Installation guide
132 Advisor Master Programming Guide
No: The condition of the zone, normal to active, triggers the timer.
Press 0 to end programming this shunt timer and to select a new shunt timer.
Notes
• If this option is set to Yes and the keypad or shunt relay starts the shunt timer,
the timer resets if the zone does not switch to normal state within:
- 3 seconds if the shunt time is programmed for 1 to 127 s.
- 3 minutes if the shunt timer is programmed for 1 to 127 min.
• If this option is set to Yes, “Entry/exit shunting” on page 133 must be set to
No.
Shunt zone when disarmed
NO-Shunt Zone When Disarmed
*-Change 0-Skip
Specify if the zone will be shunted when one or more of the areas assigned to
the shunted zone are disarmed.
Press 0 to end programming this shunt timer and to select a new shunt timer.
Note: Set either “Shunt zone when disarmed” or “Shunt zone when armed” to
Yes. Otherwise the shunt procedure will not operate.
Shunt zone when armed
NO-Shunt Zone When Armed
*-Change 0-Skip
It records whether the door shunt procedure operates when all the areas
assigned to the shunted zone are secure.
Press 0 to end programming this shunt timer and to select a new shunt timer.
Note: Set either “Shunt zone when disarmed” or “Shunt zone when armed” to
Yes. Otherwise the shunt procedure will not operate.
Cancel door event flag
NO-Cancel Door Event Flag
*-Change 0-Skip
Define that closing the zone cancels the shunt time.
Yes: As soon as the shunted zone switches to normal state, the door unlock
event and the shunt timer are cancelled.
No: The door unlock event and the shunt timer are not cancelled if the zone
switches to normal state.
Press 0 to end programming this shunt timer and to select a new shunt timer.