Installation guide
48 Advisor Master Programming Guide
4-DGP database
This menu enables or disables DGP’s (Data Gathering Panels). Also the type of
DGP can be programmed.
DGPs to be polled
1, 2, 3: 4
Poll DGP:
Each DGP has to be polled, in order to be able to exchange data with the ATS
control panel. Add DGP’s for polling by entering the dipswitch address it has
been given. DGP’s that do not have to be polled can be deleted by entering the
dipswitch address again.
The display shows the DGP’s currently recorded. A DGP number followed by a
“,” is online (available) and followed by a “:” is offline (can not be addressed by
the system).
Note: A RAS or DGP being online means it will generate RAS/DGP system
alarms and tamper alarms. When offline, system alarms and tampers will not
occur.
Once the DGP’s to be polled have been programmed and Enter has been
pressed, the DGP to be programmed has to be entered before going further.
Note: The four-door/four-lift DGP’s (ATS125x/ATS1260) must not be addressed
higher than Address 12.
Removing a DGP from the polling list clears all alarms for zones and system
points for that DGP address. If the next DGP address number is not polled,
alarms on any of the 32 zones that belong to the DGP are cleared.
For further information on addresses and numbering, refer to “Zones and Outputs
allocated to DGP’s” (see Advisor Master Installation Guide).
DGP settings
DGP type
Set DGP Type
DGP No:
Standard
Type:
The type of DGP being polled has to be programmed. The available DGP types
are:
• 0-Standard: ATS1201, ATS1210, ATS1220
• 1-Four-door DGP: ATS1250, ATS1251, ATS1252, ATS1253, ATS1254
• 2-Four-lift DGP: ATS1260
• 3-Wireless DGP (433MHz): ATS1230