Installation guide

194 Advisor Master Programming Guide
LCD arming stations - models ATS110x, ATS111x
Condition
Possible cause
All the LEDs on the arming
station are flashing.
The dipswitches may be incorrectly set (the address set on the
arming station may be incorrect and therefore polling to the
arming station is not being acknowledged).
The system databus line may be connected incorrectly.
The arming station is not being polled (it may not have been
included in arming stations to be polled when programming
arming stations).
LEDs do not appear to be
indicating the correct condition.
The arming station type may have been defined incorrectly:
LCD arming station must be set to Yes.
The arming station appears to
be going off-line and on-line
(indicated by the "RAS Fail"
message on the LCD).
The termination may be incorrect. See Advisor Master
Installation Guide, “Cabling.
An error is indicated when a
code is entered on the keypad
(seven beeps).
An invalid PIN may have been used.
The arming station may not have been programmed with an
alarm group.
The alarm group of the PIN may not permit access at this
arming station.
4 LED arming station - models ATS1150 and ATS1155
Condition
Possible cause
All the LEDs on the arming
station are flashing.
The dipswitches may be incorrectly set (the address set on the
arming station may be incorrect and therefore polling to the
arming station is not being acknowledged).
The system databus line may be connected incorrectly.
The arming station is not being polled (it may not have been
included in arming stations to be polled when programming
arming stations).
LEDs do not appear to be
indicating the correct condition.
The arming station type may have been defined incorrectly as
LCD arming station. This option must be set to No.
The arming station appears to
be going off-line and on-line
(indicated by the "RAS Fail"
message on a LCD arming
station).
The termination may be incorrect. See Advisor Master
Installation Guide, Cabling.
The arming station appears to
lockup when the relay, which it
controls via the OUT terminal,
activates.
The relay probably does not have a reverse diode across it to
protect against back EMF.
An error is indicated when a
code is entered on the keypad
(seven beeps).
An invalid PIN may have been used.
The arming station may not have been programmed with an
alarm group.
The alarm group of the PIN may not permit access at this
arming station.