Options required by EN 50131 compliance
The following options and values are mandatory for EN 50131-1 Grade 3
regulations.
• “Entry time” on page 29: ≤ 45 s
• “Reset from RAS without code” on page 43: No
• “Timed lockout by wrong codes” on page 44: Yes
• “Timed lockout by wrong badges” on page 47: Yes
• “External siren set to” on page 65: 90 s to 15 min
• “Internal siren set to” on page 65: 90 s to 15 min
• “Siren delay set to” on page 66: ≤ 10 min
• “Mains fail delay time” on page 66: 60 s
• “Delay reporting alarms for” on page 66: ≤ 10 s
• “Screen saver timeout time” on page 66: ≤ 60 s
• “RAS card & PIN timeout” on page 67: 30 s
• “Abort time (sec)” on page 68: 30 s
• “RAS lockout time” on page 68: ≥ 90 s
• “Areas selected for total disarm” on page 70: 0
• “Test mode” on page 71: 0, No test
• “Dual zone” on page 73: Yes
• “Auto uninhibit on disarm” on page 73: Yes
• “System alarms set siren and strobe” on page 74: Yes
• “Latching system alarms” on page 74: Yes
• “Disable code from displaying” on page 76: Yes
• “Sirens only after FTC” on page 77: No
• “Inhibit zone tamper” on page 78: Yes
• “Report multiple alarms” on page 79: Yes
• “Report multiple restores” on page 79: No
• “Ignore battery fault when arming” on page 80: No
• “User can do engineering reset” on page 80: No
• “Engineer entry protect” on page 80: No
• “Send arming after exit” on page 80: Yes
• “End of line resistor code” on page 81: 1, 4k7
• Use minimum 6 digits PIN codes
• “Siren Type” on page 81: 1, Constant DC Voltage
• “Inhibit alarm report on exit fault” on page 82: Yes
• “Disable tamper report in disarm” on page 82: No
• “Inhibit ext.sir&strobe for disarm tamper” on page 82: Yes
• “ATS system code” on page 82: 00000
• “ACPO” on page 83: No
• “EE confirm disable (ACPO)” on page 83: No
• “Engineer reset on ACPO zone B alarm” on page 83: No
• “NFA2P” on page 83: No
• “Installer dual code” on page 84“: Yes
• “Enable buzzer on mains/line fault” on page 84: No
• “Screen saver” on page 85: Yes
• “Enable log limitations” on page 85: Yes
• “Confirm area” on page 85: None