Advisor Master Programming Guide 27
User walk test
YES-User Walk Test
*-Change 0-Skip
Yes: Zone will be configured to be included in the user walk test.
No: Zone will not be configured to be included in the user walk test.
Note: Default will be Yes.
Anti-mask detector
YES-AntiMask Detector
*-Change 0-Skip
When this option is set to Yes, additional alarm windows are monitored for
detector mask and fault conditions.
For EN 50131 Grade 2, the lower alarm window, nominally 2,35 kΩ, is monitored
for a combined masking and fault conditions.
EN 50131 Grade 3 requires a separate detection of mask (nominally 14,7 kΩ)
and fault (nominally 19,4 kΩ) conditions if EOL resistor is set to 4,7 kΩ (provided
in V04.11.xx streams).
Yes: Anti-masking and fault zone monitoring is enabled.
No: Anti-masking and fault zone monitoring is disabled.
Part set zone
Note: this option is not available in firmware versions earlier than 04.10.00
When a zone is programmed for Part set (Yes), it is excluded when the assigned
area is Part set armed.
The normal disarmed conditions, if relevant, will continue to be monitored -
tamper, anti-mask etc.
Notes
If a zone is assigned multiple areas it is not armed until all assigned areas are
armed. If there is a mixture of Part Set and Full Set areas assigned to the
zone, the zone will obey the Part Set condition.
The Part Set exclusion is only available for the zone types listed below. All
other zone types will ignore this function.
The Part Set function works with the following zone types:
2: armed alarm
3: entry exit with arm check
4: access
13: entry/exit (no arm check)
14: access (no arm check)
28: armed alarm with auto-reset
66: final door set