Installation guide
22 Advisor Master Programming Guide
Zone event flag
No Zone Event Flag
Event Flag:
You can program event flags that are activated by a zone. Up to 15 event flags
can be assigned to an individual zone.
An event flag is activated when the zone is in alarm (except for the zone event
flag). The circumstances that cause a zone to generate an alarm depend on the
zone type. The event flags activated by an alarm depend on:
• Which event flags have been assigned to the zone.
• Whether the active time of the event flags corresponds with the alarm time.
Event flags can be active:
- 24 hours
- When disarmed only (when one or more of the areas assigned to the zone is
disarmed)
- When armed only (when all the areas assigned to the zone are armed)
• Whether the option “Make all events 24 hour” on page 23 has been set to
Yes. If so, the active period is 24 hours for all event flags.
• Zone types 0, 6, 7, 9, 10, 12, 16, 17, 18, 19, 23, 24, 25, 26, 27, 31, 34, 35, 36,
37, 38, 39, 48, 49, 50, 51,52, 53, 54, and 55 do not activate any of the event
flags.
• Zone types 7, 16, 18, 27, 48, 49, 50, 51, 52, 53, 54, and 55 only activate the
zone event type.
For further information on event flags, see “Event Flags” on page 177.
How to program event flags:
The zone event flag is programmed with a value between 17 and 255.
Note: Event flag numbers 1 to 16 are pre-defined. Do not use these event flags
elsewhere in the system, even if they are not used for zones. See also “Event
Flags” on page 177.
Internal siren event flag
YES-Internal Siren, Program in DB
*-Change 0-Skip
Select if the internal siren event flag should be activated. The Internal siren event
flag is assigned in the Area database.
Yes: The Internal siren event flag specified in the area database is activated
when the zone generates an alarm, and all the areas assigned to the zone are
armed.
No: The Internal siren event flag will not be triggered by an alarm in this zone.