Installation guide
196 Advisor Master Programming Guide
Condition
Possible cause
The siren output (with 8 Ohm
siren speaker connected) does
not operate when it is meant to.
The address setting for this data gathering panel is 15. The
siren can not be addressed as the highest output number is
255 where 256 would be required.
The 16th (last) relay number associated with the DGP address
has not been mapped to a siren event flag number. See:
• “16-Event to output” on page 121
• “2-Area database” on page 28
• Zones and outputs allocated to each DGP (installation
guide)
Serial printer interface - model ATS1802
Condition
Possible cause
No printout
The printer output or the selected events may not have been enabled,
or the timezone selected for printing may not be valid in menu “30-
Printer” on page 145.
The baud rate and parity options selected in menu “30-Printer” on page
145 may not match the options set in the printer.
The cable from ATS1802 port B to the printer may be wired incorrectly.
Check it against the installation guide.
The wrong type of cable may have been used or the cable may have
been run too far. Four or six core RS232 shielded data cable must be
used and should not be longer than 15 metres.
The printer is not providing a Data Terminal Ready signal (+8 to +11V
DC) to the CTS input on the ATS1802 Port B (check with the meter and
check the connection between printer serial connector, pin 20 "DTR"
and ATS1802 port B, "CTS").
The serial printer may not be set up correctly.
Print-out is garbled or
misaligned etc.
The Baud rate and parity options selected in menu “30-Printer” on page
145 may not match the options set in the printer.
The printer is not compatible with the Epson printer codes for
condensed and enhanced printing (SI, DC2, S0 and DC4).
Output devices - models ATS1810, ATS1811, ATS1820,
ATS1821
Condition
Possible cause
The 8-way relay card (ATS1811)
will not function:
When connected to the ATS panel.
The “No. of output controllers” on page 71 has not been
set.
Note: Number of output controllers = 1 for each 8-way
relay card.
When connected to a DGP.
DIP switch B has not been set to ON (ATS1201, ATS1210,
ATS1220).
For ATS1201E, ATS1203(E), ATS1204(E)(N),
ATS121X(L)E the DGP Settings > Static outputs option in
the DGP programming menu is not set to Clocked outputs.