junction K 355 Key 353 Keyswitch Inhibited 117 Kitchen 545 KeyBox 116
P 158 Office 161 Open 286 Outer 159 Officer 466 Orchestral 162 Over 163 Panel 169 Phone 471 Pre-School 164 Panic 170 PIR 472 Preparation 165 Park 322 360 PIR 473 Principal 467 Passage 287 Pit 311 Print 166 Passive 288 Plant 474 Printery 468 Patrol 470 Playroom 475 Production 531 Patrol-2 357 PNEUMATIC 310 Productivity 533 Patrol-3 171 Point 476 Professional Support 167 Penset 172 Pool 175 Protection 469 Performing Art Centre 356 POPUP 477 Public Waiting 168 Perimeter 17
201 Sensor 493 Sports Store 226 Storage 485 Servery 494 Spray 227 Strobe 202 Service 218 Sprinkler 359 Strongroom 547 Service Allow 219 SRT 228 Strike 405 Service Bay 544 SSO 498 Student Centre 546 Service Code 314 ST 499 Student Waiting 486 Service Manager 220 Staff 500 Studies 487 Services Room 495 Staff & Amenities 501 Studio 203 Shop 525 Staff Areas 1 to 4 319 Substation 204 Short Tom 526 Staff Areas 5 to 8 291 Sump 205 Show 380 Staff Door 229 Supermarket 206 Side 521 S
11-Version Displays the version information for the control panel, the RASs and DGPs. Select device Version 1 - ATS CP 2 - RAS 3 - DGP 0-Exit, Menu: Each device shows different information.
12-LED test LED Test is Off Code: This function is used to test all LEDs in the system. This includes LEDs on arming stations, card readers, etc. You can turn all the LEDs on by entering a valid code, exit the Programming menu, check the LEDs on all Arming Stations, then return to the menu to turn the LEDs off by entering a valid code again. How to program Press one of these keypad buttons to: • Code, Enter: Enter a valid user code and press Enter to turn on/off all the LEDs in the system.
13-Timezones Timezones are used to create timeslots in which certain events can take place. Timezones are for example used to automatically arm areas, disable users or to activate outputs to open a door. Timezones are assigned to alarm groups, door groups, floor groups, relays/outputs, arm/disarm timers, and Out of Hours Access reporting to restrict/enable some ATS operations during specific time periods. There are two main types of timezone. However, both have the same function.
How to program timezones Press one of these keypad buttons to: • Menu: Skip this timezone. • ?, Enter: Enter a new value. • Enter: Save the time values displayed and move to the days display. Note: If you only want to change one of the time values (e.g. change end time from 17:30 to 18:30), you must re-enter each time value. Timezone settings Program start time, hours Tz 1.1 Start–08:00 End–00:00 Start Hours: First program the hour for starting time for the timezone, sub-timezone 1.
14-Defaults Sometimes it is necessary to bring the control panel back to factory defaults. For example when a system is going to be programmed for the first time or when programming a system that has been de-powered for an extended period (more then 2 weeks). Select default option 99-All, 98-STD, 97-Output/Groups, 95 Software IUM Option: Select the programmed options to bring back to factory default. 99-All Resets all the system records to the factory default. All programming is erased.
Users against memory size and type There are two types of memory configurations: Standard Memory and Intelligent User Memory configuration. Refer to the table below. No. of cards No. of PINs No.
15-Alarm group restrictions Alarm group restrictions provide means to define certain alarm control functions for certain areas in alarm groups. Alarm control can be restricted to “Timed disarm” and “Arm/Reset only”. Two special restrictions are available: • Alarm group restriction Emergency • Alarm group restriction Counter The combination of alarm group and alarm group restriction provides the available alarm control to a user (or keyswitch).
Alarm group restriction 7 – Emergency: Special function for Security Guards on a guard tour who need to check in at certain intervals. As alarm group restriction 1 to 6, except that when the timer expires and the areas re-arm, an “Emergency” message is reported to the central station. Alarm group restriction 8 Counter: When the users enter their code to re-arm, the user count for each area decreases by one. Special Function: User count for each area The display always shows the user count.
• Users cannot operate alarm group restrictions unless the arming station they are using has the same alarm group restrictions in its alarm group. Restriction number Alarm Group Restrictions Restr. No: First select the Alarm group restriction to be programmed (numbered from 1 to 8). Configuring alarm restriction Alarm group restriction name Restriction Name: 0352, Cleaner Text No: Select the name of an alarm group restriction from the list of words already held by the ATS system.
1st alternate timed disarm area 9,10, 2, Timed Area: As explained in “5-Alarm groups” on page 50, it is possible to have alternate alarm groups. The alternate alarm group is used when the original alarm group is not available due to an invalid timezone. When an alternate alarm group is active and the alternate alarm group has an alarm group restriction, the alternate alarm group restriction is used.
User 1 Alarm group 31 Areas: 1, 2 AG restriction: 4 Timezone: 1 Alternate AG: 32 Alarm group restriction 4 Use standard restriction 1, Timed Area: 1, A/R Area: 2 Timezone 1 invalid Alarm group 32 Areas: 1, 2 AG restriction: 4 Timezone: 2 Alternate AG: 33 Use 1st alternate restriction 2, Timed Area: 2 2, A/R Area: Timezones 1 and 2 invalid 3, Timed Area: 1 3, A/R Area: Use 2nd alternate restriction Alarm group 33 Areas: 1 AG restriction: 4 Timezone: 0 (always) Alternate AG
1st alternate areas to arm/reset 9,10, 2, A/R Area: See “Areas to arm/reset”, “1st alternate timed disarm area” and “5-Alarm groups” (on page 50). 2nd alternate timed disarm area 12, 3, Timed Area: See “1st alternate timed disarm area”. 2nd alternate areas to arm/reset 12, 3, A/R Area: See “1st alternate areas to arm/reset”.
16-Event to output Programming section to link events to outputs. Outputs are available as relay cards (ATS1810, ATS1811) or open collector outputs (ATS1820/1821). Before an event flag actually will activate an output, a number of conditions have to be met: • The timezone has to be valid (if programmed). • The output logic defines how the output behaves when the timezone is valid. • The output behaviour can be set to normal or inverted.
Defaults The only events activating an output by default are: • • • • Output 2 (strobe output) is linked to event flag 2. Output 16 (panel siren output) is linked to event flag 1. Output 15 (internal siren output) is linked to event flag 13. Output 32, 48, 64, 80, 96, 112, 128, 144, 160, 176, 192, 208 224, 240 (DGP siren outputs) are linked to event flag 1. For more information on event flags, see “Event Flags” on page 177.
17-Auto arm/disarm To automatically arm and/or disarm areas, timezones are used. Areas being armed or disarmed automatically do not require any user action. Note: If the “Prevent arming on faults” option described on page 88 is set to Yes, particular faults may prevent auto arming. To avoid this, make sure that the selected alarm group in “Alarm group to auto arm/disarm” below allows forced arming. See also “Using alarm group restrictions in conjunction with auto arm/disarm” on page 124.
If the alarm group setting for disarm only is set to Yes, then the assigned areas will only automatically disarm. See “5-Alarm groups” on page 50 for further information. If the alarm group setting for any alarm group restriction is set to Yes, then a user can extend the time that the area(s) are disarmed for a specified period. See “Using alarm group restrictions in conjunction with auto arm/disarm” below for further information. • Each combination of a timezone and an alarm group is called a program.
• If a separate warning beeper needs to be activated from an output, link the output to the “Warning timer event flag” on page 31 that is programmed in the “2-Area database” for the areas specified in the alarm group restriction. • Ensure that the alarm group restrictions are also assigned to the alarm group for the user's and arming stations. For further information, see: • • • • “5-Alarm groups” (page 50), “6-Timers” (page 62), “15-Alarm group restrictions” (page 115), User menu 14, Program users.
18-Vaults Vault areas are areas that will automatically arm other areas after a preset time once they are armed. A user that has the vault areas in his alarm group arms the vault areas. The time starts only if all vault areas are armed. The user does not need to have alarm control over the areas that are automatically armed. 2, 3, 4, Area: By using a special programming procedure, an alarm group restriction timer starts when all the vault areas are armed.
19-Area linking In an object with multiple areas, the entrance to the object in most cases is shared by all areas. This shared area should only be armed when the last area is armed. The shared area is a common area. The simplest way to have a common entrance is by assigned multiple areas to a zone. This zone will only generate an alarm if all assigned areas are armed. The longest exit and entry time will be used. The other way to create common areas is by using a dedicated area.
20-System codes The ATS control panels support up to two different system codes (sometimes also referred to as "Site codes" or "Facility codes") for use with ATS1170 onedoor RAS. Each system code also provides an option to offset the card ID for easier programming. The system code is a unique code provided by the supplier. Notes • The ATS125x/1260 four-door/four-lift DGP does not require this setting to be programmed in the control panel.
System code 2 System Code 2: 005678 SysCode: Specify the second system code, if required. See “System code 1” på side 128 for further information. Card offset 2 Card Offset 2: + 0 *-Chg, No: Specify the card offset for cards in system code B. See “Card offset 1” on page 128 for further information.
21-Zone shunts A shunt procedure inhibits a zone from generating an alarm during a certain time period when active. A zone shunt starts on an output being activated, on most occasions a door unlocking. During the shunt time the zone is inhibited. If the zone is still active after the shunt time has expired, the zone will generate an alarm, depending on the zone type and the status of the area. A shunt timer (16 available) that can be programmed individually controls each zone shunt.
Shunt time Shunt 1: Time Is Set For (Sec) 30 Shunt Time: Program the amount of time that the zone will be shunted. If the time expires and the zone remains active, an alarm condition occurs, depending on the zone type and the status of the area. If the value entered is less than 128, the time is in seconds. I.e. 1 to 127 seconds. To set the time in minutes the value entered is 128 plus the time required in minutes. E.g. for 30 minutes enter 158. (128 + 30 = 158).
No: The condition of the zone, normal to active, triggers the timer. Press 0 to end programming this shunt timer and to select a new shunt timer. Notes • If this option is set to Yes and the keypad or shunt relay starts the shunt timer, the timer resets if the zone does not switch to normal state within: - 3 seconds if the shunt time is programmed for 1 to 127 s. - 3 minutes if the shunt timer is programmed for 1 to 127 min.
Zone holds event flag for 2 seconds NO-Zone Holds Event Flag for 2 Sec. *-Change 0-Skip Delay cancelling of the door event flag. It is used for doors with magnetic locks and drop bolts. Yes: In order to allow time for a door to be properly closed, there is a 2-second delay after the zone switches to normal and before it cancels the door event and shunt timer. No: There is no delay. Press 0 to end programming this shunt timer and to select a new shunt timer.
22-Timezone to follow output Select a timezone to follow an output. When the output is active, the timezone is valid. Use this option to invalidate alarm groups if certain conditions are not met. For example: • Prohibit the use of a keypad, unless a keyswitch on a zone is active. • Allow an area to be disarmed only if another area is disarmed before. The timezones that follow outputs are also referred to as soft timezones. Hard timezones are valid between a start and end-time.
23-Poll errors Use this menu to get an indication on how many errors have been detected in communications between the ATS control panel and devices connected to it. Select device type 1-RAS, 2-DGP, 3-Clear All Counters 0-Exit, Menu: Select the type of devices to view the number of poll errors on. Optionally the error counters can be reset.
24-Download to remote device Download data to remote devices like the ATS125x/1260. The data to download concerns access control functions for the four-door/four-lift DGP’s. While the four-door/four-lift DGP’s are programmed to be polled and are online, any programming done regarding these DGP’s will be automatically downloaded.
25-Display last card Show the system code and I.D number of the last card read by a reader connected to the ATS system databus (for doors 1 to 16 only, not for doors 17 to 64 on four-door/four-lift DGP). Last Card RAS SC=23 User=987654 Press ENTER In this example the display shows the system code as “SC=23” and the card ID as “User=987654”. How to program • Enter: Return to the Programming menu. Note: The card must have a valid format that the system is programmed to recognise.
28-To remote devices Use this option to access the programming menus for 1-Door RASs (e.g. ATS1270) or four-door/four-lift DGPs (e.g. ATS1250/1260). These remote devices have additional menu’s that can be accessed via the control panel using this menu.
29-Computer connection Holds programming concerning connection to a computer running software package to program or control the ATS system (for example, ATS8100 or ATS8300). See also the “Service menu” in Advisor Master Manager Manual. When connecting the panel directly via the J18 (on-board RS232 port) or connecting the panel via the ATS1801 computer/printer interface, it is not necessary to set menus 29.1 to 29.4.
Up/download if any area armed No–Up/Download if any Area Armed *-Change 0-Skip Note: Option 29.1 must be set to Yes to use this option. Specifies if connecting via dialler to a remote computer is possible if any area is armed. If set to No and a remote connection is established, the panel will be disconnected when the user arms the system. Yes: A remote connection is possible if an area is armed. No: A remote connection is not possible if any area is armed. Press 0 to go directly to menu 29.
Use modem init string Yes-Use Modem Init. String Change 0 - Skip Note: Option 29.1 must be set to Yes to use this option. Yes: Up/download uses a compatible modem connected to the ATS1801. No: Up/download uses the built-in modem. Note: Refer to options (29.1, 29.2, 29.3, 29.4) only for incoming calls or callbacks. Events sent via modem depend on options 29.6, 29.7 and the computer phone number. Enter modem init string (*)-End Enter 32 char init modem string If Menu 29.
Computer telephone number *-Pause, Ph No: Cmp: Holds the telephone number to be dialled by a modem connected to the ATS1801 printer/computer interface to set up a remote up/download connection. Up/Download callback number *-Pause, Ph No: Cbk: Holds the telephone number to be called back to set up a remote up/download connection. Only used for up/download when dialling into the ATS system.
Connection attempts Connection Attempts 255, Failed 0 Attempts: Enter the number of attempts that can be made to set up a connection to a computer. The number of attempt only increases if a connection to a modem is established, but no correct security password has been received. The display also shows the number of failed attempts. Number of rings before answering Number Of Rings: 0 Rings: Enter the number of rings before answering an incoming call. If set to 0, incoming calls will not be answered at all.
• 4: Universal Interface Authorize computer connection YES-Authorize computer connection *-Change 0-Skip Specifies if the computer connection requires an authorization. Yes: The connection must be authorized by a user with an appropriate access level. No: Computer connection can be established at any time.
30-Printer Program the details for the printer. To obtain a printer output from the ATS control panel, a serial printer interface (ATS1802) or serial computer and printer interface (ATS1801) has to be fitted. Printer settings Enable real-time printer NO-Enable Real Time Printer *-Change 0-Skip Enables the printer output to print in real-time. Yes: Enable the printer port on the ATS control panel to print each event as it happens. "Print History" can still be used, if required (see manager guide).
Print data outside timezone NO–Print Data Outside Timezone *-Change 0-Skip Enables the printer to only operate outside the timezone, and not during it. Yes: The printer is only active if the timezone specified is invalid. No: The printer is only active if the timezone specified is valid. Press 0 to leave Printer menu. Notes • Any event that takes place when no data is dumped to the printer will be lost for the printer. Use “Print history” in the user menu to print these events.
31-Battery testing The battery test records the details of the automatic battery test procedure and enables manual battery test to be started. A battery disconnect check is also automatically performed. If a battery is disconnected for more then 10 minutes, a warning will be given. During the battery test, the control panel and/or DGPs, and all auxiliary driven devices, are powered from the battery. Devices are tested one at a time, making sure that not all devices switch to battery test at once.
Test during holidays YES–Test during holidays *-Change 0-Skip Yes: Battery test will always take place, even during holidays. No: Battery test will not take place during holidays. Select battery test Manual battery test No DGP Battery Testing In Progress Press ENTER This allows the ATS panel and DGP batteries to be tested manually. This test does not affect the automatic battery testing. If a DGP is tested, the DGP number will be displayed.
32-Custom LCD message This records 32 characters of customised text that is displayed on the top line of LCD arming station(s) in place of the normal display. Text is considered any configuration of up to 32 characters. They can include numbers, spaces or punctuation. Aritech, (*) - End Aritech Use the text option on the keypad to enter a text of up to 32 characters. Keys 1 to 9 have alphabetical characters printed above them.
33-Program next service Program the date on which the next routine service call is due and the message is to be displayed. The user will be prompted with a programmable text on the LCD arming stations to call the installer. Maintenance date Service Required at 0/0/0 Enter Day: Enter the next date on which the user will get a text displayed to signal that service is due.
34-Program system event flags Event flags are set when specified events occur in the system, such as a mains failure, a zone generating an alarm or an entry time running. The system event flags are triggered on system wide events, like mains failures or DGP’s going offline. For more information regarding event flags, see “Event Flags” on page 177.
Siren fail event flag Siren Fail No Event Flag Event Flag: This event flag is activated when a Siren Fail condition is detected on the ATS panel or a DGP. See also “Mains fail event flag” på side 151. DGP isolated event flag DGP Isolated No Event Flag Event Flag: This event flag is activated when a DGP has been isolated via User menu 16, Isolate/deisolate RAS/DGP. See also “Mains fail event flag” på side 151.
Report fail event flag Report Fail (FTC) No Event Flag Event Flag: This event flag is activated when the ATS control panel fails to report to the central station (also referred to as FTC). See also “Mains fail event flag” på side 151. Test mode event flag Testmode No Event Flag Event Flag: This event flag is activated when the ATS panel is in test mode. See also “Mains fail event flag” på side 151.
External siren test event flag Ext Siren Test No Event Flag Event Flag: This flag is active whenever a siren test is active. All armed pulse event flag All Armed No Event Flag Event Flag: If “NFA2P” option on page 83 is Yes, an event flag/output is provided with or without event recorder that will be active for 20 seconds, after fully armed condition is true.
System A (ACPO) System A (ACPO) No Event Flag Event Flag: Event flag associates an event flag with a system A event. A system A event flag is set whenever any ACPO area A flag is set. System B (ACPO) System B (ACPO) No Event Flag Event Flag: Event flag associates an event flag with a system B event. A system B event flag is set whenever any ACPO area B flag is set. User walk test User Walk Test No Event Flag Event Flag: Indicates that a walk test is running.
Zone test Zone test No Event Flag Event Flag: The Zone test even flag becomes active when a zone becomes active while being tested via “54.1-Test individual zone” menu described on page 172. Panel CPU restart Panel CPU Restart No Event Flag Event Flag: The Panel CPU Restart even flag becomes active after the panel CPU is restarted. It remains active until the CPU restart event is acknowledged.
35-Program macro logic Macro logic provides a powerful tool for activating zones or event flags under specific conditions. These conditions are macro inputs being triggered, logic equations combining the macro inputs and output conditions. Up to four macro inputs can be included in the logic equation. A macro input is an event flag or an output. Each macro input in the logic equation can be programmed as an AND or an OR function and can be programmed to invert the logic.
Configuring program Macro output function M 1 Disabled *-Change, 0-Exit The result of a macro, the macro output, will trigger an event flag or a zone. The macro output can have some timing functions. • • Disabled: This macro logic program is disabled. Non Timed: Follows the result of the logic equation only. If an event flag or output for this macro changes, the logic equation will be calculated again.
How to program Press one of these keypad buttons to: • ?, Enter: Enter and display new event flag or zone number. Enter the same number twice to invert the macro output. It will now trigger the event flag or output if the result of the equation is not true. An inverted macro output is recognised by the exclamation mark (!) preceding the number. • Menu: Select “Event Flag” or “Zone”. • Enter: Save the displayed details and move to the next display.
Notes • • Any unused macro inputs MUST be left as an OR. NAND and NOR functions can be made using the invert operator on the macro output or the macro inputs. NAND = INVERT (Macro Input 1) OR INVERT (Macro Input 2). NOR = INVERT (Macro Input 1) AND INVERT (Macro Input 2). 36 to 41-Reserved menus Reserved. Do not use.
42-Reporting class database Reporting of alarms depends on the settings in Reporting of zone in “1-Zone database” on page 7. This setting is a reporting class. There are 8 classes containing 6 conditions that can be selected for reporting. Select the reporting class Class Number Class No: Select the class to program.
Report to Central Station 1 YES-Report Alarm to CS1 *-Change 0-Skip Use this option to select whether this condition should be reported to Central Station 1. Report to Central Station 2 See “Report to Central Station 1” above. Report to Central Station 3 See “Report to Central Station 1” above. Report to Central Station 4 See “Report to Central Station 1” above. Enable Audio Listen in for this condition NO-Enable Audio Listen In *-Change 0-Skip Specify if audio listen in is allowed for this condition.
43-Test calls This menu holds programming regarding test calls to central stations. Test call settings Select central station number Select one of the 4 available central stations to set the test call for. Start test call Start First Test Call at: 00:00 Hours: Enter the time in hours and minutes, when a test call should be made. The time programmed is based on the real time clock. Test call interval Test Call Interval 00 Hours Hours: Specify the interval between test calls (in hours).
50-Channel mapping 1-Inputs 2-Areas 3-System Option: This menu relates to the 200 Baud FSK protocol used in France. Inputs Each sub menu is broken down into group menus. For example: Input group 1-16 Enter channel number 00 to 99 for each input (zone). The defaults are: • Inputs 1 to 72 > channels 1 to 72. • Inputs 73 to 256 > channel 73. Areas Each sub menu is broken down into group menus. For example, Area group 1 to 8 Enter channel number 00 to 99 for each area.
Event name Channel (default) Channel type 8 Summary RAS Offline 00-99 (91) A,R 9 Summary DGP Offline 00-99 (91) A,R 10 DGP Reset 00-99 (Dis) A 11 Summary DGP Mains Fail 00-99 (92) A,R 12 Summary DGP Low Batt 00-99 (93) A,R 13 Summary DGP Tamper 00-99 (94) A,R 14 Summary DGP Siren Tamper 00-99 (95) A,R 15 Summary Duress Code 00-99 (96) A,R 16 Summary Remote Log-In 00-99 (97) A,R 17 Summary Filmout 00-99 (Dis) A,R 18 Summary Program Mode Ent.
51-Engineering reset Engineer reset? *-Reset 0 - Skip This option allows the engineer to perform a reset without having to calculate the “ATS System Code”. When the installer presses the “*” button, the RAS displays “Done”.
52-Voice reporting BA Burglar Alarm – Voice Message 0 Msg. No. Reporting code no. Program the voice messages to be transmitted to the monitoring station, if voice protocol is programmed. See “9-Communication options” on page 94. Voice Messages can be programmed to report on the following alarm events. More than 1 event may have the same voice message programmed. Range is from 0 to 14. Table 11: Default table Reporting Code No.
Reporting code No. Reporting code 18 136 BA Outdoor 19 137 BA Tamper 20 138 BA Near Alarm 21 140 UA General Alarm 22 Low battery 23 Low battery restore 24 Mains restore 25 Technical restore Voice alarm message Note that event code 130 BA Burglary in the user table and code 1 – Burglar Alarm BAA in table 1 are the same event codes (130). If 130, BA in the user table is programmed with an alarm message, then this will have priority over event code 1 - BA Burglar alarm in table 1.
53-Program DVMRe Note: This is a legacy option. Current DVR/NVR firmware no longer supports RS232 commands. DVMRe alarm handling via the printer port In a conventional alarm-handling configuration the alarm devices are connected via the alarm PCB on the back of the DVMRe unit. Each alarm input corresponds with the camera input of the same function. Alarm input to camera assignments can be changed on 10 and 16-channel models via the DVMRe programming.
Yes: The ATS panel and DVMRe connection can be established and the next following control flags will be considered. No: Overrides all other control flags and there will be no communication at all between the ATS panel and the DVMRe. Note: If the DVMRe HLI is used, the ATS panel will no longer be able to communicate with a serial printer.
Enable history Search and Play YES-Enable History Search And Play *-Change 0-Skip The ATS panel will have a new menu set added which will be used to emulate a subset of the DVMR front panel controls. This feature will allow an ATS panel operator to view and search recorded footage via the RAS. This feature will be used when the DVMR front panel controls are not accessible and the panels RAS is located next to a spot monitor. In addition to this, a Search and Play feature will also be supported.
54-Test zone 1–Test individual zone 2–Walktest The Test zone menu allows you to test a single zone or perform a walk test with a range of zones. 54.1-Test individual zone Test individual zone Zone No: Enter zone number to display its status. Press Enter. The status of the selected zone is displayed. ACTIVE on 1, Main entrance Press Enter As long as the zone is not in normal state, the buzzer signals an abnormal status. If the zone returns to normal state, the display redraws, and the buzzer stops.
1, 2 0–All, Area The user may select all available areas by pressing the “0” key followed by the Enter key. Pressing Clear will cause the test to be aborted and the user will return to the installer menu. If aborted at this stage, no event (test started, failed, etc) will be logged and no test event flag will be set. Press Enter (without an area number) to start the test.
When the aux output pulsing is completed, the walk test will be exited automatically to the install menu. Test not completed Please wait At the end of the walk test, the walk test event flag will be deactivated. The test will cause the following events to be logged.
Test closing Please wait See also Event flags: • “Engineer walk test” on page 154 • “Engineer walk test reset” on page 154 55-Reserved Advisor Master Programming Guide 175
56-Siren calibration The siren calibration allows the panel to calculate the required impedance tresholds for the connected siren. The treshold values are stored in the panel and used to ensure reliable siren fault and tamper detection. Siren: 1-External, 2-Internal, 3-Strobe Siren: To start the calibration, choose the appropriate output first. This starts the appropriate output measurement. The calibration may cause one of the following messages.
Event Flags What are event flags? Event flags are memory locations in a microprocessor system that register the occurrence of certain events. Those events can be pre-defined or can be programmed. In other words: when certain events take place, event flags are triggered. Why does the ATS system use event flags? The ATS system uses event flags to provide the most flexible solution for activating outputs and manipulating macros. Using event flags gives both options using the same event flag.
Which event flags are predefined? There are 16 predefined event flags. These are: Event Name Description 1 Default External siren event flag (assigned in area database). External Siren If set to Yes in the zone database, activates when any External siren activates in any area. 2 Armed Alarm If set to Yes on the zone database, activates when an alarm is generated by the zone and all the areas assigned to the zone are armed. It is used to activate the system strobe.
• Menu “28-To remote devices” on page 138 (four-door DGP and four-lift DGP) and the appropriate programming guide concerning the appropriate remote controller. • Menu “34-Program system event flags” on page 151. • Menu “35-Program macro logic” on page 157.
Reporting Reporting in an ATS panel is divided in zone event reporting and system events. Zones use reporting classes and sub-classes that can be programmed per zone. In “42-Reporting class database” on page 161 a selection can be made regarding the conditions to report per class. Table 14 below shows an overview of the reported event per sub-class and condition. The column CID holds the reported Contact ID event. SIA holds the SIA event.
Class Type No 6 7 8 9 10 11 Advisor Master Programming Guide Sub-class Fire 112 Fire 113 Fire 114 Fire 115 Fire 116 Fire 117 Condition CID SIA Tamper Restore R383 TR Inhibit Restore R570 FU Alarm E112 FA Tamper E383 TA Inhibit E570 FB Alarm restore R112 FR Tamper Restore R383 TR Inhibit Restore R570 FU Alarm E113 FA Tamper E383 TA Inhibit E570 FB Alarm restore R113 FR Tamper Restore R383 TR Inhibit Restore R570 FU Alarm E114 FA Tamper E383 TA
Class Panic Type No Sub-class Condition CID SIA 12 Fire 118 Alarm E118 FA Tamper E383 TA Inhibit E570 FB Alarm restore R118 FR Tamper Restore R383 TR Inhibit Restore R570 FU Alarm E120 PA Tamper E383 TA Inhibit E570 PB Alarm restore R120 PR Tamper Restore R383 TR Inhibit Restore R570 PU Alarm E121 HA Tamper E383 TA Inhibit E570 HB Alarm restore R121 HR Tamper Restore R383 TR Inhibit Restore R570 HU Alarm E122 PA Tamper E383 TA Inhibit E57
Class Type No 19 20 21 22 23 24 Advisor Master Programming Guide Sub-class Burglar 132 Burglar 133 Burglar 134 Burglar 135 Burglar 136 Burglar 137 Condition CID SIA Inhibit E570 BB Alarm restore R131 BR Tamper Restore R383 TR Inhibit Restore R570 BU Alarm E132 BA Tamper E383 TA Inhibit E570 BB Alarm restore R132 BR Tamper Restore R383 TR Inhibit Restore R570 BU Alarm E133 BA Tamper E383 TA Inhibit E570 BB Alarm restore R133 BR Tamper Restore R383
Class Type No 25 General alarms 26 27 28 29 30 184 Sub-class Burglar 138 General 140 General 141 General 142 General 143 General 144 Condition CID SIA Tamper Restore R383 TR Inhibit Restore R570 BU Alarm E138 BA Tamper E383 TA Inhibit E570 BB Alarm restore R138 BR Tamper Restore R383 TR Inhibit Restore R570 BU Alarm E140 UA Tamper E383 TA Inhibit E570 UB Alarm restore R140 UR Tamper Restore R383 TR Inhibit Restore R570 UU Alarm E141 GA Tamper
Class Type No Sub-class Condition CID SIA 31 General 145 Alarm E145 BA Tamper E383 TA Inhibit E570 BB Alarm restore R145 BR Tamper Restore R383 TR Inhibit Restore R570 BU Alarm E150 QA Tamper E383 TA Inhibit E570 QB Alarm restore R150 QR Tamper Restore R383 TR Inhibit Restore R570 QU Alarm E151 QA Tamper E383 TA Inhibit E570 QB Alarm restore R151 QR Tamper Restore R383 TR Inhibit Restore R570 QU Alarm E152 QA Tamper E383 TA Inhibit E570 Q
Class Type No 38 39 40 41 42 Fire supervisory 186 43 Sub-class 24 Hour 156 24 Hour 157 24 Hour 158 24 Hour 159 24 Hour 161 Fire Supervisory 200 Condition CID SIA Inhibit E570 QB Alarm restore R155 QR Tamper Restore R383 TR Inhibit Restore R570 QU Alarm E156 QA Tamper E383 TA Inhibit E570 QB Alarm restore R156 QR Tamper Restore R383 TR Inhibit Restore R570 QU Alarm E157 QA Tamper E383 TA Inhibit E570 QB Alarm restore R157 QR Tamper Restore R383
Class Type No 44 45 46 47 48 Advisor Master Programming Guide Sub-class Fire Supervisory 201 Fire Supervisory 202 Fire Supervisory 203 Fire Supervisory 204 Fire Supervisory 205 Condition CID SIA Alarm restore R200 FR Tamper Restore R383 FJ Inhibit Restore R570 FU Alarm E201 FA Tamper E383 FT Inhibit E570 FB Alarm restore R201 FR Tamper Restore R383 FJ Inhibit Restore R570 FU Alarm E202 FA Tamper E383 FT Inhibit E570 FB Alarm restore R202 FR Tamper Rest
Class Type No Sub-class Condition CID SIA 49 Fire Supervisory 206 Alarm E206 FA Tamper E383 FT Inhibit E570 FB Alarm restore R206 FR Tamper Restore R383 FJ Inhibit Restore R570 FU The list of system events depends on the selection of the protocol type being large or small. The small protocols only report summarised events. The large format reports as much as possible (see Table 15 and Table 16).
Description Contact ID SIA Event Area Pt/User Event Pt/User Area Out of Timezone E608 00 C 012 OK 000 Area Within Timezone R608 00 C 012 – – Film Out E150 00 C 011 – – Film Out Restore R150 00 C 011 – – Emergency Alarm E102 00 C 009 QA 000 Auto Test Call E602 00 C 016 RP 000 Service Requested E411 00 C 013 YX 000 Line Fault Monitor Fail E351 00 C 014 LT connection type [1] Line Fault Monitor Restored R351 00 C 014 LR connection type [1] Direct Co
Table 16: Overview of large reporting format Description Contact ID SIA Event Area Pt/User Event Pt/User Duress Code Entered E120 00 C 001–064 HA C 401–464 Duress Code Restored R120 00 C 001–064 HR C 401–464 Area Armed C402 01–16 U 001–999 CL U 001–999 Area Disarmed O402 01–16 U 001–999 OP U 001–999 RAS Offline E143 00 C 001–064 ET C 401–464 RAS Online R143 00 C 001–064 ER C 401–464 DGP Offline E143 00 C 065–079 ET C 301–316 DGP Online R143 00 C 065–079
Description Contact ID SIA Event Area Pt/User Event Pt/User RAS Polled R330 00 C 001–064 – – RAS Isolated E570 00 C 001–064 UB C 401–464 RAS De-Isolated R570 00 C 001–064 UU C 401–464 Area Out of Timezone E608 00 C 160–175 OK 000 Area Within Timezone R608 00 C 160–175 – – Film Low E150 00 129 – – Film Out E150 00 130 – – Film Out Restore R150 00 130 – – Restart Exit timer E150 00 131 – Emergency Alarm E102 00 143 QA 000 Camera Pop Enabled R
Description Contact ID SIA Event Area Pt/User Event Pt/User Remote/Direct Disconnection R146 00 147 RS 000 Program Mode Entered E150 00 146 LB 000 Program Mode Exited R150 00 146 LS 000 Emergency Alarm (Dead Man’s Alarm) R628 00 C 009 Engineering Reset Ok IR 1-999 (user) Engineering Reset Required IA 1st Area Engineer Walk Test - Started TS 1-999 (user) Engineer Walk Test - Failed WF 1-999 (user) Engineer Walk Test - Completed WP 1-999 (user) Film Low Restored R
Troubleshooting ATS control panel - model ATS1000/2000/3000/4000/4500 Condition Possible cause The master LCD arming station (RAS address 1) has all LEDs flashing and displays the “System Fault” message. The system databus line may be connected incorrectly. The panel is not communicating with arming stations and/or data gathering panels. The system databus line may be connected incorrectly. The address links on the RAS may be incorrectly set.
LCD arming stations - models ATS110x, ATS111x Condition Possible cause All the LEDs on the arming station are flashing. The dipswitches may be incorrectly set (the address set on the arming station may be incorrect and therefore polling to the arming station is not being acknowledged). The system databus line may be connected incorrectly. The arming station is not being polled (it may not have been included in arming stations to be polled when programming arming stations).
Data gathering panels - models ATS120X(E)(N), ATS121X(L)(E), ATS1220 Condition Possible cause The "Tx" LED on the data gathering panel is not flashing. The dipswitches may be incorrectly set (the address recorded on the DGP may be incorrect and therefore polling to the DGP is not being acknowledged). The system databus cable may be connected incorrectly. The data gathering panel is not programmed to be polled. "Tx" and "Rx" LED’s are not operating. No power or low power.
Condition Possible cause The siren output (with 8 Ohm siren speaker connected) does not operate when it is meant to. The address setting for this data gathering panel is 15. The siren can not be addressed as the highest output number is 255 where 256 would be required. The 16th (last) relay number associated with the DGP address has not been mapped to a siren event flag number.
Condition Possible cause 16-way open collector card (ATS1820/1821) will not function: When connected to the Challenger Panel. The “No. of output controllers” on page 71 has not been set. Note: Number of output controllers = 2 for each 16-way open collector. When connected to a DGP. DIP switch B has not been set to ON (ATS1201, ATS1210, ATS1220). For ATS1201E, ATS1203(E), ATS1204(E)(N), ATS121X(L)E the DGP Settings > Static outputs option in the DGP programming menu is not set to Clocked outputs.
Options required by EN 50131 compliance The following options and values are mandatory for EN 50131-1 Grade 3 regulations.
• • • • • • • • • • • • “Indicate inhibited zones” on page 85: Yes “Eng Rst on ACPO zone B tamper” on page 85: No “Eng Rst on ACPO system B tamper” on page 86: No “Security grade” on page 86: 3 (Med to High Risk) “Ignore AC mains fault when arming” on page 86: No “Latch mains/battery/line faults” on page 86: Yes “Enable PA siren on FTC” on page 87: No “Latch AWDGP jam and supervision” on page 87: No “Prevent arming on faults” on page 88: Yes “Authorize computer connection” on page 144: Yes “Battery test fr
RAS options required by EN 50131 compliance Each arming scenario described below meets EN 50131 requirements.
Additional functions The following settings are default. Modifying these settings has no influence on EN 50131 compliance. • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • “Film low level” on page 70: 800 “Film out level” on page 71: 1100 “No.
Additional zone types The following zone types are additional and have no influence on EN 50131 compliance. 7. Camera Suspicion Zone 44. Firedoor with AlmGrp Restr. 15. Firedoor 45. (Event Flag/Arm.Alm) Restr. 20. Zone to Event Flag 24Hr 46. Disarm Alm/Arm Gen. Alm 21. Firedoor With User Code 47. Dis. Alm Susp/Arm Gen. Alm 23. Camera 1 Count 48. Camera 1 Film Out 24. Camera 2 Count 49. Camera 2 Film Out 25. Camera 3 Count 50. Camera 3 Film Out 26. Camera 4 Count 51. Camera 4 Film Out 27.
EN 50131 Grade 3 certified components The ATS Classic EN Grade 3 system exists out the following components.
I/O expanders Panel and DGP can support up to 3 I/O devices depending on the type. ATS1202 Plug in 8-zone expander ATS1810 4 way relay board ATS1811 8 way relay board ATS1820 16 way open collector board ATS1821 8 way open collector board Reporting devices Panel can support 1 GSM device connected onto MI bus.
Glossary Access control The control of entry to, or exit from, a security area. Active See Normal/Active/Tamper/Inhibited Alarm The state of a security system when a device connected to a zone is activated and the condition of the area is such that activation should be signalled. E.g. a door lock is broken, causing a siren to sound. Alarm control The control over alarm functions. Alarm group Alarm groups define the options available to users, arming stations or door reader to allow alarm control.
Dialler An electronic device that allows the ATS system to transmit alarms and other events to a central station. Can also be used to perform up/download. Disarmed The condition of an area when it is occupied and when the security system has been set so that normal activity does not set off an alarm. Door contact A magnetic contact used to detect if a door or window is opened. Door control The control over door functions.
Macro input An event flag or an output that is used in a logic equation. Each macro input is an event flag or output. Macro logic program A set of rules that is created by macro inputs, logic equations and macro outputs that is used to trigger event flags or zones. Macro output A macro output holds the result of a logic equation. The macro output can have a timing element. Macro outputs trigger event flags or zones. Normal / Active / Tamper / Inhibited / Isolated Describes the condition of a zone.
Shunt A procedure that automatically inhibits a zone from generating an alarm when it is activated. E.g. shunts stop a door generating an alarm when opened for a short time. Tamper A situation where a zone, an arming station, control panel, DGP or associated wiring are tampered with, or accidentally damaged. The ATS tamper facility activates a signal when tamper occurs. Tamper alarms from zones are called zone tampers. Timezone A program setting which identifies specific time periods on specific days.
Index 2 200 baud reverse area armed/disarmed, 96 A abort time, 68 ACPO, 83 active zones arming with active zones, 55 Advanced Wireless DGP, 87 alarm control alarm group restrictions, 115 arm with active zones, 55 auto arm/disarm, 123 cards always arm/disarm, 43 cards auto disarm, 43 combining access control and alarm control, 72 common areas, 127 entry/exit, 7 entry/exit buzzers, 44 entry/exit time, 28, 29 forced arming, 55 latching system alarms, 74 lockout RAS on wrong codes, 44 no alarm group restrictio
zone database, 20 alarm-A event flag, 32 alarm-B event flag, 32 alarms A to B alarm delay (ACPO), 66 activate siren and strobe on system alarm, 74 auto reset, 93 auto reset time, 93 disable flashing area LEDs, 76 display alarms immediately, 76 latching system alarms, 74 program local alarm reminder time, 64 reset latching system alarms, 53 reset without using PIN, 43 silent alarms until fail to report, 77 alert indicator event flag, 35 anti-mask detector, 27 anti-mask reset event flag, 31 anti-mask/fault ev
select the class, 161 select the condition, 161 specify central station for condition to report to, 162 code tamper, 44, 46 event flag, 46 common area programming, 20 zones, 20 communication options, 94 allow audio listen in, 99 dual reporting, 99 enable the line monitor, 95 MSN number, 94 PABX number, 94 program account codes, 98 program central station phone nbrs, 98 report inhibits, 99 select reporting format for central station, 97 select tone or pulse dialling, 94 SIA reporting with 3 digit extensions,
enable ISDN line fault monitor, 95 enable log limitations, 85 enable soak test, 19 end-of-line resistors, 73 engineer entry protect, 80 engineer reset, 85, 86, 88, 166 system alarms, 79 system tampers, 80 zone alarm, 19 zone tamper, 18 engineer reset on ACPO zone B alarm, 83 engineer walk test, 26 engineering reset, 80 entry/exit buzzer on RAS, 44 delay reporting, 66 program time, 28, 29 shunted entry/exit zone, 133 errors between ATS and units connected number detected, 135 event flags 24 hr alarm 8, 24 ac
ISDN point to point, 95 timezone, 111 zone, 7 J jamming, 92 K keybox time, 34 keypad duress activating with a code, 53 L latch jam and supervision, 87 latch mains/battery/line faults, 86 latched reset event flag, 32 LCD rotation delay, 72 text rotation speed, 72 LED test, 110 local alarm, 91 lockout, 44, 46, 47, 88 lockout time, 68 low battery event flag, 151 M macros. See program macro logic mains fail time before reporting to central station, 66 mains fault override, 89 maintenance.
specify if the macro output triggers an event flag or a zone, 158 time period for macro output, 158 use macro inputs to set up logic equations, 159 what will the result of the logic equation do, 158 program next service, 150 enter next service date, 150 text displayed on service date, 150 program text, 102 programming how to program, 5 programming four-door/four-lift DGP or onedoor RAS, 138 programming menu accessing, 4 explanation of the LCD display, 5 master engineer code, 4 moving around between the menu
siren, 92 activate on system alarm, 74 activated when panel fails to report to central station, 77 calibration, 176 delay, 66 fault, 176 fault override, 90 testing during arm test, 75 siren delay set to, 66 siren fault override, 90 siren type, 81 site code.
testing battery, 148 LED's, 110 testing event flag activation time, 65 view poll errors, 135 text words, 102 alarm group restrictions, 117 area name, 28 how to program, 102 keypad layout for entering text, 103 list of pre-programmed words in the library, 104 program zone event text, 72 zone name, 17 timed lockout by wrong badges, 47 timers, 62 A to B alarm delay (ACPO), 66 accuracy of timers, 62 camera suspicion time, 64 delay time for reporting entry/exit alarms, 66 delayed disarmed alarm time, 64 disarmed
test procedure for zones, 20 trigger chime/camera event flag, 25 trigger zone event flag, 25 using audio listen in, 18 zone name, 17 zone number, 7 zone type, 7 zone number description, 7 zone shunts, 130 cancel door event flag, 132 door open command starts shunt, 131 door shunted when disarmed, 132 door shunted while armed, 132 entry/exit shunting, 133 program the output to start the shunting, 130 program the time to shunt, 131 program the warning time, 131 Advisor Master Programming Guide program zones
Programming map Simple/Advanced Menu *-Advanced Legend: Simple menu Advanced menu 1-Zone database Zone number Zone type Zone name Reporting of zone Report alarm to CS 1 Report alarm to CS 2 Report alarm to CS 3 Report alarm to CS 4 Enable audio listen in Engineer Reset on Alarm Engineer reset for tampers Disable inhibit Enable soak test Area / alarm group assignment Test option Zone event flag Internal siren event flag External siren event flag Keypad buzzer Make all events 24 hour 2-Area database Select
3-RAS database RAS to be polled Select RAS to program Area alarm group Menu alarm group Door event flag Output controller assigned LCD arming station Toggle Area status Enter key opens door only Door event flag on alarm codes Display shunted zone on LCD Arm/disarm using one key Cards auto disarm Card always arms/disarms Reset from RAS without code AG restriction disarm only Entry/exit buzzers Timed lockout by wrong codes Cards arm after 3 badges Disable status LED's 3 LED RAS Card & PIN (disarm only) RAS t
6-Timers AG restriction 1 disarmed time AG restriction 2 disarmed time AG restriction 3 disarmed time AG restriction 4 disarmed time AG restriction 5 disarmed time AG restriction 6 disarmed time AG restriction 7 disarmed time AG restriction 8 disarmed time Disarm test time Arm test time Warning time Disarmed alarm delay time Suspicion time Service time available Local alarm reminder time Individual zone test time Doors unlock time Testing event flag time External siren set to Internal siren set to Siren del
Ignore battery fault when arming User can do engineering reset Engineer entry protect Send arming after exit User offset End of line resistor code Duress mode Siren Type Override tamper Override interconnection fault Override RAS fault Override DGP fault Enable buzzer on alerts Internal siren on exit fault RF jamming set sirens Number of attempts for PIN of the day 8-Auto reset Auto reset time Reset alarm group 9-Communication options PABX number MSN number Dial tone detection Select tone dialling Enable
16-Event to output Output number Event flag number Timezone to control output Active or inactive during timezone Invert output 17-Auto arm/disarm Auto arm/disarm program Timezone to arm/disarm Alarm group to auto arm/disarm 18-Vaults 19-Area linking Linking areas 20-System codes System code 1 Card offset 1 System code 2 Card offset 2 21-Zone shunts Shunt timer number Zone number to shunt Output number to start shunt Shunt time Shunt warning time Shunt event flag Shunt warning event flag Door open co
30-Printer Enable real-time printer Print alarm events Print access control events Print data outside timezone Print during timezone Printer options 31-Battery testing Select battery test program Battery test frequency Start battery test Battery test period Test during holidays Select battery test Manual battery test Battery test report Select DGP for battery test 32-Custom LCD message 33-Program next service Maintenance date Maintenance message 34-Program system event flags Mains fail event flag Low
43-Test calls Select central station number Start test call Test call interval Extend test call 44 to 49-Reserved menus 50-Channel mapping Inputs Input group 1-16 Areas Area group 1 to 8 System System group 1 to 10 51-Engineering reset 52-Voice reporting 53-Program DVMRe DVMRe alarm input map Enable DVMRe interface Enable time update Enable event text insertion Enable alarm feedback Enable history Search and Play 54-Test zone 54.1-Test individual zone 54.