Condition
Possible cause
16-way open collector card
(ATS1820/1821) will not function:
When connected to the Challenger
Panel.
The No. of output controllerson page 71 has not been
set.
Note: Number of output controllers = 2 for each 16-way
open collector.
When connected to a DGP.
DIP switch B has not been set to ON (ATS1201, ATS1210,
ATS1220).
For ATS1201E, ATS1203(E), ATS1204(E)(N),
ATS121X(L)E the DGP Settings > Static outputs option in
the DGP programming menu is not set to Clocked outputs.
4-way relay card(s)(ATS1810) will
not function:
When connected to the ATS panel.
The “No. of output controllerson page 71 has not been set
to 0.
When connected to a DGP.
DIP switch B has not been set to OFF (ATS1201,
ATS1210, ATS1220).
For ATS1201E, ATS1203(E), ATS1204(E)(N),
ATS121X(L)E the DGP Settings > Static outputs option in
the DGP programming menu is set to Clocked outputs.
Relays will not function after
being enabled as above
The relay has not been mapped to an event flag or the
relay/output number has been calculated incorrectly and
therefore is not programmed as the correct output number.
The output is being held inactive during a timezone.
The cable has been connected incorrectly.
See:
Event to output Numbering, Zones/ DGPs/ Relays.
Hardware installation guides supplied with the
relay/output cards.