Installation guide

10 Advisor Master Programming Guide
Zone type
Description
15.
Firedoor
Generates a local alarm when the area is disarmed.
Automatically activates an audible alert on arming stations
assigned to the same areas (regardless of the event flag
programming). The only event flag activated (as specified in
the zone database) is the zone event flag.
This local alarm can be reset by entering "Enter, Enter, 0,
Enter" or "user code, Off, area, Enter" on the arming station to
stop the audible alert and cancel the event.
If the zone remains activated, it generates a new local alarm
after the programmed local alarm reminder time.
Generates an alarm when the area is armed.
Example: Firedoors or emergency doors.
You need to program the local alarm reminder time. See 6-
Timers on page 62 for more information.
16.
24Hr Local Mains Fail
It is not used in standard commercial versions of the ATS
control panel. It generates a local alarm, and activates an
audible alert.
17.
Do not use
18.
Report Fail
Generates a local alarm. Activates an audible alert on arming
stations assigned to the same areas.
Activates fault LED on all arming stations and generates LCD
fault display message.
19.
Report Fail LED
Activates fault LED on all arming stations and generates LCD
fault display message.
20.
Zone to Event Flag 24Hr
When activated, opened or shorted, it only activates the zone
event flag.
Example: Doorbell.
21.
Firedoor With User
Code
Generates a local alarm when the area is disarmed but does
not report it to the central station, no audible alert on arming
stations.
This alarm can only be acknowledged by entering "user code,
Off, area, Enter" on the arming station.
Generates an alarm when the area is armed.
Example: Fire door or emergency door.
22.
Dis. Delay Reset/Arm
Alm
Generates an alarm when the area is disarmed but does not
report to a central station until the delayed alarm timer has
expired or a second delayed alarm is activated.
If the zone closes to normal state during the delayed time, it
resets automatically.
Generates an alarm when the area is armed.
Example: Hold-up button.
You need to program the delayed alarm time. See 6-Timers
on page 62 for more information.
23.
Camera 1 Count
Used to increment the film counter for camera 1 by
connecting a normally open contact across the zone. The
counter increments if the zone switches from open to short.
Can only be used with zones on the ATS control panel.