Installation guide

6 Advisor Master Programming Guide
Some programming menus need certain values to be entered, while others are
used to select Yes/No. Programming lines containing Yes/No options often also
allow the 0 key to be pressed. Use this key to skip a number of options. The
display will indicate if the 0 key can be used on the second line.
Programming menus like Poll RAS, Poll DGP or Entry time show the status
of the current values. To update the values, press Menu.
Where programming of an option does not follow this procedure, the (additional)
keys available are described in the How to program section of the option.
First startup
During the first startup of the panel, after the installer enters the programming
menu, he is prompted to apply EN 50131 default settings.
Select EN50131 Grade
Grade:
Enter a grade number and press Enter. The following options are available:
2: Apply Grade 2 default settings.
3: Apply Grade 3 default settings. See also Options required by EN 50131
complianceon page 198.
Siren calibration
For EN 50131 regulation compliance the system must provide monitoring for
sirens and strobes. This monitoring is only possible after siren calibration.
The installer must perform siren calibration manually from keypad using
programming menu 56-Siren calibrationon page 176.
Caution: Siren calibration is not performed automatically when applying
EN 50131 default settings using menu 14 or during the first startup.