Installation guide
172 Advisor Master Programming Guide
54-Test zone
1–Test individual zone
2–Walktest
The Test zone menu allows you to test a single zone or perform a walk test with
a range of zones.
54.1-Test individual zone
Test individual zone
Zone No:
Enter zone number to display its status. Press Enter.
The status of the selected zone is displayed.
ACTIVE on 1, Main entrance
Press Enter
As long as the zone is not in normal state, the buzzer signals an abnormal status.
If the zone returns to normal state, the display redraws, and the buzzer stops. If
an input was inhibited prior to the test, it is uninhibited for the duration of the test.
Press Enter to exit this menu.
54.2-Walktest
Introduction
The engineer walk test allows testing of all zones that are configured for an
engineering walk test in selected areas. These areas are tested by a
technician/engineer. This test is independent to the zone configured test type and
is only run manually from a new installer menu item.
Zones are configured to be included in the engineer walk test (See “Engineer
walk test” on page 26). The default is Yes (include in engineer walk test).
A technician/engineer starts the engineer walk test from menu 54.2. The areas
do not need to be armed/disarmed before a new test is started. The test can be
initiated whenever needed.
Procedure
When starting the engineer walk test the user will be prompted to select area/s to
test by the display shown below. Initially no areas are selected and the top line of
the display would be blank.
The user selects an area by entering the area number followed by the Enter key.
Areas selected are displayed as shown on the display below. Areas will be
masked so that only areas that are available for the test are those that both the
user and RAS have access to. If a user enters an area that is not available the
RAS buzzer will sound a warning (several short beeps) and the area will not be
displayed in the selected list.