Advisor Master Programming Guide 19
Engineer reset for tampers
NO-Engineer Reset on Tamper
*-Change 0-Skip
Select Yes to enable engineer reset for tamper alarm in this zone. The user can
not arm the area the zone belongs to, until an engineer reset has been
performed.
Yes: Engineer reset enabled for tamper alarms in this zone.
No: No engineer reset.
How to perform an engineer reset
Whenever an engineer reset is required, the panel will display a 4-digit code.
This code is a reference to a special code that can be found in the Titan software
package (menu control) or contact your local distributor.
Disable inhibit
NO-Disable Inhibit
*-Change 0-Skip
If users are allowed to inhibit the zone, select No.
Yes: No inhibit allowed.
No: This zone can be inhibited.
Enable soak test
NO-Enable Soak Test
*-Change 0-Skip
This new option enables the input into soak test mode. The soak period is started
when a zone input is set to ‘soak test’. The period of the soak test is set via menu
Soak test days on page 83 from 0 to 255 days. If the Soak Test days value is set
to 0 then the soak test period is infinite and must be disabled by the user. If an
input is in soak test mode, it does not:
report to central station
activate siren
activate strobe
activate any outputs
But the change of state is logged in the history file with the new events soak
alarm and soak alarm restore. If the zone input does not alarm during the soak
test period, the Enable Soak Test option in that zone input’s database will be
reset when the soak test period has elapsed. The soak period is extended by the
Soak Test days period again if the zone input alarms during the soak test period.
The default is set to No.