Installation guide

158 Advisor Master Programming Guide
Configuring program
Macro output function
M 1 Disabled
*-Change, 0-Exit
The result of a macro, the macro output, will trigger an event flag or a zone. The
macro output can have some timing functions.
Disabled: This macro logic program is disabled.
Non Timed: Follows the result of the logic equation only. If an event flag or
output for this macro changes, the logic equation will be calculated again.
On Pulse: Activates for the programmed time or the active period of the logic
result, whichever is the shortest.
On Timed: Activates for the programmed time regardless of the macro output
changing.
On Delay: Activates after the programmed time period unless the result of the
logic equation is no longer valid.
Off Delay: Follows the result of the logic equation, but remains active for the
time programmed after the result of the logic equation is no longer active
Latched: Activates on any of the first three macro inputs in the logic equation
and is only reset by the fourth macro input. Any programmed AND / OR
function is not used.
How to program
Press one of these keypad buttons to:
Menu: Display a new output function.
0: Leave the 35-Program macro logic menu.
Enter: Save the displayed function and move to the next display.
Time
M1 Times for 0 Seconds
Time:
The time period (2 to 255 seconds) that is used when any of the timed macro
output functions is selected (pulse, on timed, on delay or off delay). Use any
value of 2 or higher.
Macro output triggers EF or zone
M 1 Activates Event Flag 0
*-Change, No:
Specify if the macro output should trigger an event flag or a zone and which
event flag or zone.
The macro output is triggered as a result of the logic equation on the macro
inputs. The output will behave as programmed in the Macro output function.