23-Poll errors
Use this menu to get an indication on how many errors have been detected in
communications between the ATS control panel and devices connected to it.
Select device type
1-RAS, 2-DGP, 3-Clear All Counters
0-Exit, Menu:
Select the type of devices to view the number of poll errors on. Optionally the
error counters can be reset. The available options are:
1 - RAS: View poll errors for remote arming stations
2 - DGP: View poll errors for DGP’s or the dialler
3 - Reset: Reset all poll error counters.
After selecting the device type, a list of all devices is shown. Select a particular
device by entering its device number. The device numbers are as follows:
RAS 1 to 16: Arming stations 1 to 16
DGP 0: Panel communications to central station
DGP 1 to 15: Data gathering panels 1 to 15
RAS 1, Poll Error Count Is 0
0-Exit, RAS No:
How to read poll errors for devices
Press one of these keypad buttons to:
?, Enter: Select the device to view the poll errors.
Enter: Leave the list and return to the device type selection.
Note: Set the error count for all units to zero when the system is error free after
installation. If you do not do this, errors that occurred during installation could
distort any error count. The maximum error count that can be recorded is 255.