Installation guide

Advisor Master Programming Guide 147
31-Battery testing
The battery test records the details of the automatic battery test procedure and
enables manual battery test to be started. A battery disconnect check is also
automatically performed. If a battery is disconnected for more then 10 minutes, a
warning will be given.
During the battery test, the control panel and/or DGPs, and all auxiliary driven
devices, are powered from the battery. Devices are tested one at a time, making
sure that not all devices switch to battery test at once.
Select battery test program
Battery Testing: 1-Program, 2-Test
Option:
Select 1 to program the battery test options or 2 to perform a manual battery test.
Programming battery test
Battery test frequency
Batt Test Frequency - Disabled
*-Change, 0-Skip
Specify how often the automatic battery test should be performed.
Use Menu to select one of the available options:
Disabled
Every working day
Every Monday
First Monday of month
Every day
Press 0 to move to Start battery test.
Start battery test
Start Battery Test 00:00
Hours:
Program the time of day, in hours and minutes, when the battery test will start.
Battery test period
Run Battery Test For 000
Minutes:
Program the period, in minutes (with a minimum of 2), that the automatic battery
test will run. If a battery test on any device fails, that device immediately restores
AC power.